Bill

Construction Code Amendments
Number
H.B. 65 (2026GS)
Sponsor
Rep. Peterson, Thomas W.
Final action
House/ to Governor 3/17/2026
Outcome
House/ to Governor

Summary

This bill modifies the State Construction Code.

What it does

  • This bill:
  • amends the State Construction Code to address updated standards in the:
  • International Building Code;
  • International Energy Conservation Code;
  • International Existing Building Code;
  • International Fuel Gas Code;
  • International Mechanical Code;
  • International Plumbing Code;
  • International Residential Code; and
  • International Swimming Pool and Spa Code.
  • removes the regulation of water heaters in certain areas; and
  • makes technical and conforming changes.

Every vote on this bill

2026-01-22House Comm - Substitute Recommendation
House Business, Labor, and Commerce Committee
13-0-3ABSENT
2026-01-22House Comm - Favorable Recommendation
House Business, Labor, and Commerce Committee
11-0-5ABSENT
2026-02-03Senate Comm - Substitute Recommendation
Senate Business and Labor Committee
7-0-1not eligible / no record
2026-02-03Senate Comm - Favorable Recommendation
Senate Business and Labor Committee
7-0-1not eligible / no record
2026-02-05Senate/ passed 2nd reading
Senate 3rd Reading Calendar
20-5-4not eligible / no record
2026-02-09House/ concurs with Senate amendment
Senate President
67-2-6YEA
2026-02-06Senate/ passed 3rd reading
Clerk of the House
27-0-2not eligible / no record
2026-01-27House/ passed 3rd reading
Senate Secretary
67-2-6YEA

Bill text

introduced version · official source
45
15A-2-103
15A-3-102
15A-3-103
15A-3-104
15A-3-105
15A-3-106
15A-3-107
15A-3-108
15A-3-110
15A-3-202
15A-3-203
15A-3-204
15A-3-205
15A-3-302
15A-3-303
15A-3-304
15A-3-306
15A-3-313
15A-3-315
15A-3-401
15A-3-402
15A-3-501
15A-3-701
15A-3-801
15A-3-1001
0
Construction Code Amendments
2026 GENERAL SESSION
STATE OF UTAH
Chief Sponsor: Thomas W. Peterson
Senate Sponsor: Evan J. Vickers
LONG TITLE
Committee Note:
 The Business and Labor Interim Committee recommended this bill.
Legislative Vote:
16 voting for
0 voting against
4 absent
General Description:
This bill modifies the State Construction Code.
Highlighted Provisions:
This bill:
amends the State Construction Code to address updated standards in the:
 International Building Code;
International Energy Conservation Code;
International Existing Building Code; 
International Fuel Gas Code; 
International Mechanical Code; 
International Plumbing Code; and
International Residential Code; and
makes technical and conforming changes.
Money Appropriated in this Bill:
None
Other Special Clauses:
None
Utah Code Sections Affected:
AMENDS:
15A-2-103
, as last amended by Laws of Utah 2025, Chapter 532
15A-3-102
, as last amended by Laws of Utah 2024, Chapter 15
15A-3-103
, as last amended by Laws of Utah 2023, Chapters 209, 327
15A-3-104
, as last amended by Laws of Utah 2023, Chapter 209
15A-3-105
, as last amended by Laws of Utah 2025, Chapter 532
15A-3-106
, as last amended by Laws of Utah 2016, Chapter 249
15A-3-107
, as last amended by Laws of Utah 2023, Chapter 209
15A-3-108
, as last amended by Laws of Utah 2023, Chapter 209
15A-3-110
, as last amended by Laws of Utah 2019, Chapter 20
15A-3-202
, as last amended by Laws of Utah 2025, Chapter 532
15A-3-203
, as last amended by Laws of Utah 2025, First Special Session, Chapter 15
15A-3-204
, as last amended by Laws of Utah 2024, Chapter 505
15A-3-205
, as last amended by Laws of Utah 2024, Chapter 505
15A-3-302
, as last amended by Laws of Utah 2023, Chapter 209
15A-3-303
, as last amended by Laws of Utah 2023, Chapter 209
15A-3-304
, as last amended by Laws of Utah 2023, Chapter 209
15A-3-306
, as last amended by Laws of Utah 2023, Chapter 209
15A-3-313
, as last amended by Laws of Utah 2023, Chapter 209
15A-3-315
, as last amended by Laws of Utah 2023, Chapter 209
15A-3-401
, as last amended by Laws of Utah 2024, Chapter 505
15A-3-402
, as last amended by Laws of Utah 2024, Chapter 15
15A-3-501
, as last amended by Laws of Utah 2019, Chapter 20
15A-3-701
, as last amended by Laws of Utah 2024, Chapter 505
15A-3-801
, as last amended by Laws of Utah 2024, Chapter 505
15A-3-1001
, as last amended by Laws of Utah 2023, Chapter 209
Be it enacted by the Legislature of the state of Utah:
Section 1. Section 
15A-2-103
 is amended to read:
15A-2-103
. Specific editions adopted of construction code of a nationally 
recognized code authority.
(1)
Subject to the other provisions of this part, the following construction codes are 
incorporated by reference, and together with the amendments specified in Chapter 3, 
Statewide Amendments Incorporated as Part of State Construction Code, and Chapter 4, 
Local Amendments Incorporated as Part of State Construction Code, are the 
construction standards to be applied to building construction, alteration, remodeling, and 
repair, and in the regulation of building construction, alteration, remodeling, and repair 
in the state:
(a)
the 
2021
2024
 edition of the International Building Code, including Appendices C 
and J, issued by the International Code Council;
(b)
the 2021 edition of the International Residential Code, issued by the International 
Code Council;
(c)
Appendix AQ of the 2021 edition of the International Residential Code, issued by the 
International Code Council;
(d)
the 
2021
2024
 edition of the International Plumbing Code, issued by the 
International Code Council;
(e)
the 
2021
2024
 edition of the International Mechanical Code, issued by the 
International Code Council;
(f)
the 
2021
2024
 edition of the International Fuel Gas Code, issued by the International 
Code Council;
(g)
the 2023 edition of the National Electrical Code, issued by the National Fire 
Protection Association;
(h)
the 
2021
2024
 edition of the International Energy Conservation Code, issued by the 
International Code Council;
(i)
the 
2021
2024
 edition of the International Existing Building Code, issued by the 
International Code Council;
(j)
subject to Subsection 
15A-2-104(2)
, the HUD Code;
(k)
subject to Subsection 
15A-2-104(1)
, Appendix AE of the 2021 edition of the 
International Residential Code, issued by the International Code Council;
(l)
subject to Subsection 
15A-2-104(1)
, the 2005 edition of the NFPA 225 Model 
Manufactured Home Installation Standard, issued by the National Fire Protection 
Association;
(m)
subject to Subsection 
(3)
, for standards and guidelines pertaining to plaster on a 
historic property, as defined in Section 
9-8a-302
, the U.S. Department of the Interior 
Secretary's Standards for Rehabilitation and Guidelines for Rehabilitating Historic 
Buildings;
(n)
the residential provisions of the 2021 edition of the International Swimming Pool 
and Spa Code, issued by the International Code Council; and
(o)
Modular Building Institute Standards 1200 and 1205, issued by the International 
Code Council, except as modified by provisions of this title governing modular units.
(2)
Consistent with Title 65A, Chapter 8, Management of Forest Lands and Fire Control, 
the Legislature adopts the 2006 edition of the Utah Wildland Urban Interface Code, 
issued by the International Code Council, with the alternatives or amendments approved 
by the Utah Division of Forestry, Fire, and State Lands, as a construction code that may 
be adopted by a local compliance agency by local ordinance or other similar action as a 
local amendment to the codes listed in this section.
(3)
The standards and guidelines described in Subsection 
(1)(m)
 apply only if:
(a)
the owner of the historic property receives a government tax subsidy based on the 
property's status as a historic property;
(b)
the historic property is wholly or partially funded by public money; or
(c)
the historic property is owned by a government entity.
Section 2. Section 
15A-3-102
 is amended to read:
15A-3-102
. Amendments to Chapters 1 through 3 of IBC.
(1)
IBC, Section 106, is deleted.
(2)
In IBC, Section 110, a new section is added as follows: 
"
110.3.13, Weather-resistant exterior wall envelope. An inspection shall be 
made of the weather-resistant exterior wall envelope as required by Section 1404.2, and 
flashing as required by Section 1404.4 to prevent water from entering the 
weather-resistive barrier."
(3)
IBC, Section 115.1, is deleted and replaced with the following: 
"115.1 Authority. Whenever the building official finds any work regulated by this 
code being performed in a manner either contrary to the provisions of this code or other 
pertinent laws or ordinances or is dangerous or unsafe, the building official is authorized 
to stop work."
(4)
In IBC, Section 202, the following definition is added for Ambulatory Surgical Center: 
"AMBULATORY SURGICAL CENTER. A building or portion of a building 
licensed by the Department of Health and Human Services where procedures are 
performed that may render patients incapable of self preservation where care is less than 
24 hours. See 
Utah Administrative Code 
Utah Administrative Code, 
R432-13."
(5)
In IBC, Section 202, the definition for "
Approved
APPROVED
" is modified by adding 
the words "or independent third-party licensed engineer or architect and submitted to the 
building official" after the word "official."
(6)
In IBC, Section 202, the definition for "
Approved Agency
APPROVED AGENCY
" is 
modified by deleting the words "where such agency has been approved by the building 
official."
(7)
In IBC, Section 202, the definition for "
Approved Fabricator
APPROVED 
FABRICATOR
" is modified by adding the words "or approved by the state of Utah or a 
licensed engineer" after the word "code."
(8)
In IBC, Section 202, the definition for "
Approved Source
APPROVED SOURCE
" is 
modified by adding the words "or licensed engineer" after the word "official."
(9)
In IBC, Section 202, the following definition is added for Assisted Living Facility, 
Residential Treatment and Support: 
"ASSISTED LIVING FACILITY, RESIDENTIAL TREATMENT AND SUPPORT. A 
residential facility that provides a group living environment for four or more residents licensed 
by the Department of Health and Human Services and provides a protected living arrangement 
for ambulatory, non-restrained persons who are capable of achieving mobility sufficient to exit 
the facility without the physical assistance of another person.
ASSISTED LIVING FACILITY, TYPE I. A residential facility licensed by the 
Department of Health and Human Services that provides a protected living arrangement, 
assistance with activities of daily living, and social care to two or more ambulatory, 
non-restrained persons who are capable of mobility sufficient to exit the facility without the 
assistance of another person.
ASSISTED LIVING FACILITY, TYPE II. A residential facility licensed by the 
Department of Health and Human Services that provides an array of coordinated supportive 
personal and health care services to two or more residents who are:
(i) Physically disabled but able to direct his or her own care; or
(ii) Cognitively impaired or physically disabled but able to evacuate from the facility, or to 
a zone or area of safety, with the physical assistance of one person.
ASSISTED LIVING FACILITY, LIMITED CAPACITY. A Type I or Type II assisted 
living facility having two to five residents.
ASSISTED LIVING FACILITY, SMALL. A Type I or Type II assisted living facility 
having six to sixteen residents.
ASSISTED LIVING FACILITY, LARGE. A Type I or Type II assisted living facility 
having more than sixteen residents."
(10)
In IBC, Section 202, the following definition is added for ballistic glass:
"BALLISTIC GLASS. Glass certified at a minimum level of:
(i) Underwriters Laboratories Standard UL752-23, Standard for Bullet-Resisting 
Equipment, Threat Level UL-RF-E from Table C1 (Legacy Level 7) (2023); or
(ii) ASTM F3279-24, Standard Test Method for Ballistic Resistant Security Glazing 
Materials, Threat and Performance Level 4, Ballistic Test Identity (BTI) R1-T1-C5-21 
under Table 1, Ballistic Criteria (2021)."
(11)
In IBC, Section 202, the following definition is added for 
Child Care Facility
child 
care facility
: 
"CHILD CARE FACILITY. A facility where care and supervision is provided for 
four
five
 or more children for less than 24 hours a day and for direct or indirect 
compensation in place of care ordinarily provided in their home."
(11)
(12)
In IBC, Section 202, the definition for " [A] 
Record Drawings
RECORD 
DRAWINGS
" is modified by deleting the words "a fire alarm system" and replacing 
them with "any fire protection system."
(12)
(13)
In IBC, Section 202, the following definition is added for security glazing:
"SECURITY GLAZING. A clear or tinted durable material applied to glass doors 
and windows that enhances the structural integrity of the glass by preventing it from 
shattering and falling to the ground when impacted by an object and meets the minimum 
standard established by:
(i) ASTM F3561, Standard Test Method for Forced-Entry-Resistance of Fenestration 
Systems After Simulated Active Shooter Attack, minimum level 3 of Table 2, Potential 
Energy of Impactor and Drop Height (2023); or
(ii) ANSI Z97.1-15(R20) American National Standard for safety glazing materials 
used in buildings safety performance specifications and methods of test, and must meet 
the durability requirements of Sections 5.3 and 5.4."
(14)
In IBC, Section 304.1, the words "and technical colleges who also educate high school 
students as part of their student body" are added after the words "Educational 
occupancies for students above the 12th grade including higher education laboratories."
(13)
(15)
In IBC, Section 305, Sections 305.2 through 305.2.3 are deleted and replaced with 
the following:
"305.2 Group E, child 
day 
care facilities. This group includes buildings and structures or 
portions thereof occupied by 
four
five
 or more children 2 years of age or older who receive 
educational, supervision, child care services or personal care services for fewer than 24 hours 
per day. See Section 429 Day Care, for special requirements for day care.
305.2.1 Within places of religious worship. Rooms and spaces within places of religious 
worship providing such day care during religious functions shall be classified as part of the 
primary occupancy.
305.2.2 Four or fewer children. A facility having four or fewer children receiving such 
day care shall be classified as part of the primary occupancy.
305.2.3 
Four or fewer children in a dwelling unit. A facility such as the above within a 
dwelling unit and having four or fewer children receiving such day care shall be classified as a 
Group R-3 occupancy or shall comply with the International Residential Code
Child day care 
facilities ancillary to the main occupancy. A facility where any number of children receive 
such day care may be classified as an accessory occupancy if the area complies with Section 
508.2
.
305.2.4 
Child day care -- residential child care certificate or a license. Areas used for 
child day care purposes with a residential child care certificate, as described in Utah 
Administrative Code, R430-50, Residential Certificate Child Care, or a residential child care 
license, as described in Utah Administrative Code, R430-90, Licensed Family Child Care, may 
be located in a Group R-2 or R-3 occupancy as provided in Sections 310.3 and 310.4 or shall 
comply with the International Residential Code in accordance with Section R101.2
Four or 
fewer children in a dwelling unit. A facility such as the above within a dwelling unit and 
having four or fewer children receiving such day care shall be classified as a Group R-3 
occupancy or shall comply with the International Residential Code
.
305.2.5 
Child care centers. Each of the following areas may be classified as accessory 
occupancies, if the area complies with Section 508.2:
1. Hourly child care center, as described in Utah Administrative Code, R381-60 Hourly 
Child Care Centers;
2. Child care centers, as described in Utah Administrative Code, R381-100, Child Care 
Centers;
3. Out-of-school-time programs, as described in Utah Administrative Code, R381-70, 
Out of School Time Child Care Programs; and
4. Commercial preschools, as described in Utah Administrative Code, R381-40, 
Commercial Preschool Programs."
Residential child day care. A residential certificate child 
care facility as described in Utah Administrative Code, R430-50, or a licensed family child 
care facility as described in Utah Administrative Code, R430-90, licensed by the Department 
of Health and Human Services shall be classified as a Group R-2 or R-3 occupancy, or shall 
comply with the International Residential Code."
(14)
(16)
In IBC, Table 307.1(1), footnote "d" is added to the row for Explosives, Division 
1.4G in the column titled STORAGE - Solid Pounds (cubic feet).
(15)
(17)
In IBC, Section 308.2, in the list of items under "This group shall include," the 
words "Type-I Large and Type-II Small, see Section 308.2.5" are added after "Assisted 
living facilities."
(16)
(18)
In IBC, Section 308.2.4, all of the words after the first International Residential 
Code are deleted.
(17)
(19)
A new IBC, Section 308.2.5, is added as follows:
"308.2.5 Assisted living facilities. A Type I, Large assisted living facility is classified as 
occupancy Group I-1, Condition 1. A Type II, Small assisted living facility is classified as 
occupancy Group I-1, Condition 2. See Section 202 for definitions."
(18)
(20)
IBC, Section 308.3, is deleted and replaced with the following: 
"308.3 Institutional Group I-2. Institutional Group I-2 occupancy shall include buildings 
and structures used for medical care on a 24-hour basis for more than four persons who are 
incapable of self-preservation. This group shall include, but not be limited to the following:
Assisted living facilities, Type-II Large, see Section 308.3.3
Child care facilities
Foster care facilities
Detoxification facilities
Hospitals
Nursing homes (both intermediate care facilities and skilled nursing facilities)
Psychiatric hospitals"
(19)
(21)
In IBC, Section 308.3.2, 
the number "five" is deleted and replaced with the 
number "four" in each location
all the wording following the word "Group" is deleted 
and replaced with the words "R-4 Condition 2."
.
(20)
(22)
A new IBC, Section 308.3.3, is added as follows:
"308.3.3 Assisted living facilities. A Type-II, Large assisted living facility is classified 
as occupancy Group I-2, Condition 1. See Section 202 for definitions."
(21)
(23)
In IBC, Section 308.5, the words "more than five" are deleted and replaced with 
the words "five or more in each location."
(22)
(24)
IBC, Section 308.5.1, is deleted and replaced with the following:
"308.5.1 Classification as Group E. A child day care facility that provides care for five 
or more but not more than 100 children under two years of age, where the rooms in which the 
children are cared for are located on a level of exit discharge serving such rooms and each of 
these child care rooms has an exit door directly to the exterior, shall be classified as a Group E. 
See Section 429 for special requirements for Day Care."
(23)
(25)
In IBC, 
Sections
Section
 308.5.3
 and 308.5.4
, the words "five or fewer" are 
deleted and replaced with the words "four or fewer" in each location and the following 
sentence is added at the end: 
"See Section 429 for special requirements for Day Care."
(26)
IBC, Section 308.5.4, is deleted and replaced with the following:
"308.5.4 Child day care facilities ancillary to the main occupancy. A facility 
where any number of children receive such day care may be classified as an accessory 
occupancy if the area complies with Section 508.2."
(27)
A new IBC Section 308.5.5 is added as follows:
"308.5.5 Four or fewer persons receiving care in a dwelling-unit. A facility such 
as the above within a dwelling unit and having four or fewer persons receiving custodial 
care shall be classified as a Group R-3 occupancy or shall comply with the International 
Residential Code."
(24)
(28)
IBC, Section 310.4, is deleted and replaced with the following:
"310.4 Residential Group R-3. Residential Group R-3 occupancies 
and single family 
dwellings complying with the International Residential Code 
where the occupants are 
primarily permanent in nature
, are children receiving child day care services,
 and 
are 
not 
classified as Group R-1, R-2, R-4 or I, including:
Assisted Living Facilities, Type-I, limited capacity, see Section 310.5.3
Buildings that do not contain more than two dwellings
Care facilities, other than child care, that provide accommodations for five or fewer 
persons receiving care
Child day care facilities having four or fewer children receiving care in a dwelling
Residential child day care facilities licensed by the Utah Department of Health and 
Human Services as a:
Residential certificate child care facility
Licensed family child care facility
Congregate living facilities (nontransient) with 16 or fewer occupants
Boarding houses (nontransient)
Convents
Dormitories
Fraternities and sororities
Monasteries
Congregate living facilities (transient) with 10 or fewer occupants
Boarding houses (transient)
Lodging houses (transient) with five or fewer guest rooms and 10 or fewer occupants"
(25)
(29)
IBC, Section 310.4.1, is deleted and replaced with the following:
"310.4.1 Care facilities within a dwelling. Care facilities, other than child care, for five 
or fewer persons receiving care that are within a single family dwelling are permitted to 
comply with the International Residential Code. See Section 429 for special requirements for 
Child Day Care."
(26)
(30)
A new IBC Section 310.4.3 is added as follows: 
" 
"
310.4.3 Child Care. Areas used for child care purposes may be located in a residential 
dwelling unit under all of the following conditions and Section 429:
1. Compliance with Utah Administrative Code, R710-8, Day Care Rules, as enacted 
under the authority of the Utah Fire Prevention Board.
2. Use is approved by the Department of Health and Human Services, as enacted under 
the authority of the Utah Code, Title 26B, Chapter 2, Part 4, Child Care Licensing, and in any 
of the following categories:
a. Utah Administrative Code, R430-50, Residential Certificate Child Care.
b. Utah Administrative Code, R430-90, Licensed Family Child Care.
3. Compliance with all zoning regulations of the local regulator."
(27)
(31)
A new IBC, Section 310.4.4, is added as follows: 
"310.4.4 Assisted living facilities. Type I assisted living facilities with two to five 
residents are Limited Capacity facilities classified as a Residential Group R-3 occupancy 
or are permitted to comply with the International Residential Code. See Section 202 for 
definitions."
(28)
(32)
A new IBC, Section 310.4.5, is added as follows:
"310.4.5 Child day care facilities ancillary to the main occupancy. Child day care 
facilities may be classified as accessory occupancies if the area complies with Section 
508.2."
(33)
In IBC, Section 310.5, the words "Type II Limited Capacity and Type I Small, see 
Section 310.5.3" are added after the words "assisted living facilities."
(29)
(34)
A new IBC, Section 310.5.3, is added as follows: 
"310.5.3 Group R-4 Assisted living facility occupancy groups. The following 
occupancy groups shall apply to Assisted Living Facilities: Type II Assisted Living 
Facilities with two to five residents are Limited Capacity Facilities classified as a 
Residential Group R-4, Condition 2 occupancy. Type I assisted living facilities with six 
to 
sixteen
16
 residents are Small Facilities classified as Residential Group R-4, 
Condition 1 occupancies. See Section 202 for definitions."
Section 3. Section 
15A-3-103
 is amended to read:
15A-3-103
. Amendments to Chapters 4 through 6 of IBC.
(1)
IBC Section 403.5.5
 is deleted.
(2)
In 
IBC, Section 404.5
, Exception 2.3 is added as follows:
"2.3 The atrium does not contain any means of egress component above the two lowest 
stories."
(3)
In 
IBC, Section 407.2.5
, the words "and assisted living facility" are added in the title 
and first sentence after the words "nursing home."
(4)
In 
IBC, Section 407.2.6
, the words "and assisted living facility" are added in the title 
after the words "nursing home."
(5)
In 
IBC, Section 407.3.1.1
, Item 3 is deleted and replaced with the following:
"3. To provide makeup air for exhaust systems in accordance with Section 1020.6, 
Exception 1, doors to toilet rooms, bathrooms, shower rooms, sink closets, and similar 
auxiliary spaces that do not contain flammable or combustible materials are permitted to have 
louvers or an undercut of 2/3 inch (19.1 mm) maximum."
(6)
In 
IBC, Section 407.4.1
, Exception 3 is added as follows:
"3. Only one exit access with direct access to a corridor is required from an assisted 
living facility, single resident sleeping unit that consists of a living space and one or two 
separate sleeping rooms. For other than closets, toilet and shower rooms, occupants may not be 
required to pass through more than one room before reaching the exit access."
(7)
In 
IBC, Section 407.4.3
, the words "and assisted living facility" are added in the title 
and after the words "nursing home."
(8)
In 
IBC, Section 407.11
, a new exception is added as follows: 
"Exception: An essential electrical system is not required in assisted living 
facilities."
(9)
In 
IBC, Section 412.3.1
, a new exception is added as follows: 
"Exception: Aircraft hangars of Type I or II construction that are less than 5,000 
square feet (464.5m2) in area."
(10)
A new 
IBC, Section 422.2.1
,
 is added as follows: 
" 
"
422.2.1 Separations: Ambulatory care facilities licensed by the Department of 
Health and Human Services shall be separated from adjacent tenants with a fire partition 
having a minimum one hour fire-resistance rating. Any level below the level of exit discharge 
shall be separated from the level of exit discharge by a horizontal assembly having a minimum 
one hour fire-resistance rating.
Exception: A fire barrier is not required to separate the level of exit discharge when:
1. Such levels are under the control of the Ambulatory Care Facility.
2. Any hazardous spaces are separated by horizontal assembly having a minimum one 
hour fire-resistance rating."
(11)
A new
,
IBC Section 429
, Day Care, is added as follows:
"
429.1 
Detailed Requirements. In addition to the occupancy and construction 
requirements in this code, the additional provisions of this section shall apply to all Day Care 
in accordance with Utah Administrative Code R710-8 Day Care Rules
Applicability. The 
provisions of Sections 429.1 through 429.5 and other applicable provisions of this code shall 
apply to all occupancies containing day care facilities
.
429.2 Definitions.
429.2.1 
Authority Having Jurisdiction (AHJ): State Fire Marshal, his duly authorized 
deputies, or the local fire enforcement authority code official
Adult Day Care. Nonresidential 
care and supervision for three or more adults for at least four but less than 24 hours a day and 
that meets the needs of functionally impaired adults through a comprehensive program that 
provides a variety of health, social, recreational and related support services in a protective 
setting. For more information, refer to Utah Administrative Code, R501-13, Adult Day Care
.
429.2.2 
Day Care Facility: Any building or structure occupied by clients of any age 
who receive custodial care for less than 24 hours by individuals other than parents, guardians, 
relatives by blood, marriage or adoption
Commercial Preschool Program. A facility where 
child care is provided for direct or indirect compensation on an ongoing basis in the absence of 
the child's parent for five or more unrelated children between the ages of two and five years 
old, for four or more hours, but not exceeding 24 hours a day, is not on a regular schedule, and 
is in a place other than the provider's or child's home. For more information, refer to Utah 
Administrative Code, R381-40, Commercial Preschool Programs
.
429.2.3 
Day Care Center: Providing care for five or more clients in a place other than 
the home of the person cared for. This would also include Child Care Centers, Out of School 
Time or Hourly Child Care Centers licensed by the Department of Health and Human Services
Hourly Child Care Center. A facility where child care is provided for direct or indirect 
compensation on an ongoing basis in the absence of the child's parent for five or more 
unrelated children, for four or more hours, but not exceeding 24 hours a day, is not on a 
regular schedule, and is in a place other than the provider's or child's home. For more 
information, please refer to Utah Administrative Code, R381-60, Hourly Child Care Centers
.
429.2.4 
Family Day Care: Providing care for clients listed in the following two groups:
Out-of-School-Time Child Care Program. A facility where child care is provided for direct or 
indirect compensation on an ongoing basis in the absence of the child's parent for five or more 
unrelated children who are at least five years of age for less than 24 hours a day, in a place that 
is not the provider's or child's home. For more information refer to Utah Administrative Code, 
R381-70, Out-of-School-Time Child Care Programs.
429.2.4.1 Type 1: Services provided for five to eight clients in a home. This would also 
include a home that is certified by the Department of Health and Human Services as 
Residential Certificate Child Care or licensed as Family Child Care.
429.2.4.2 Type 2: Services provided for nine to sixteen clients in a home with sufficient 
staffing. This would also include a home that is licensed by the Department of Health and 
Human Services as Family Child Care.
429.2.5 
R710-8: Utah Administrative Code, R710-8, Day Care Rules, as enacted under 
the authority of the Utah Fire Prevention Board
Child Care Center. A facility where child care 
is provided in the absence of the child's parent on an ongoing basis for direct or indirect 
compensation for five or more unrelated children of any age for less than 24 hours a day in a 
place that is not the provider's or child's home. For more information refer to Utah 
Administrative Code, R381-100, Child Care Centers.
429.2.6 Residential Certificate Child Care. A facility where child care is provided for 
direct or indirect compensation on an ongoing basis for four or more hours a day but less than 
24 hours a day, for eight or fewer children or up to ten children including the provider's own 
children, of any age within a dwelling that is also the provider's home. For more information, 
refer to Utah Administrative Code, R381-50, Residential Certificate Child Care.
429.2.7 Licensed Family Child Care. A facility where child care is provided for direct or 
indirect compensation on an ongoing basis, in the absence of a child's parent, for four or more 
hours a day but less than 24 hours a day, for nine or more unrelated children of any age, within 
a dwelling that is also the provider's home. For more information, please refer to Utah 
Administrative Code, R381-90, Licensed Family Child Care
.
429.3 
Family Day Care
Day Care Facilities
.
429.3.1 
Family Day Care units shall have on each floor occupied by clients, two 
separate means of egress, arranged so that if one is blocked the other will be available
Detailed 
Requirements. In addition to the occupancy and construction requirements in this code, the 
additional provisions of this section shall apply to all day care in accordance with Utah 
Administrative Code, R710-8, Day Care Rules
.
429.3.2 
Family Day Care units that are located in the basement or on the second story 
shall be provided with two means of egress, one of which shall discharge directly to the outside
Emergency Evacuation. A fire escape plan shall be completed and posted in a conspicuous 
place. All staff shall be trained on the fire escape plan and procedure. Emergency evacuation 
drills shall be completed in accordance with the International Fire Code and Utah 
Administrative Code, R710-8, Day Care Rules
.
429.3.2.1 Residential Certificate Child Care and Licensed Family Child Care with five 
to eight clients in a home, located on the ground level or in a basement, may use an emergency 
escape or rescue window as allowed in IFC, 
Chapter 10
, Section 1030.
429.3.3 
Family Day Care units shall not be located above the second story
Occupancy 
Classification. Buildings or areas within a building containing a commercial preschool 
program, hourly child care center, out-of-school-time child care program or a child care center 
shall comply with the requirements of Group I-4, Group E, or the primary occupancy, 
whichever is applicable for the type of facility. Buildings or areas within a building containing 
a residential certificate child day care or a licensed family child day care shall be classified as 
Residential Group R-3 or shall comply with the International Residential Code
.
429.3.3.1 Child day care facilities having four or fewer children receiving care in a 
dwelling unit may be located in a Group R-2 occupancy.
429.3.4 
In Family Day Care units, clients under the age of two shall not be located 
above or below the first story
Group E Occupancies
.
429.3.4.1 
Clients under the age of two may be housed above or below the first story 
where there is at least one exit that leads directly to the outside and complies with IFC, Section 
1011 or Section 1012 or Section 1027
Stories containing a Group E child day care occupancy 
shall be located at the level of exit discharge
.
429.3.4.2 Child day care spaces for children over the age of two may be located one 
story above the level of exit discharge in buildings equipped with a 903.3.1.1 NFPA 13 
sprinkler system throughout and the building is protected by an automatic fire detection system 
installed in accordance with Section 907.429.3.4.3. All Group E child day care spaces with an 
occupant load of more than 10 shall have a second means of egress. If the second means of 
egress is not an exit door leading directly to the exterior, the room shall have an emergency 
escape and rescue window complying with Chapter 10.
429.3.5 Family Day Care units located in split entry/split level type homes in which 
stairs to the lower level and upper level are equal or nearly equal, may have clients housed on 
both levels when approved by the AHJ.
429.3.6 Family Day Care units shall have a portable fire extinguisher on each level 
occupied by clients, which shall have a classification of not less than 2A:10BC, and shall be 
serviced in accordance with NFPA, Standard 10, Standard for Portable Fire Extinguishers.
429.3.7 Family Day Care units shall have single station smoke detectors in good 
operating condition on each level occupied by clients. Battery operated smoke detectors shall 
be permitted if the facility demonstrates testing, maintenance, and battery replacement to 
insure continued operation of the smoke detectors.
429.3.8 Rooms in Family Day Care units that are provided for clients to sleep or nap, 
shall have at least one window or door approved for emergency escape.
429.3.9 Fire drills shall be conducted in Family Day Care units quarterly and shall 
include the complete evacuation from the building of all clients and staff. At least annually, in 
Type I Family Day Care units, the fire drill shall include the actual evacuation using the escape 
or rescue window, if one is used as a substitute for one of the required means of egress.
429.4 
Day Care Centers
Child day care facilities located in a dwelling
.
429.4.1 
Day Care Centers shall comply with either I-4 requirements or E requirements 
of the IBC, whichever is applicable for the type of Day Care Center
Each story of a dwelling 
used for child day care shall have two separate means of egress placed a distance apart equal to 
but not less than one-half of the length of the maximum overall diagonal dimension of the 
dwelling measured in a straight line between them.
429.4.1.1 Where child day care is located one story above or below the level of exit 
discharge, one of the exits shall discharge directly to the outside.
429.4.1.2 Child day care located on a level of exit discharge may use an emergency 
escape and rescue opening as one of the exits where approved by the authority having 
jurisdiction
.
429.4.2 Emergency Evacuation Drills shall be completed as required in IFC, 
Chapter 4
, 
Section 405.
429.4.3 
Location at grade. Group E child day care centers shall be located at the level 
of exit discharge
Child day care shall not be located on a story more than two stories above 
grade
.
429.4.3.1 Child day care spaces for children over the age of 24 months may be located 
on the second floor of buildings equipped with automatic fire protection throughout and an 
automatic fire alarm system.
429.4.4 
Egress. All Group E child day care spaces with an occupant load of more than 
10 shall have a second means of egress. If the second means of egress is not an exit door 
leading directly to the exterior, the room shall have an emergency escape and rescue window 
complying with Section 1030
Child day care for children under the age of two shall not be 
located on any level other than a level of exit discharge.
429.4.4.1 Child day care for children under the age of two may be located above or 
below the first story where at least one exit leads directly to outside
.
429.4.5 
All Group E Child Day Care Centers shall comply with Utah Administrative 
Code, R430-100 Child Care Centers, R430-60 Hourly Child Care Centers, and R430-70 Out of 
School Time
Child day care facilities located in a split entry or split level type dwelling in 
which stairs to both levels are equal or nearly equal may be located on both levels when 
approved by the authority having jurisdiction
.
429.4.6 Child day care facilities located in a dwelling shall have a portable fire 
extinguisher on each level with a classification of not less than 2A:10BC, and shall be serviced 
in accordance with NFPA 10, Standard for Portable Fire Extinguishers.
429.4.7 Child day care facilities located in a dwelling shall have single station smoke 
detectors in good operating condition on each level.
429.4.8 Rooms that are used for sleeping or napping shall have at least one emergency 
escape and rescue opening.
429.4.9 Fire drills shall be conducted in family day care units quarterly and shall include 
the complete evacuation from the building of all clients and staff. At least annually, in Type I 
family day care units, the fire drill shall include the actual evacuation using the escape or 
rescue window, if one is used as a substitute for one of the required means of egress.
429.5 Requirements for all Day Care.
429.5.1 Heating equipment
, fireplaces, and cooking equipment
 in spaces occupied by 
children shall be provided with partitions, screens, or other means to protect children from hot 
surfaces and open flames.
429.5.2 A fire escape plan shall be completed and posted in a conspicuous place. All 
staff shall be trained on the fire escape plan and procedure."
(12)
In 
IBC, Section 504.4
, a new section is added as follows: 
"504.4.1 Group I-2 Assisted Living Facilities. Notwithstanding the allowable number of 
stories permitted by Table 504.4 Group I-2 Assisted Living Facilities of type VA, construction 
shall be allowed on each level of a two-story building when all of the following apply:
1. The total combined area of both stories does not exceed the total allowable area for a 
one-story, above grade plane building equipped throughout with an automatic sprinkler system 
installed in accordance with Section 903.3.1.1.
2. All other provisions that apply in Section 407 have been provided."
(13)
A new 
IBC, Section 504.5
, is added as follows: 
"504.5 Group 1-2 Secured areas in Assisted Living Facilities. In Type IIIB, IV, 
and V construction, all areas for the use and care of residents required to be secured 
shall be located on the level of exit discharge with door operations in compliance with 
Section 1010.2.14."
Section 4. Section 
15A-3-104
 is amended to read:
15A-3-104
. Amendments to Chapters 7 through 9 of IBC.
(1)
In 
IBC, Section 703.5
, the words "with signs or stenciling" are deleted.
(2)
(1)
IBC, Section (F)
 902.1, is deleted and replaced with the following: 
"(F) 902.1 Pump and riser room size. Fire pump rooms and automatic sprinkler system 
riser rooms shall be designed with adequate space for all installed equipment necessary for the 
installation and to provide sufficient working room around the stationary equipment. 
Clearances around equipment to elements of permanent construction, including other installed 
equipment and appliances, shall be sufficient to allow inspection, service, repair or 
replacement without removing such elements of permanent construction or disabling the 
function of a required fire-resistance-rated assembly and not less than the following minimum 
elements:
902.1.1 A minimum clear and unobstructed distance of 12-inches shall be provided from 
the installed equipment to the elements of permanent construction.
902.1.2 A minimum clear and unobstructed distance of 12-inches shall be provided 
between all other installed equipment and appliances.
902.1.3 A clear and unobstructed width of 36-inches shall be provided in front of all 
installed equipment and appliances, to allow for inspection, service, repair or replacement 
without removing such elements of permanent construction or disabling the function of a 
required fire-resistance-rated assembly."
(3)
(2)
In 
IBC, Section 902
, new sections are added as follows:
"(F) 902.2 Fire pump room. Fire pumps and controllers shall be provided with ready 
access. Fire pump rooms shall be provided with doors and an unobstructed passageway large 
enough to allow for the removal of the largest piece of equipment. The passageway shall have 
a clear width not less than 72 inches. Openings into the room shall be clear and unobstructed, 
with doors swinging in the outward direction from the fire pump room and the opening 
providing a clear width of not less than 68 inches and a clear height of the door opening shall 
not be less than 80 inches. The door shall be permitted to be locked provided that the key is 
available at all times and located in a Key Box in accordance with Section 506 of the 
International Fire Code.
(F) 902.3 Automatic sprinkler riser room. Automatic sprinkler system risers shall be 
provided with ready access. Automatic sprinkler system riser rooms shall be provided with 
doors and an unobstructed passageway large enough to allow for the removal of the largest 
piece of equipment. The passageway shall have a clear width not less than 36 inches. Openings 
into the room shall be clear and unobstructed, with doors swinging in the outward direction 
from the riser room and the opening providing a clear width of not less than 32 inches and a 
clear height of the door opening shall not be less than 80 inches. The door shall be permitted to 
be locked provided that the key is available at all times and located in a Key Box in 
accordance with Section 506 of the International Fire Code.
(F) 902.4 Marking on access doors. Access doors for automatic sprinkler system riser 
rooms and fire pump rooms shall be labeled with an approved sign. The lettering shall be in 
contrasting color to the background. Letters shall have a minimum height of 2 inches (51 mm) 
with a minimum stroke of 3/8 inch (10 mm).
(F) 902.5 Environment. Automatic sprinkler system riser rooms and fire pump rooms 
shall be maintained at a temperature of not less than 40 degrees Fahrenheit (4 degrees Celsius). 
Heating units shall be permanently installed.
(F) 902.6 Lighting. Permanently installed artificial illumination shall be provided in the 
automatic sprinkler system riser rooms and fire pump rooms."
(4)
(3)
IBC, Section (F)
903.2.2, is deleted and replaced with the following:
"(F) 903.2.2 Ambulatory care facilities. An automatic sprinkler system shall be installed 
throughout the building containing an ambulatory care facility where either of the following 
conditions exist at any time.
1. Four or more care recipients are incapable of self-preservation.
2. One or more care recipients that are incapable of self-preservation are located at other 
than the level of exit discharge serving such a facility."
(5)
(4)
IBC, Section (F)
903.2.4, condition 2, is deleted and replaced with the following: 
"2. A Group F-1 fire area is located more than three stories above the lowest level 
of fire department vehicle access."
(6)
(5)
IBC, Section (F)
903.2.7, condition 2, is deleted and replaced with the following: 
"2. A Group M fire area is located more than three stories above the lowest level 
of fire department vehicle access."
(7)
(6)
In 
IBC, Section (F)
903.2.8, the following exceptions are added:
"Exceptions:
1. Detached one- and two-family dwellings and multiple single-family dwellings 
(townhouses) constructed in accordance with the International Residential Code For One- and 
Two-Family Dwellings.
2. Single story Group R-1 occupancies with fire areas not more than 2,000 square feet 
that contain no installed plumbing or heating, where no cooking occurs, and constructed of 
Type I-A, I-B, II-A, or II-B construction.
3. Group R-4 fire areas not more than 4,500 gross square feet and not containing more 
than 16 residents, provided all residents are housed on a level of exit discharge and the 
building is equipped throughout with an approved fire alarm system that is interconnected and 
receives its primary power from the building wiring and a commercial power system."
(8)
(7)
IBC, Section (F)
 903.2.8.1
,
 is deleted.
(9)
(8)
IBC, Section (F)
903.2.9, condition 2, is deleted and replaced with the following: 
"2. A Group S-1 fire area is located more than three stories above the lowest level 
of fire department vehicle access."
(10)
(9)
In 
IBC, Section 905
, a new subsection, Section (F)905.3.9, is added as follows:
"Open Parking Garages. Open parking garages shall be equipped with an approved 
Class 1 manual standpipe system when fire department access is not provided for firefighting 
operations to within 150 feet of all portions of the open parking garage as measured from the 
approved fire department vehicle access. Class 1 manual standpipe shall be accessible 
throughout the parking garage such that all portions of the parking structure are protected 
within 150 feet of a hose connection."
(11)
(10)
In 
IBC, Section (F)
905.8, the exception is deleted and replaced with the following:
"Exception: Where subject to freezing and approved by the fire code official."
(12)
(11)
In 
IBC, Section (F)
907.2.3
,
 Group E is deleted and 
rewritten as follows
replaced with the following
: 
"A manual fire alarm system that initiates the occupant notification signal using an 
emergency voice/alarm communication system that meets the requirements of Section 
(F)
 907.5.2.2, or a manual fire alarm system that initiates an approved audible and visual 
occupant notification signal that meets the requirements of Sections 
(F)
907.5.2.1, 
(F)907.5.2.1.1, (F)907.5.2.1.2, and (F)907.5.2.3, and is installed in accordance with 
Section 
(F)
907.6 shall be installed in Group E occupancies. Where automatic fire 
sprinkler systems or smoke detectors are installed, the fire sprinkler systems and smoke 
detectors shall be connected to the building fire alarm system."
(13)
(12)
In 
IBC, Section (F)
 907.2.3 Group E, Exception 2 is deleted and the remaining 
exceptions are renumbered.
(14)
(13)
In 
IBC, Section (F)
 907.2.3 Group E, renumbered Exception 3.2 is deleted and 
replaced with the following: 
"Exception 3.2 The fire alarm system will activate on fire sprinkler waterflow."
(15)
(14)
In 
IBC, Section (F)
 907.2.3 Group E, new 
sections
Sections
(F)
 907.2.3.1 through 
(F) 907.2.3.7 are added as follows:
"(F) 907.2.3.1 Automatic detection devices that detect smoke shall be installed 
throughout all corridors and spaces open to the corridor at the maximum prescribed spacing of 
thirty feet on center and no more than fifteen feet from the walls or smoke detectors shall be 
installed as required in NFPA, Standard 72, Section 17.7.
(F) 907.2.3.2 Where structures are not protected or are partially protected with an 
automatic fire sprinkler system, approved automatic smoke detectors shall be installed in 
accordance with the complete coverage requirements of NFPA, Standard 72.
(F) 907.2.3.3 An approved key plan drawing and operating instructions shall be posted 
at the main fire alarm panel which displays the location of all alarm zones and if applicable, 
device addresses.
(F) 907.2.3.4 The main panel shall be located in a normally attended area such as the 
main office or lobby. Location of the main panel other than as stated above, shall require the 
review and authorization of the State Fire Marshal Division. Where location as required above 
is not possible, an electronically supervised remote annunciator from the main panel shall be 
located in a supervised area of the building. The remote annunciator shall visually indicate 
system power status, alarms for each zone, and give both visual and audible indication of 
trouble conditions in the system. All indicators on both the main panel and remote annunciator 
shall be adequately labeled.
(F) 907.2.3.5 All system wiring shall be as follows: 
(A) The initiating device circuits shall be designated and installed Class A as 
defined in NFPA, Standard 72.
(B) The notification appliance circuits shall be designated and installed Class A as 
defined in NFPA, Standard 72.
(C) Signaling line circuits shall be designated and installed Class A loop as defined 
in NFPA, Standard 72.
(F) 907.2.3.6 Fan Shutdown shall be as follows:
(A) Fan shut down shall be as required in the International Mechanical Code, 
Chapter 6
, Section 606.
(B) Duct detectors required by the International Mechanical Code, shall be 
interconnected and compatible with the fire alarm system."
(16)
(15)
IBC, Section (F)
 915.2.3 Group E occupancies is deleted and replaced with the 
following:
"(F) 915.2.3 Group E occupancies. Carbon monoxide detectors shall be installed in the 
following areas within Group E occupancies:
(1) Boiler rooms, furnace rooms, and similar rooms, or in adjacent areas where 
carbon monoxide is likely to spread. (The installation of carbon monoxide detectors in boiler 
rooms and furnace rooms may cause a false alarm problem. Installing these detectors in 
adjacent spaces where the carbon monoxide is likely to spread from these spaces may be a 
better option.)
(2) Home economics rooms with gas appliances.
(3) School kitchens with gas appliances. (Commercial kitchens).
(4) Arts rooms and other areas with a gas kiln or open flame.
(5) Gas roof top units, and other carbon monoxide producing HVAC units, one per 
zone. (The zone shall be the area covered by the HVAC unit.)
(6) In areas with gas wall units.
(7) In areas with a gas water heater or boiler.
(8) Areas with a forge or foundry.
(9) Metal shop or auto shop areas or in adjacent areas where carbon monoxide is 
likely to spread. (The installation of carbon monoxide detectors in metal shop or auto shop 
areas may cause a false alarm problem. Installing these detectors in adjacent spaces, i.e. class 
rooms or corridors, where the carbon monoxide is likely to spread from these spaces may be a 
better option.)
(10) Labs with open flame.
(11) HVAC units drawing outside air that could be contaminated with carbon 
monoxide.
(12) Other areas with an open flame or fuel fired appliance.
(F) 915.2.3.1 Carbon monoxide alarm signals shall be automatically transmitted to an 
onsite location that is staffed by school personnel.
Exception: Carbon monoxide alarm signals shall not be required to be automatically 
transmitted to an onsite location that is staffed by school personnel in Group E occupancies 
with an occupant load of 30 or less."
(17)
(16)
A new 
IBC, Section (F)
 915.7 is added as follows:
"(F) 915.7 Carbon monoxide systems in Group E occupancies. Carbon monoxide 
systems may be part of a fire alarm system or standalone system.
(F) 915.7.1 Power and wiring.
(F) 915.7.1.1 Power. Carbon monoxide detection systems shall require a primary and 
secondary power source.
(F) 915.7.1.2 Wiring. Class "A" wiring is required when the carbon monoxide system is 
part of, or connected to, a fire alarm system. Standalone carbon monoxide detection systems 
may use Class "B" wiring. All wiring shall be Class "A" or "B."
(F) 915.7.2 Equipment shut down. Equipment and appliances that are producing carbon 
monoxide shall shut down automatically in the zone involved upon carbon monoxide system 
activation.
(F) 915.7.3 Notification.
(F) 915.7.3.1 Local alarm. Each occupied space shall sound an audible alarm when 
detecting carbon monoxide at a level in excess of 70 ppm for one hour.
(F) 915.7.3.2 General alarm. A blue strobe, visual alarm, is required in a normally 
occupied location, similar to the administrative offices, when carbon monoxide is detected in 
the facility in excess of 70 ppm for one hour.
(F) 915.7.3.2.1 The general alarm shall require a manual reset following an alarm 
activation.
(F) 915.7.3.3 Digital notification. Portable carbon monoxide detectors, with digital read 
out indicating parts per million of carbon monoxide, in a space to determine the level of hazard 
in a given space.
(F) 915.7.4 Monitoring. System monitoring is not required. If the system is monitored, 
the signal should be a supervisory signal indicating carbon monoxide.
(F) 915.7.5 Inspection.
(F) 915.7.5.1 The carbon monoxide detection system shall be tested in the presence of a 
Deputy or Special Deputy of the State Fire Marshal Division. The Deputy shall require "spot 
testing" of the system and its components.
(F) 915.7.5.2 Before requesting final inspection and approval, the installing contractor 
shall test each component of the system and issue a statement of compliance, in writing, to the 
State Fire Marshal Division that the carbon monoxide detection system has been installed in 
accordance with approved plans and has been tested in accordance with the manufacturer's 
specifications, and the appropriate installation standard.
(F) 915.7.5.3 Systems shall be tagged with the State approved tag for fire alarm 
systems, upon final approval and shall be inspected and tagged annually by an individual 
certified as a Master Fire Alarm Technician, by the State Fire Marshal Division.
(F) 915.7.6 Evacuation. The affected area within Group E occupancies shall be 
evacuated when carbon monoxide is detected at a level in excess of 70 ppm for one hour in 
that area."
Section 5. Section 
15A-3-105
 is amended to read:
15A-3-105
. Amendments to Chapters 10 through 12 of IBC.
(1)
In IBC, Section 1010.2.4, number (2), the following is added at the end of the sentence: 
"Blended assisted living facilities shall comply with Section 
1010.2.14.1
1010.2.13.1
."
(2)
A new IBC
,
 Section 
1010.2.14.1
1010.2.13.1,
 is added as follows: 
"1010.2.14.1 
1010.2.13.1 
Blended assisted living facilities. In occupancy Group 
I-1, Condition 2 or Group I-2, a Type-II assisted living facility licensed by the 
Department of Health and Human Services for residents with Alzheimer's or dementia, 
and having a controlled egress locking system to prevent operation from the egress side 
shall be permitted to also house residents without a clinical need for their containment 
where all of the following provisions are met:
(a)
locks in the means of egress comply with all IBC requirements for controlled egress 
doors;
(b)
all residents without a clinical need for their containment shall have the keys, codes, 
or other means necessary to exit the facility, in a manner that is determined by the 
facility operator and communicated to the resident or their legal representative;
(c)
residents or their legal representative acknowledge in writing that they understand 
and agree to living in a facility where egress is controlled; and
(d)
the number of residents housed 
in a smoke compartment 
with controlled egress 
shall not be greater than 30."
(3)
In IBC, Section 1011.5.2, 
exception
Exception
 3 is deleted and replaced with the 
following: 
" 
"
3. In Group R-3 occupancies, within dwelling units in Group R-2 
occupancies, and in Group U occupancies that are accessory to a Group R-3 occupancy, 
or accessory to individual dwelling units in Group R-2 occupancies, the maximum riser 
height shall be 
8
eight
 inches (203 mm) and the minimum tread depth shall be 9 inches 
(229 mm). The minimum winder tread depth at the walk line shall be 10 inches (254 
mm), and the minimum winder tread depth shall be 6 inches (152 mm). A nosing not 
less than 0.75 inch (19.1 mm) but not more than 1.25 inches (32 mm) shall be provided 
on stairways with solid risers where the tread depth is less than 10 inches (254 mm)."
(4)
In IBC, Section 1011.11, a new 
exception
Exception
 6 is added as follows:
 " 
"
6. In occupancies in Group R-3, as applicable in Section 101.2 and in 
occupancies in Group U, which are accessory to an occupancy in Group R-3, as 
applicable in Section 101.2, handrails shall be provided on at least one side of stairways 
consisting of four or more risers."
(5)
In IBC, Section 1025, is deleted.
(6)
In IBC, Section 1104.4, 
exception
Exception
 1.5 is deleted.
(7)
In IBC, Section 1110.4.1(4), the following is added at the end of the sentence:
"as defined in Section 
72-7-502
 of the Utah Code."
Section 6. Section 
15A-3-106
 is amended to read:
15A-3-106
. Amendments to Chapters 13 through 15 of IBC.
(1)
IBC, Chapters 13
, 14, and 15
 and 14
 are not amended.
(2)
In IBC, Section 1512.2, a new Exception 2 is added as follows:
"(2) Any existing layers of polyisocyanurate insulation shall be permitted to 
remain in place if the roof decking is in serviceable condition and the insulation is not 
damaged, deteriorated or water soaked. All other types of roof insulation and any areas 
of damage, deteriorated or water soaked polyisocyanurate insulation are to be removed 
and replaced with new."
Section 7. Section 
15A-3-107
 is amended to read:
15A-3-107
. Amendments to Chapter 16 of IBC.
(1)
In IBC, Table 1604.5, Risk Category III, in the sentence that begins "Group I-2 
Condition 1," a new footnote c is added as follows: "c. Type II Assisted Living 
Facilities that are I-2 Condition 1 occupancy classifications in accordance with Section 
308 shall be Risk Category II in this table."
(2)
(1)
In 
IBC, Section 1605.1
, Exception 2 is deleted and replaced with the following:
"2. Where the allowable stress design load combinations of ASCE 7 Section 2.4 are 
used, flat roof snow loads of 
30
45
 pounds per square foot 
(1.44kN/m2) 
(2.15kN/m2) 
or less 
and roof live loads of 
30
45
 pounds per square foot
 (1.44kN/m2) 
 (2.15kN/m2) 
or less need 
not be combined with seismic loads. Where flat roof snow loads exceed 
30
45
 pounds per 
square foot 
(1.44kN/m2)
(2.15kN/m2)
, the snow loads 
may be reduced
shall be
 in 
accordance with the following in load combinations including both snow and seismic loads. S 
as calculated below, shall be combined with seismic loads.
S = 
(0.20 + 0.025 (A-5))
(0.15 + 0.016 (A-5))
Proof, where S shall be greater than or 
equal to 
0.20Proof
0.15 Proof
.
Where:
S = Weight of snow to be used in combination with seismic loads
.
A = Elevation above sea level at the location of the structure (ft/1,000)
Proof = Design roof snow loads, Pf or Ps, psf
For the purpose of this section, snow load shall be assumed uniform on the horizontal 
projection without including the effects of drift or sliding. The
 Importance Factor, I, 
 Risk 
Category factor 
used in calculating Pf may be considered 
1.0
Risk Category II
."
(3)
(2)
In 
IBC, Section 1605.1
 a new 
exception
Exception
4
5
 is added as follows:
"4. 
"5. 
ASCE 
7-16
7-22
 Section 2.3.6 Equation 6 shall be modified to 1.2D + Ev + 
Eh + L +f2S and 1.2D + Ev + Emh + L +f2S with f2 = 
(0.20 +0.025(A-5)) 
f2 = (0.15 + 0.016 
(A-5)) 
where the roof snow load exceeds 
30
45
 pounds per square foot 
(1.44kN/m2)
(2.15kN/m2)
. Where A = Elevation above sea level at the location of the structure (ft/1000). f2 
= 0 for roof snow loads of 
30
45
 pounds per square foot 
(1.44kN/m2) 
(2.15kN/m2) 
or less."
(4)
IBC, Section 1608.1
, is deleted and replaced with the following: "1608.1 General. 
Except as modified in Sections 1608.1.1 and 1608.1.2, design snow loads shall be 
determined in accordance with 
Chapter 7
 of ASCE 7, but the design roof load shall not 
be less than that determined by Section 1607. Where the minimum live load, in 
accordance with Section 1607, is greater than the design roof snow load, the live load 
shall be used for design, but it may not be reduced to a load lower than the design roof 
snow load. Drifting need not be considered for design roof snow loads, less than 20 psf."
(5)
A new 
IBC, Section 1608.1.1
, is added as follows: "1608.1.1 Ice dams and icicles 
along eaves. Section 7.4.5 of 
Chapter 7
 of ASCE 7 referenced in 
IBC Section 1608.1
 is 
deleted and replaced with the following: 7.4.5 Ice Dams and Icicles Along Eaves. 
Where ground snow loads exceed 75 psf, eaves shall be capable of sustaining a 
uniformly distributed load of 2pf on all overhanging portions. No other loads except 
dead loads shall be present on the roof when this uniformly distributed load is applied. 
All building exits under down-slope eaves shall be protected from sliding snow and ice."
(6)
(3)
A new 
IBC, Section 1608.1.2
A new IBC, Section 1608.1.1,
 is added as follows: 
"1608.1.2 
"1608.1.1. 
Drifts on adjacent structures. Section 7.7.2 of ASCE 7 
referenced in 
IBC, Section 1608.1
, is deleted and replaced with the following:
 7.7.2 Adjacent structures. At lower adjacent structures, the requirements of 
Section 7.7.1 shall be used to calculate windward and leeward drifts. The resulting drift 
is permitted to be truncated."
(7)
A new 
IBC, Section 1608.2.1
 is added as follows: "1608.2.1 Utah ground snow loads. 
Section 7.2 of ASCE 7 referenced in 
IBC, Section 1608.1
 is modified as follows:
(a)
In paragraph 1, 7.2-8 is deleted and replaced with 7.2-9.
(b)
On Figure 7.2-1, remove CS and other ground snow load values in the state of Utah. 
Add red shaded region for the state of Utah with the following note: See note for 
Utah.
(c)
The following is added to the Note on Figure 7.2.1: See Table 7.2-9 for Utah.
(d)
Add Table 7.2-9 as follows:
TABLE 7.2-9
GROUND SNOW LOADS FOR SELECTED LOCATIONS IN UTAH
City/Town
County
Ground Snow Load (lb/ft2)
Elevation (ft)
Beaver
Beaver
35
5886
Brigham City
Box Elder
42
4423
Castle Dale
Emery
32
5669
Coalville
Summit
57
5581
Duchesne
Duchesne
39
5508
Farmington
Davis
35
4318
Fillmore
Millard
30
5138
Heber City
Wasatch
60
5604
Junction
Piute
27
6030
Kanab
Kane
25
4964
Loa
Wayne
37
7060
Logan
Cache
43
4531
Manila
Daggett
26
6368
Manti
Sanpete
37
5620
Moab
Grand
21
4029
Monticello
San Juan
67
7064
Morgan
Morgan
52
5062
Nephi
Juab
39
5131
Ogden
Weber
37
4334
Panguitch
Garfield
41
6630
Parowan
Iron
32
6007
Price
Carbon
31
5558
Provo
Utah
31
4541
Randolph
Rich
50
6286
Richfield
Sevier
27
5338
St. George
Washington
21
2585
Salt Lake City
Salt Lake
28
4239
Tooele
Tooele
35
5029
Vernal
Uintah
39
5384
Note: To convert lb/ft2 to kN/m2, multiply by 0.0479. To convert feet to meters, multiply by 0.3048.
1. Statutory requirements of the Authority Having Jurisdiction are not included in this state ground snow load table.
2. For locations where there is substantial change in altitude over the city/town, the load applies at and below the cited elevation, with a tolerance of 100 ft (30 m).
3. For other locations in Utah, see Bean, B., Maguire, M., Sun, Y. (2018), "The Utah Snow Load Study," Utah State University Civil and Environmental Engineering Faculty Publications, Paper 3589, http://utahsnowload.usu.edu/, for ground snow load values."
(8)
(4)
A new 
IBC, Section 1613.1.1
, is added as follows: 
"1613.1.1 Effective Seismic Weight. In ASCE
 7
 12.7.2 and 12.14.8.1 as referenced in 
Section 1613.1, Definition of W, Item 4 is deleted and replaced with the following:
4. Where flat roof snow load, Pf, exceeds 
30 psf (1.44kN/m2)
45 pounds per square 
foot (2.15kN/m2)
, the snow load included in the effective seismic weight shall be calculated, 
in accordance with the following equation: 
Ws = (0.20 + 0.025(A-5))Pf >= 0.20 Pf
Ws=(0.15 
+ 0.016(A-5))Pf >=0.15 Pf
.
WHERE
Where
:
Ws = Weight of snow to be included as effective seismic weight
A = Elevation above sea level at the location of the structure (ft./1,000)
Pf = Design flat roof snow load, psf.
For the purposes of this section, snow load shall be assumed uniform on the horizontal 
projection without including the effects of drift or sliding. The 
Importance Factor, Is,
Risk 
Category factor
 used in calculating Pf may be considered 
1.0
Risk Category II
 for use in the 
formula for Ws."
(5)
A new IBC, Section 1613.1.2, is added as follows:
"1613.1.2 Equivalent Lateral Forces (ELF) Procedure. In ASCE 7 Section 12.8.1.1 
the first paragraph is deleted and replaced with the following: Where the design special 
acceleration parameter Sa determined in accordance with either Section 11.4.5.1 or 
Chapter 21 is available, Method 1 shall be used to determine the seismic response 
coefficient, Cs. Where Exception 2 of Section 11.4.5 applies, Method 1 shall not be 
used. The lower bound for the seismic response coefficient, Cs, provided in Eq.12.8-6 or 
12.8-7 shall be applicable for both Method 1 and Method 2."
Section 8. Section 
15A-3-108
 is amended to read:
15A-3-108
. Amendments to Chapters 17 through 19 of IBC.
(1)
A new IBC, Section 1807.1.6.4, is added as follows: 
"1807.1.6.4 Empirical concrete foundation design. Group R, Division 3 
Occupancies three stories or less in height, and Group U Occupancies, which are 
constructed in accordance with Section 2308, or with other methods employing 
repetitive wood-frame construction or repetitive cold-formed steel structural member 
construction, shall be permitted to have concrete foundations constructed in accordance 
with Table 1807.1.6.4."
(2)
A new IBC, Table 1807.1.6.4 is added as follows:
"TABLE 1807.1.6.4
EMPIRICAL FOUNDATION WALLS (1,7,8)
Max. Height
Top Edge Support
Min.
Thickn ess
Vertic al Steel (2)
Horizon tal Steel (3)
Steel at
Openings (4)
Max. Lintel Length
Min. Lintel Length
2'(610 mm)
None
6"
(5)
2- #4 Bars
2- #4 Bars above
1- #4 Bar each side
1- #4 Bar below
2'(610 mm)
2" for each foot of opening width;
min. 6"
3'(914 mm)
None
6"
#4@3 2"
3- #4 Bars
2- #4 Bars above
1- #4 Bar each side
1- #4 Bar below
2'(610 mm)
2" for each foot of opening width;
min. 6"
4'(1,219 mm)
None
6"
#4@3 2"
4- #4 Bars
2- #4 Bars above
1- #4 Bar each side
1- #4 Bar below
3'(914 mm)
2" for each foot of opening width;
min. 6"
6'(1,829 mm)
Floor or roof Diaphra gm (6)
8"
#4@2 4"
5- #4 Bars
2- #4 Bars above
1- #4 Bar each side
1- #4 Bar below
6'(1,829 mm)
2" for each foot of opening width;
min. 6"
8'(2,438 mm)
Floor or roof Diaphra gm (6)
8"
#4@2 4"
6- #4 Bars
2- #4 Bars above
1- #4 Bar each side
1- #4 Bar below
6'(1,829 mm)
2" for each foot of opening width;
min. 6"
9'(2,743 mm)
Floor or roof Diaphra gm (6)
8"
#4@1 6"
7- #4 Bars
2- #4 Bars above
1- #4 Bar each side
1- #4 Bar below
6'(1,829 mm)
2" for each foot of opening width;
min. 6"
Over 9'(2,743 mm), Engineering required for each column
Footnotes:
(1) Based on 3,000 psi (20.6 Mpa) concrete and 60,000 psi (414 Mpa) reinforcing steel.
(2) To be placed in the center of the wall, and extended from the footing to within three inches (76 mm) of the top of the wall; dowels of #4 bars to match vertical steel placement shall be provided in the footing, extending 24 inches (610 mm) into the foundation wall.
(3) One bar shall be located in the top four inches (102 mm), one bar in the bottom four inches (102 mm) and the other bars equally spaced between. Such bar placement satisfies the requirements of Section 1808.8.6. Corner reinforcing shall be provided so as to lap 24 inches (610 mm).
(4) Bars shall be placed within two inches (51 mm) of the openings and extend 24 inches (610 mm) beyond the edge of the opening; vertical bars may terminate three inches (76 mm) from the top of the concrete.
(5) Dowels of #4 bar at 32 inches on center shall be provided in the footing, extending 18 inches (457 mm) into the foundation wall.
(6) Diaphragm shall conform to the requirements of Section 2308.
(7) Footing shall be a minimum of nine inches thick by 20 inches wide.
(8) Soil backfill shall be soil classification types GW, GP, SW, or SP, per Table 1610.1. Soil shall not be submerged or saturated in groundwater."
(3)
A new
 Section
IBC, Section 1905.1.9
1904.3
, is added as follows:
"1905.1.9 
"1904.3 
ACI 318, Section 19.3.1.1." Modify ACI 318, Table 19.3.1.1 to 
read as follows: In the portion of the table designated as "Conditions", the following Exposure 
category and class is deleted and replaced with the following:
"F0: Concrete elements not exposed to freezing and thawing cycles including footing 
elements, such as footings, tie beams, piles, and pile caps, etc., that are completely buried in 
soil."
(4)
A new IBC, Section 1905.8, is added as follows:
"1905.8 In ACI 318, Section 18.10.3 is deleted and replaced with the following:
18.10.3 Design Forces:
18.10.3.1 Design shear forces for horizontal wall segments, including coupling 
beams, shall be in accordance with 18.10.7.
18.10.3.2 Design shear forces for wall piers shall be in accordance with 18.10.8.
18.10.3.3 Design shear forces for parts of walls not covered by 18.10.3.1 or 18.10.3.2 
shall be in accordance with the requirements of 18.10.3.3.1 through 18.10.3.3.5.
18.10.3.3.1 If the wall design actions are determined in accordance with nonlinear 
dynamic analysis procedures satisfying Appendix A, design forces shall be as 
determined in Appendix A.
18.10.3.3.2 If the design shear force is determined by linear analysis procedures of 
the general building code, it shall be amplified by the product 
v 
v, where 
v and 
v, are 
defined in 18.10.3.3.3 through 18.10.3.3.5.
18.10.3.3.3 
v and 
v, shall be in accordance with Table 18.10.3.3.3. Alternatively, it 
shall be permitted to calculate 
v = Mpr/Mu at the critical section for flexure, where Mpr 
is calculated for axial force that includes the effects of and the expected gravity loads, 
with expected gravity loads in accordance with ASCE/SEI 7 Section 16.3.2.
Table 18.10.3.3.3 Factors 
v and 
v
Condition
v
v
hwcs/lw
1.0
1.0
1.0
1.0 < hwcs/lw < 2.0
Linear interpolation permitted between 1.0 and 1.5
1.0
hwcs/lw 
 2.0
1.5
0.8 + 0.09hn1/3 1.0
18.10.3.3.4 If the general building code includes provision to account for over 
strength of the seismic-force-resisting system, it shall be permitted to take 
v 
v equal to 
o.
18.10.3.3.5 If 3 
v 
v = 
o, it shall be permitted to take the redundancy factor contained 
in the general building code equal to 1.0 for determination of the design shear force."
(5)
A new IBC, Section 1905.9, is added as follows:
"1905.9 In ACI 318, Section 21.2.4.1, the following words are added after the words 
"resist E", except for walls where 
v 
1.5 or if 
v is taken as equal to 
o."
(6)
A new IBC, Section 1909, Modifications to ACI 318, is added as follows:
"1909.1 General. The text of ACI 318 shall be modified as indicated in Sections 
1909.2 through 1909.5.
1909.2 ACI 318 Section 13.2.6.2, For shallow foundation members continuously 
supported by soil and designed based upon the assumption of rigid behavior of the 
shallow member, (a) and (b) shall be permitted:
(a) For one-way shear strength, Vc shall be taken as: Vc = 2
flcbwd.
(b) For two-way shear strength, the size factor, 
s, specified in 22.6 shall be taken 
equal to 1.0.
1909.3 ACI 318, Section 13.3.6.1.1 is added as follows:
13.3.6.1.1 It shall be permitted to calculate Vc for cantilever retaining wall as Vc =2
flcbwd.
1909.4 ACI 318, Section 13.3.7 Basement Walls is added as follows:
13.3.7.1 The design of basement walls to resist out-of-plane lateral earth pressures 
shall satisfy (a) through (e):
(a) Basement walls shall be designed as one-way slabs in accordance with the 
applicable provision of Chapter 7 or as two-way slabs in accordance with the applicable 
provision of Chapter 8.
(b) Basement walls shall be designed to resist hydrostatic pressure, if applicable.
(c) It shall be permitted to calculate the one-way sheer strength of concrete as Vc = 2
flcbwd.
(d) For two-way shear strength, the size effect factor 
s, as specified in 22.6 shall be 
taken equal to 1.0.
(e) Basement walls shall satisfy the applicable provision of Chapter 18.13.3.7.2. For 
loads other than out-of-plane lateral earth pressure, basement walls shall satisfy the 
applicable provisions of Chapter 11." 
(7)
1909.5 ACI 318, Section 22.5.5.1.1, is deleted and replaced with the following:
"22.5.5.1.1 Vc shall not be taken as greater than 5
flcbwd. Vc need not be taken less 
than 
flcbwd except in cases (a) or (b):
(a) elements subject to net axial tension
(b) if Sections 18.6.5.2 or 18.7.6.2.1 apply."
Section 9. Section 
15A-3-110
 is amended to read:
11. Statewide Amendments to the International Wildland-Urban Interface Code 
15A-3-110
. Amendments to Chapters 23 through 25 of IBC.
(1)
A new 
IBC, Section 2306.1.5
IBC, Section 2306.1.6
, is added as follows: 
"2306.1.5 
"2306.1.6 
Load duration factors. 
The allowable stress increase of 1.15 
for snow load, shown in Table 2.3.2, Frequently Used Load Duration Factors, Cd, of the 
National Design Specifications, shall not be utilized at elevations above 5,000 feet 
(1,524 M)."
(2)
In
IBC, Section 2308.3.1
In IBC, Section 2308.7.1
, the words "6 feet (1829 mm)" 
and "4 feet (1219 mm)" are deleted and each replaced with the words "32 inches."
(3)
A new IBC, Section 2406.6, is added as follows:
"2406.6 Glazing in Educational Occupancies (K-12). Exterior entrance level 
windows within 25 feet of an exterior entrance shall have ballistic glass or security 
glazing, extending from ground level to a minimum height of six feet from ground level.
Windows surrounding the interior of the classroom entrance or instructional areas 
shall have ballistic glass or security glazing installed, extending from the floor to a 
minimum height of six feet from the floor.
2406.6.1 Standard for Security Glazing in Educational Occupancies (K-12). For the 
purpose of this section, Ballistic glass is defined as glass certified at a minimum level of:
(i) Underwriters Laboratories Standard UL752-23, Standard for Bullet-Resisting 
Equipment,Threat Level UL-RF-E from Table C1 (Legacy Level) (2023); or
(ii) ASTM F3279-24, Standard Test Methods for Ballistic Resistant Security Glazing 
Materials,Threat and Performance Level 4, Ballistic Test Identity (BTI) R1-T1-C5-2L 
under Table 1,Ballistic Criteria (2021).
Security glazing is defined as a clear or tinted durable material applied to glass doors 
and windows that enhances the structural integrity of the glass by preventing it from 
shattering and falling to the ground when impacted by an object and meets the minimum 
standard established by:
(i) ASTM F3561, Standard Test Method for Forced-Entry-Resistance of Fenestration 
Systems After Simulated Active Shooter Attack, minimum level 3 of Table 2, Potential 
Energy of Impactor and Drop Height (2023); or
(ii) ANSI Z97.1-15 (R20) American National Standards For Safety Glazing Materials 
used in Buildings safety performance specifications and methods of test, must meet the 
durability requirements of Sections 5.3 and 5.4.
References:
Minimum Safety and Security Standards for School Facilities
State Security Chief: Subsections 
53-22-102(3)(b)
 and 
(c)
County Security Chief: Subsection 
53-22-103(2)
State Board of Education Construction Guidelines: Sections 
53E-3-702
; 
53E-3-706
Panic device: Section 56G-8-805"
Section 10. Section 
15A-3-202
 is amended to read:
15A-3-202
. Amendments to Chapters 1 through 5 of IRC.
(1)
In IRC, Section R101.2, Exception, 
the words
the following words are deleted:
"where provided with an automatic sprinkler system complying with Section 
P2904
.
"
 are deleted.
(2)
In IRC, Section R101.2, Exception, 
the words
the following words are added:
"6. A triplex or fourplex of no more than two levels with 2-hour 
fire-resistance-rated vertical shared wall assemblies tested in accordance with ASTM 
E119 or UL263, 1-hour fire-resistance-rated horizontal floor assemblies tested in 
accordance with ASTM E119 or UL263, and independent egress for each unit."
 are 
added.
(3)
In IRC, Section R102, a new Section R102.7.2 is added as follows: 
"R102.7.2 Physical change for bedroom window egress. A structure whose egress 
window in an existing bedroom is smaller than required by this code, and that complied 
with the construction code in effect at the time that the bedroom was finished, is not 
required to undergo a physical change to conform to this code if the change would 
compromise the structural integrity of the structure or could not be completed in 
accordance with other applicable requirements of this code, including setback and 
window well requirements."
(4)
In IRC Section R105.2, under Building, the following changes are made:
(a)
Number 3 is deleted and replaced with the following: 
"3. Retaining walls retaining less than 4 feet (1219mm) of unbalanced fill, 
unless supporting a surcharge or requiring design per Section R404.4."
(b)
Number 10 is deleted and replaced with the following: 
"10. Decks that are not more than 30 inches (762mm) above grade at any point 
and not requiring guardrails, that do not serve exit door required by Section R311.4."
(5)
In IRC, Section R105.2, a new exception is added: 
"11. Grade level, non-connected conex boxes, less than 350 square feet, used for 
storage only."
(6)
In IRC, Section R108.3, the following sentence is added at the end of the section: 
"The building official shall not request proprietary information."
(7)
In IRC, Section 109.1.5, is deleted and replaced with the following: 
"R109.1.5 Other inspections. In addition to the inspections listed in R109.1.1 
through R109.1.4, the building official shall have the authority to inspect the proper 
installation of insulation. R109.1.5.1 Weather-resistant exterior wall envelope 
inspections. An inspection shall be made of the weather-resistant exterior wall envelope 
as required by Section R703.1 and flashings as required by Section R703.4 to prevent 
water from entering the weather-resistive barrier.R109.1.5.2 Fire-resistance-rated 
construction inspection. Where fire-resistance-rated construction is required between 
dwelling units or due to location on property, the building official shall require an 
inspection of such construction after lathing or gypsum board or gypsum panel products 
are in place, but before any plaster is applied, or before board or panel joints and 
fasteners are taped and finished."
(8)
In IRC, Section R202, the following definition is added: 
"ACCESSORY DWELLING UNIT: A habitable living unit created within the 
existing footprint of a primary owner-occupied single-family dwelling."
(9)
In IRC, Section R202, the definition for 
"Approved
"APPROVED
" is modified by 
adding the words "or independent third-party licensed engineer or architect and 
submitted to the building official" after the word "official."
(10)
In IRC, Section R202, the definition for 
"Approved Agency
"APPROVAL AGENCY
" is modified by replacing the word "and" with "or."
(11)
In IRC, Section 202, the definition for "
Approved Source
APPROVED SOURCE
" is 
modified by adding the words "or licensed engineer or architect" after the word 
"official."
(12)
In IRC, Section R202, the following definition is added: 
"CERTIFIED BACKFLOW PREVENTER ASSEMBLY TESTER: A person who 
has shown competence to test Backflow prevention assemblies to the satisfaction of the 
authority having jurisdiction under Utah Code, Subsection 
19-4-104(4)
."
(13)
In IRC, Section R202, the definition of "
Cross Connection
CROSS CONNECTION
" 
is deleted and replaced with the following: 
"CROSS CONNECTION. Any physical connection or potential connection or 
arrangement between two otherwise separate piping systems, one of which contains 
potable water and the other either water of unknown or questionable safety or steam, 
gas, or chemical, whereby there exists the possibility for flow from one system to the 
other, with the direction of flow depending on the pressure differential between the two 
systems (see "Backflow, Water Distribution")."
(14)
In IRC, Section 202, the following definition is added: 
"DUAL SOURCE CONNECTION. A pipe that is installed so that either the 
nonpotable (i.e. secondary) irrigation water or the potable water is connected to a 
pressurized irrigation system at one time, but not both at the same time; or a pipe that is 
installed so that either the potable water or private well water is connected to a residence 
at one time, but not both at the same time. The potable water supply line shall be 
protected by a reduced pressure backflow preventer."
(15)
In IRC, Section 202, the following definition is added: 
"ENERGY STORAGE SYSTEM (ESS). One or more devices, assembled 
together, that are capable of storing energy for supplying electrical energy at a future 
time."
(16)
In IRC, Section 202, in the definition for 
gray water
"GRAY WATER",
 a comma is 
inserted after the word "washers"; the word "and" is deleted; and the following is added 
to the end: 
"and clear water wastes which have a pH of 6.0 to 9.0; are non-flammable; 
non-combustible; without objectionable odors; non-highly pigmented; and will not 
interfere with the operation of the sewer treatment facility."
(17)
In IRC, Section R202, the definition of "
Potable Water
POTABLE WATER
" is 
deleted and replaced with the following: 
"POTABLE WATER. Water free from impurities present in amounts sufficient to 
cause disease or harmful physiological effects and conforming to the Utah Code, Title 
19, Chapter 4, Safe Drinking Water Act, and Title 19, Chapter 5, Water Quality Act, and 
the regulations of the public health authority having jurisdiction."
(18)
In IRC, Figure R301.2 (3), is deleted and replaced with R301.2 (3) as follows:
"TABLE R301.2 (3)
GROUND SNOW LOADS FOR SELECTED LOCATIONS IN UTAH
City/Town
County
Ground Snow Load (lb/ft2)
Elevation (ft)
Beaver
Beaver
35
5886
Brigham City
Box Elder
42
4423
Castle Dale
Emery
32
5669
Coalville
Summit
57
5581
Duchesne
Duchesne
39
5508
Farmington
Davis
35
4318
Fillmore
Millard
30
5138
Heber City
Wasatch
60
5604
Junction
Piute
27
6030
Kanab
Kane
25
4964
Loa
Wayne
37
7060
Logan
Cache
43
4531
Manila
Daggett
26
6368
Manti
Sanpete
37
5620
Moab
Grand
21
4029
Monticello
San Juan
67
7064
Morgan
Morgan
52
5062
Nephi
Juab
39
5131
Ogden
Weber
37
4334
Panguitch
Garfield
41
6630
Parowan
Iron
32
6007
Price
Carbon
31
5558
Provo
Utah
31
4541
Randolph
Rich
50
6286
Richfield
Sevier
27
5338
St. George
Washington
21
2585
Salt Lake City
Salt Lake
28
4239
Tooele
Tooele
35
5029
Vernal
Uintah
39
5384
Note: To convert lb/ft2 to kN/m2, multiply by 0.0479. To convert feet to meters, multiply by 0.3048.1. Statutory requirements of the Authority Having Jurisdiction are not included in this state ground snow load table.
2. For locations where there is substantial change in altitude over the city/town, the load applies at and below the cited elevation, with a tolerance of 100 ft (30 m).
3. For other locations in Utah, see Bean, B., Maguire, M., Sun, Y. (2018), "The Utah Snow Load Study," Utah State University Civil and Environmental Engineering Faculty Publications, Paper 3589, http://utahsnowload.usu.edu/, for ground snow load values."
(19)
In IRC, Section R301.6, is deleted and replaced with the following: 
"R301.6 Utah Snow Loads. The snow loads specified in Table R301.2(5b) shall 
be used for the jurisdictions identified in that table. Otherwise, for other locations in 
Utah, see Bean, B., Maguire, M., Sun, Y. (2018), "The Utah Snow Load Study," Utah 
State University Civil and Environmental Engineering Faculty Publications, Paper 3589, 
http://utahsnowload.usu.edu/, for ground snow load values."
(20)
In IRC, Section R302.2, the following sentence is added at the end of the paragraph: 
"When an access/maintenance agreement or easement is in place, plumbing, 
mechanical ducting, schedule 40 steel gas pipe, and electric service conductors including 
feeders, are permitted to penetrate the common wall at grade, above grade, or below 
grade."
(21)
In IRC, Section R302.3, a new 
exception
Exemption
 3 is added as follows: 
"3. Accessory dwelling units separated by walls or floor assemblies protected by 
not less than 1/2-inch (12.7 mm) gypsum board or equivalent on each side of the wall or 
bottom of the floor assembly are exempt from the requirements of this section."
(22)
In IRC, Section R302.5.1, the last sentence is deleted.
(23)
In IRC, Section R302.13, is deleted.
(24)
In IRC, Section R303.4, the following exception is added: 
"Exception: Dwelling units tested in accordance with Section N1102.4.1.2 
(R402.4.1.2) which has an air tightness of 3.0 ACH (50) or greater do not require 
mechanical ventilation."
(25)
In IRC, Section R310.1, all words in the last sentence after "or to a yard or court", are 
deleted, and Exception 3 of this section is deleted.
(26)
In IRC, Section R310.7, in the exception, the words "or accessory dwelling units" are 
added after the words "sleeping rooms".
(27)
IRC, Sections 
R311.7.45
R311.7.5.1
 through R311.7.5.3, are deleted and replaced with 
the following: 
"
R311.7.45.1 Stair treads and risers. R311.7.5.1 
R311.7.5.1 
Riser height. The 
maximum riser height shall be 8 inches (203 mm). The riser shall be measured vertically 
between leading edges of the adjacent treads. The greatest riser height within any flight of 
stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm).
R311.7.5.2 Tread depth. The minimum tread depth shall be 9 inches (228 mm). The 
tread depth shall be measured horizontally between the vertical planes of the foremost 
projection of adjacent treads and at a right angle to the tread's leading edge. The greatest tread 
depth within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). 
Winder treads shall have a minimum tread depth of 10 inches (254 mm) measured as above at 
a point 12 inches (305 mm) from the side where the treads are narrower. Winder treads shall 
have a minimum tread depth of 6 inches (152 mm) at any point. Within any flight of stairs, the 
greatest winder tread depth at the 12-inch (305 mm) walk line shall not exceed the smallest by 
more than 3/8 inch (9.5 mm).
R311.7.5.3 Nosing. The radius of curvature at the leading edge of the tread shall be no 
greater than 9/16 inch (14.3 mm). A nosing not less than 3/4 inch (19 mm) but not more than 
1 1/4 inches (32 mm) shall be provided on stairways with solid risers. The greatest nosing 
projection shall not exceed the smallest nosing projection by more than 3/8 inch (9.5 mm) 
between two stories, including the nosing at the level of floors and landings. Beveling of 
nosing shall not exceed 1/2 inch (12.7 mm). Risers shall be vertical or sloped from the 
underside of the leading edge of the tread above at an angle not more than 30 degrees (0.51 
rad) from the vertical. Open risers are permitted, provided that the opening between treads 
does not permit the passage of a 4-inch diameter (102 mm) sphere.
Exceptions.
1. A nosing is not required where the tread depth is a minimum of 10 inches (254 mm).
2. The opening between adjacent treads is not limited on stairs with a total rise of 30 
inches (762 mm) or less."
(28)
In IRC, Section R312.2, is deleted.
(29)
In IRC, Sections R313.1 through R313.2.1, are deleted and replaced with the 
following: 
"R313.1 Design and installation. When installed, automatic residential fire 
sprinkler systems for townhouses or one- and two-family dwellings shall be designed 
and installed in accordance with Section P2904 or NFPA 13D."
(30)
In IRC, Section R314.2.2, the words "accessory dwelling units," are added after the 
words "Where alterations, repairs."
(31)
In IRC, Section R315.2.2, the words "accessory dwelling units," are added after the 
words "Where alterations, repairs."
(32)
In IRC, Section 315.3, the following words are added to the first sentence after the 
word "installed": "on each level of the dwelling unit and."
(33)
A new IRC, Section R328.12, is added as follows:
"R328.12 Signage. A sign located on the exterior of the dwelling shall be installed at a 
location approved by the authority having jurisdiction which identifies the battery chemistry 
included in the ESS. This sign shall be of sufficient durability to withstand the environment 
involved and shall not be handwritten."
(34)
In IRC, Section 403.1.3.5.3, an exception is added as follows:
"Exception: Vertical steel in footings shall be permitted to be located while 
concrete is still plastic and before it has set. Where vertical steel resists placement or the 
consolidation of concrete around steel is impeded, the concrete shall be vibrated to 
ensure full contact between the vertical steel and concrete."
(35)
In IRC, Section R403.1.6, a new Exception 3 is added as follows: 
"3. 
When anchor bolt spacing does not exceed 32 inches (813 mm) apart, 
anchor bolts may be placed with a minimum of two bolts per plate section located not 
less than 4 inches (102 mm) from each end of each plate section at interior bearing 
walls, interior braced wall lines, and at all exterior walls."
(36)
In IRC, Section R403.1.6.1, a new exception is added at the end of Item 2 and Item 3 
as follows: 
"Exception: When anchor bolt spacing does not exceed 32 inches (816 mm) apart, 
anchor bolts may be placed with a minimum of two bolts per plate section located not 
less than 4 inches (102 mm) from each end of each plate section at interior bearing 
walls, interior braced wall lines, and at all exterior walls."
(37)
In IRC, Section R404.1, a new exception is added as follows: 
"Exception: As an alternative to complying with Sections R404.1 through 
R404.1.5.3, concrete and masonry foundation walls may be designed in accordance with 
IBC Sections 1807.1.5 and 1807.1.6 as amended in Section 1807.1.6.4 and Table 
1807.1.6.4 under these rules."
(38)
In IRC, Section R405.1, a second exception is added as follows: 
"Exception: When a geotechnical report has been provided for the property, a 
drainage system is not required unless the drainage system is required as a condition of 
the geotechnical report. The geotechnical report shall make a recommendation regarding 
a drainage system."
(39)
In IRC, Section R506.2.3, the words "10-mil (0.010 inch; 0.25 mm)" are deleted and 
replaced with "6-mil (0.006 inch; 0.152 mm)" and the words "conforming to ASTM 
E1745 Class A requirements" are deleted.
(40)
In IRC, Section 507.2.1, Wood materials. The following 
sentence 
is added after the 
words, "in accordance with section R317," "field applied weather resistant barrier 
applied to the top of untreated material,".
Section 11. Section 
15A-3-203
 is amended to read:
15A-3-203
. Amendments to Chapters 6 through 15 of IRC.
(1)
IRC, Section R609.4.1, is deleted.
(2)
IRC, Section R702.7, is deleted.
(2)
(3)
In IRC, Section N1101.4 (R102.1.1), a new section N1101.4.1 (R102.1.1) is added as 
follows: 
"N1101.4.1 National Green Building Standard. Buildings complying with ICC 
700-2020 National Green Building Standard and achieving the Gold rating level for the 
energy efficiency category shall be deemed to exceed the energy efficiency required by 
this code. The building shall also meet the requirements identified in table N1105.2 and 
the building thermal envelope efficiency is greater than or equal to levels of efficiency 
and solar heat gain coefficients (SHGC) in Tables N1102.2.2 and N1102.1.3 of the 2009 
IRC."
(3)
(4)
In IRC, Section N1101.5 (R103.2), all words after the words "herein governed." are 
deleted and replaced with the following: 
"Construction documents include all documentation required for building permits 
shall include only those items specified in Subsection 
10-20-909(12)
 or 
17-79-810(12)
of the Utah Code."
(4)
(5)
In IRC, Section N1101.10.3 (R303.1.3) the following changes are made:
(a)
The following is added at the end of the first sentence "or EN 
14351-1:2006+A1:2010."
(b)
The word "accredited" is replaced with "approved" in the third sentence.
(c)
The following sentence is added after the third sentence: 
"A conversion factor of 5.678 shall be used to convert from U values expressed 
in SI units: ()/53678=."
(d)
After "NFRC 200" the following words are added: "or EN 14351-1:2006+A1:2010," 
and in the sentence the word "accredited" is replaced with the word "approved."
(e)
The following new sentence shall be inserted immediately before the last sentence: 
"Total Energy Transmittance values may be substituted for SHGC, and 
Luminous Transmission values may be substituted for VT."
(5)
(6)
In IRC, Section N1101.12 (R303.3), all wording after the first sentence is deleted.
(6)
(7)
In IRC, Section N1101.13 (R401.2), in the first sentence, the words "Section 
N1101.13.5 and" are deleted.
(7)
(8)
In IRC, Section N1101.13.5 (R401.2.5) is deleted.
(8)
(9)
In IRC, Section N1101.14 (R401.3) Number 7, the words "and the compliance path 
used" are deleted.
(9)
(10)
In IRC, Table N1102.1.2 (R402.1.2):
(a)
in the column titled Fenestration U-Factor the following changes are made:
(i)
in the row titled "Climate Zone 3" delete 0.30 and replace it with 0.32;
(ii)
in the row titled "Climate Zone 5 and Marine 4" delete 0.30 and replace it with 
0.32; and
(iii)
in the row titled "Climate Zone 6" delete 0.30 and replace it with 0.32;
(b)
in the column titled "Glazed Fenestration SHGC", the following change is made: in 
the row titled "Climate Zone 3" delete 0.25 and replace it with 0.35;
(c)
in the column titled "Ceiling U-Factor" the following changes are made:
(i)
in the row titled "Climate Zone 3" delete 0.026 and replace it with 0.030;
(ii)
in the row titled "Climate Zone 5 and Marine 4" delete 0.024 and replace it with 
0.026; and
(iii)
in the row titled "Climate Zone 6" delete 0.024 and replace it with 0.026;
(d)
in the column titled "Wood Frame Wall U Factor", the following changes are made:
(i)
in the row titled "Climate Zone 3" delete 0.060 and replace it with 0.060;
(ii)
in the row titled "Climate Zone 5 and Marine 4" delete 0.045 and replace it with 
0.060; and
(iii)
in the row titled "Climate Zone 6" delete 0.045 and replace it with 0.060;
(e)
in the column titled "Basement Wall U-Factor" the following changes are made:
(i)
in the row titled "Climate Zone 5 and Marine 4" delete 0.050 and replace it with 
0.075; and
(ii)
in the row titled "Climate Zone 6" delete 0.50 and replace it with 0.065; and
(f)
in the column titled "Crawl Space Wall U-Factor" the following changes are made:
(i)
in the row titled "Climate Zone 5 and Marine 4" delete 0.055 and replace it with 
0.078; and
(ii)
in the row titled "Climate Zone 6" delete 0.55 and replace it with 0.065.
(10)
(11)
In IRC, Table N1102.1.3 (R402.1.3), the following changes are made:
(a)
in the column titled "Wood Frame Walls R-Value" a new footnote indicator "j" is 
added and at the bottom of the footnotes the following footnote "j" is added: 
"j. In 
climate zone
Climate Zones
 3B and 5B, an R-15, and in climate zone 6, an 
R-20 shall be acceptable where air-impermeable insulation is installed in the cavity 
space, exterior continuous insulation, or some combination thereof; and the tested 
house air leakage is a maximum of 2.0 ACH50"; and
(b)
add a new footnote "k" as follows: 
"k. Log walls complying with ICC400 and with a minimum average wall 
thickness of 5 inches or greater shall be permitted in Zones 5 through 8 when overall 
window glazing has 0.30 U-factor or lower, minimum heating equipment efficiency 
is for gas 95 AFUE, or for oil, 84 AFUE, and all other components requirements are 
met."
(11)
(12)
In IRC, Table N1102.1.3 (R402.1.3) the following changes are made:
(a)
in the column titled "Fenestration U-Factor" the following changes are made:
(i)
in the row titled "Climate Zone 3" delete 0.30 and replace it with 0.32;
(ii)
in the row titled "Climate Zone 5 and Marine 4" delete 0.30 and replace it with 
0.32; and
(iii)
in the row titled "Climate Zone 6" delete 0.30 and replace it with 0.32;
(b)
in the column titled "Glazed Fenestration SHGC" the following change is made: in 
the row titled "Climate Zone 3" delete 0.25 and replace it with 0.35;
(c)
in the Column R-Value the following changes are made:
(i)
in the row titled "Climate Zone 3" delete 49 and replace it with 38;
(ii)
in the row titled "Climate Zone 5 and Marine 4" delete 60 and replace it with 49; 
and
(iii)
in the row titled "Climate Zone 6" delete 60 and replace it with 49;
(d)
in the Column titled "Wood Frame Wall R-Value" the following changes are made:
(i)
in the row titled "Climate Zone 3" delete all values and replace with 20+Oci or 
13+5ci or 015ci;
(ii)
in the row titled "Climate Zone 5 or Marine 4" delete all values and replace with 
21+Oci or 15+5ci or 0+15ci; and
(iii)
in the row titled "Climate Zone 6" delete all values and replace with 21+Oci or 
15+5ci or 0+15ci;
(e)
in the column titled "Basement Wall R Value" the following changes are made:
(i)
in the row titled "Climate Zone 5 or Marine 4" delete all values and replace with 
15+Oci or 0+11ci or 11+5ci; and
(ii)
in the row titled "Climate Zone 6" delete all values and replace with 19+Oci or 
0+13ci or 11+5ci;
(f)
in the column titled "Slab R Value and Depth" the following changes are made:
(i)
in the row titled "Climate Zone 3" delete 10ci. 2 ft and replace it with NR; and
(ii)
in the row titled "Climate Zone 5 
and 
Marine 4" delete 4 ft and replace it with 
2 ft; and
(g)
in the column titled "Crawl Space Wall R-Value" the following changes are made:
(i)
in the row titled "Climate Zone 5 or Marine 4" delete all values and replace with 
15+Oci or 0+11ci or 11+5ci; and
(ii)
in the row titled "Climate Zone 6" delete all values and replace with 19+Oci or 
0+13ci or 0+11+5ci.
(12)
(13)
In IRC, a new subsection N1102.1.5.1 (R402.1.5.1) is added as follows: 
"1102.1.5.1 (R402.1.5.1) RESCheck 2012 Utah Energy Conservation Code. 
Compliance with section N1102.1.5 (R402.1.5) may be satisfied using the software 
RESCheck 2012 Utah Energy Conservation Code, which shall satisfy the R-value and 
U-factor requirements of N1102.1, N1102.2, and N1102.3, provided the following 
conditions are met:
(a)
in "Climate Zone 5 and 6" the software result shall show 5% better than code; and
(b)
in "Climate Zone 3", the software result shall show 5% better than code when 
software inputs for window U-factor .65 and window SHGC=0.40, notwithstanding 
actual windows installed shall conform to requirements of Tables N1102.1.2 
(R402.1.2) and N1102.1.3 (R402.1.3)."
(13)
(14)
In IRC, Sections N1102.2.1 (R402.2.1), a new Section N1102.2.1.1 is added as 
follows:
"N1102.2.1.1. Unvented attic and unvented enclosed rafter assemblies. Unvented attic 
and unvented enclosed rafter assemblies conforming to Section R806.5 shall be provided with 
an R-value of R-22 (maximum U-Factor of 0.045) in Climate Zone 3-B or an R-value of R-26 
(maximum U-factor of 0.038) in Climate Zones 5-B and 6-B shall be permitted provided all 
the following conditions are met:
1. The unvented attic assembly complies with the requirements of the International 
Residential Code, R806.5.
2. The house shall attain a blower door test result 
 2.5ACH 50.
3. The house shall require a whole house mechanical ventilation system that does not 
rely solely on a negative pressure strategy (must be positive, balanced or hybrid).
4. Where insulation is installed below the roof deck and the exposed portion of roof 
rafters are not already covered by the R-20 depth of the air-impermeable insulation, the 
exposed portion of the roof rafters shall be wrapped (covered) by minimum R-3 unless directly 
covered by drywall/finished ceiling. Roof rafters are not required to be covered by minimum 
R-3 if a continuous insulation is installed above the roof deck.
5. Indoor heating, cooling and ventilation equipment (including ductwork) shall be 
inside the building thermal envelope."
(14)
(15)
In IRC, Section N1102.2.9.1 (R402.2.9.1) the numeral (i) is added before the 
words "cut at a 45 degree" and the following is added after the words "exterior wall": "or 
(ii) lowered from top of slab 4" when a 4" thermal break material such as, but not 
limited to, felt or asphalt impregnated fiber board, with a minimum thickness of 1/4" is 
installed at the upper 4" of slab
.
"
.
(15)
(16)
In IRC, Section N1102.4.1 (R402.4.1), in the first sentence, the word "and" is 
deleted and replaced with the word "or."
(16)
(17)
In IRC, Section N1102.4.1.1 (R402.4.1.1), the last sentence is deleted and 
replaced with the following: 
"Where allowed by the code official, the builder may certify compliance to 
components criteria for items which may not be inspected during regularly scheduled 
inspections."
(17)
(18)
In IRC, Table N1102.4.1.1 (R402.4.1.1) in the column titled "COMPONENT, 
the following changes are made:
(a)
In the row "Rim Joists" the word "exterior" in the first sentence is deleted, and the 
second sentence is deleted.
(b)
In the row "Electrical/phone box on the exterior walls" the last sentence is deleted 
and replaced with: "Alternatively, close cell foam, caulking or gaskets may be used, 
or air sealed boxes may be installed."
(18)
(19)
In IRC, Section N1102.4.1.2 (R402.4.1.2), the following changes are made:
(a)
In the fourth sentence, the word "third" is deleted.
(b)
The following sentence is added after the fourth sentence: 
"The following parties shall be approved to conduct testing: Parties certified by 
BPI or RESNET, or licensed contractors who have completed training provided by 
Blower Door Test equipment manufacturers or other comparable training."
(c)
In the first Exception the second sentence is deleted.
(19)
(20)
IRC, Section N1103.3.3 (R403.3.3), is deleted.
(20)
(21)
IRC Section N1103.3.3.1 (R403.3.3.1) is deleted.
(21)
(22)
In IRC, Section N1103.3.5 (R403.3.5), the following changes are made:
(a)
a second Exception is added as follows: "A duct leakage test shall not be required for 
any system designed such that no air handlers or ducts are located within 
unconditioned attics."; and
(b)
the following is added at the end of the section: 
"The following parties shall be approved to conduct testing:
(i)
Parties certified by BPT or RESNET; and
(ii)
Licensed contractors who have completed training provided by Duct Test 
equipment manufacturers or other comparable training."
(22)
(23)
In IRC, Section N1103.3.6 (R403.3.6) the following changes are made:
(a)
in Subsection 1:
(i)
the number 4.0 is changed to 6.0;
(ii)
the number 113.3 is changed to 170;
(iii)
the number 3.0 is changed to 5.0; and
(iv)
the number 85 is changed to 141;
(b)
in Subsection 2:
(i)
the number 4.0 is changed to 5.0; and
(ii)
the number 113.3 is changed to 141; and
(c)
Subsection 3 is deleted.
(23)
(24)
In IRC, Section N1103.3.7 (R403.3.7) the words "or plenums" are deleted.
(24)
(25)
In IRC, Section N1103.5.1.1 (R403.5.1.1) the words "Where installed" are added 
at the beginning of the first sentence.
(25)
(26)
In IRC, Section N1103.5.2 (R403.5.2) the following change is made, Subsections 
5 and 6 are deleted and Subsection 7 is renumbered to 5.
(26)
(27)
IRC, Section N1103.6.2 (R403.6.2), is deleted and replaced with the following: 
"N1103.6.2 (R403.6.2) Whole-house mechanical ventilation system fan efficacy. Fans 
used to provide whole-house mechanical ventilation shall meet the efficacy requirements of 
Table N1103.6.2 (R403.6.2).
Exception: Where an air handler that is integral to tested and listed HVAC equipment is 
used to provide whole-house mechanical ventilation, the air handler shall be powered by an 
electronically commutated motor."
(27)
(28)
In IRC, Section N1103.6.2 (R403.6.2), the table is deleted and replaced with the 
following:
"TABLE N1103.6.2 (R403.6.2)",
MECHANICAL VENTILATION SYSTEM FAN EFFICACY
FAN LOCATION
AIR FLOW RATE MINIMUM (CFM)
MINIMUM EFFICACY (CFM/WATT)
AIR FLOW RATE MAXIMUM (CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/watt
Any
In-line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
90
Bathroom, utility room
90
2.8 cfm/watt
Any"
(28)
(29)
IRC, Section N1103.6.3 (R403.6.3) is deleted.
(29)
(30)
In IRC, Section N1103.7 (R403.7) the word "approved" is deleted in the first 
sentence and the following is added after the word "methodologies": "complying with 
N1103.7.1 (R403.7.1)
.
"
.
(30)
(31)
A new IRC, Section N1103.7.1 (R403.7.1) is added as follows: 
"N1103.7.1 Qualifications. An individual performing load calculations shall be qualified 
by completing HVAC training from one of the following:
1. HVAC load calculation education from ACCA;
2. A recognized educational institution;
3. HVAC equipment manufacturer's training; or
4. Other recognized industry certification."
(31)
(32)
In IRC, Section N1104.1 (R404.1), the word "All" is replaced with "Not less 
than 90 percent of the lamps in
.
"
.
(32)
(33)
IRC, Section N1104.1.1 (R404.1.1) is deleted.
(33)
(34)
IRC, Section N1104.2 (R404.2) is deleted.
(34)
(35)
IRC, Section N1104.3 (R404.3) is deleted.
(35)
(36)
In IRC, section N1105.2 (R405.2) the following changes are made:
(a)
In Subsection 3, the words "approved by the code official" are deleted; and
(b)
In Subsection 3, the following words are added at the end of the sentence: "when 
applicable and readily available
.
"
.
(36)
(37)
In IRC, Section N1106.3 (R406.3)
,
 "Building thermal envelope" is deleted, and 
replaced with 
the following:
"Building thermal envelope and on-site renewables. The proposed total building 
thermal envelope UA, which is the sum of U-factor times assembly area, shall be less 
than or equal to the building thermal envelope UA using the prescriptive U-factors from 
Table N1102.1.2 multiplied by 1.15 in accordance with Equation 11-4. The 
area-weighted maximum fenestration SHGC permitted in Climate Zones 0 through 3 
shall be: 0.30.UAProposed design =1.15xUAPrescriptive reference design (Equation 
11-4)."
(37)
(38)
In IRC, Section N1106.3.1 (R406.3.1) is deleted.
(38)
(39)
In IRC, Section N1106.3.2 (R403.3.2) is deleted.
(39)
(40)
In IRC, Section N1106.4 (R406.4) the following changes are made:
(a)
In the first sentence, the words "in accordance with Equation 11-5" are deleted and 
replaced with: "permitted to be calculated using the minimum total air exchange rate 
for the rated home (Qtot) and for the index adjustment factor in accordance with 
Equation 11.5.";
(b)
In equation 11-5, the words "Ventilation rate, CFM" are deleted and replaced with: 
"Qtot"; and
(c)
In the last sentence the number "5" is deleted and replaced with "15
.
"
.
(40)
(41)
In IRC
, Section
 N1106.5, in the column titled "ENERGY RATING INDEX" of 
Table R406.5, the following changes are made:
(a)
In the row for "Climate Zone 3", "51" is deleted and replaced with "65";
(b)
In the row for "Climate Zone 5", "55" is deleted and replaced with "69"; and
(c)
In the row for "Climate Zone 6", "54" is deleted and replaced with "68
.
"
.
(41)
(42)
In IRC, Section N1108 (R408) is deleted.
(42)
(43)
In IRC, Section M1401.3 the word "approved" is deleted in the first sentence and 
the following is added after the word 
"
methodologies
", 
"
complying with M1401.3.1
.
"
.
(43)
(44)
A new IRC, Section M1401.3.1, is added as follows: 
"M1401.3.1 Qualifications. An individual performing load calculations shall be qualified 
by completing HVAC training from one of the following:
1. HVAC load calculation education from ACCA;
2. A recognized educational institution;
3. HVAC equipment manufacturer's training; or
4. Other recognized industry certification."
(44)
(45)
In IRC, Section M1402.1, the following is added at the end of the second 
sentence: "or UL/CSA 60335-2-40."
(45)
(46)
In IRC, Section M1403.1, the characters "/ANCE" are deleted.
(46)
(47)
IRC, Section M1411.9, is deleted.
(47)
(48)
In IRC, Section M1412.1, the characters "/ANCE" are deleted.
(48)
(49)
In IRC, Section M1413.1, the characters "/ANCE" are deleted.
Section 12. Section 
15A-3-204
 is amended to read:
15A-3-204
. Amendments to Chapters 16 through 25 of IRC.
(1)
In IRC, Section M1602.2, a new exception is added at the end of Item 7 as follows: 
"Exception: The discharge of return air from an accessory dwelling unit into 
another dwelling unit, or into an accessory dwelling unit from another dwelling unit, is 
not prohibited."
(2)
A new IRC, Section G2401.2, is added as follows: 
"G2401.2 Meter Protection. Fuel gas services shall be in an approved location 
and/or provided with structures designed to protect the fuel gas meter and surrounding 
piping from physical damage, including falling, moving, or migrating ice and snow. If 
an added structure is used, it must provide access for service and comply with the IBC 
or the IRC."
(3)
In IRC, Section 2503.5.1, #2 Air Test is deleted and replaced with the following: 
"Where water is not available at the construction site or where freezing conditions 
limit the use of water on the construction site, plastic drainage and vent pipe may be 
permitted to be tested with air. The following procedures shall be followed:
(a)
Proper personal protective equipment, including safety eyewear and protective 
headgear, should be worn by all individuals in any area where an air or gas test is 
being conducted.
(b)
Contractor shall take all precautions necessary to limit the pressure within the plastic 
piping.
(c)
No drain and vent system shall be pressurized in excess of 6 psi as measured by 
accurate gauges graduated to no more than three times the test pressure.
(d)
The pressure gauge shall be monitored during the test period, which should not 
exceed 15 minutes.
(e)
At the conclusion of the test, the system shall be depressurized gradually, all trapped 
air or gases should be vented, and test balls and plugs should be removed with 
caution."
(4)
In IRC, Section P2503.8, the word "devices" is deleted and replaced with the word 
"assemblies."
(5)
IRC, Section P2503.8.2, is deleted and replaced with the following: 
"P2503.2 Testing. Reduced pressure principle, double check, pressure vacuum 
breaker, reduced pressure detector fire protection, double check detector fire protections, 
and spill-resistant vacuum breaker backflow preventer assemblies shall be tested at the 
time of installation, immediately after repairs or relocation and at least annually. The 
Utah Cross-Connection Control Commission
Utah Division of Water Quality
 has 
adopted the field test procedures published by the Manual of Cross Connection Control, 
Tenth Edition. This manual is published by the University of Southern California's 
Foundation for Cross-Connection Control and Hydraulic Research. Test gauges shall 
comply with ASSE 1064."
Section 13. Section 
15A-3-205
 is amended to read:
15A-3-205
. Amendments to Chapters 26 through 35 of IRC.
(1)
IRC, Section P2602.1, is deleted and replaced with the following: 
"P2602.1 General. The water-distribution system of any building or premises where 
plumbing fixtures are installed shall be connected to a public water supply. Where a potable 
public water supply is not available, individual sources of potable water supply shall be 
utilized provided that the source has been developed in accordance with Utah Code Sections 
73-3-1
, 
73-3-3
, and 
73-3-25
, as administered by the Department of Natural Resources, 
Division of Water Rights. In addition, the quality of the water shall be approved by the local 
health department having jurisdiction. The source shall supply sufficient quantity of water to 
comply with the requirements of this chapter.
Every building in which plumbing fixtures are installed and all premises having drainage 
piping shall be connected to a public sewer where the sewer is accessible and is within 300 
feet of the property line in accordance with Utah Code Section 
10-8-38
, or an approved private 
sewage disposal system in accordance with Utah Administrative Code, Rule R317-4, as 
administered by the Department of Environmental Quality, Division of Water Quality.
Exception: Sanitary drainage piping and systems that convey only the discharge from 
bathtubs, showers, lavatories, clothes washers, and laundry trays shall not be required to 
connect to a public sewer or to a private sewage disposal system provided that the piping or 
systems are connected to a system in accordance with Sections P2910 or P2911."
(2)
A new IRC, Section P2602.3, is added as follows: 
"P2602.3 Individual water supply. Where a potable public water supply is not 
available, individual sources of potable water supply shall be utilized, provided that the 
source has been developed in accordance with Utah Code, Sections 
73-3-1
 and 
73-3-25
, 
as administered by the Department of Natural Resources, Division of Water Rights. In 
addition, the quality of the water shall be approved by the local health department 
having jurisdiction."
(3)
A new IRC, Section P2602.4, is added as follows: 
"P2602.4 Sewer required. Every building in which plumbing fixtures are installed and 
all premises having drainage piping shall be connected to a public sewer where the sewer is 
accessible and is within 300 feet of the property line in accordance with Utah Code, Section 
10-8-38
; or an approved private sewage disposal system in accordance with Utah 
Administrative Code, 
Chapter 4, Rule R317, as administered by the Department of Environmental Quality, 
Division of Water Quality."
(4)
In IRC, Section P2705, Item 5, the words "lavatory" and "lavatories" are deleted.
(5)
In IRC, Section P2705, a new Item 9 is added as follows
 and the remaining item 
numbers are renumbered accordingly
: 
"9. Lavatories. A lavatory shall not be set closer than 12 inches from its center to 
any side wall or partition. A lavatory shall be provided with a clearance of 24 inches in 
width and 21 inches in depth in front of the lavatory to any side wall, partition, or 
obstruction." 
Remaining item numbers are renumbered accordingly.
(6)
In IRC, Section P2801.6.2, the following is added at the end of the section: 
"When permitted by the code official, the pan drain may be directly connected to a 
soil stack, waste stack, or branch drain. The pan drain shall be individually trapped and 
vented as required in Section 907.1. The pan drain shall not be directly or indirectly 
connected to any vent. The trap shall be provided with a trap primer conforming to 
ASSE 1018 or ASSE 1044, a barrier type floor drain trap seal protection device meeting 
ASSE 1072, or a deep seal p-trap."
(7)
A new IRC, Section P2801.6.3, is added as follows: 
"P2801.6.3 Pan designation. A water heater pan shall be considered an emergency 
receptor designated to receive the discharge of water from the water heater only and 
shall not receive the discharge from any other fixtures, devises, or equipment."
(8)
IRC, Section P2801.8, is deleted and replaced with the following: 
"P2801.8 Water heater seismic bracing. As a minimum requirement, water heaters 
shall be anchored or strapped to resist horizontal displacement caused by earthquake 
motion. Strapping shall be at points within the upper one-third and lower one-third of 
the appliance's vertical dimensions.
(9)
In IRC, Section P2804.6.1, a new number 15 is added as follows: 
"15. Be installed in accordance with the manufacturer's installation instructions, not 
to exceed 180 degrees in directional changes."
(10)
A new IRC, Section P2902.1.1, is added as follows:
"P2902.1.1 Backflow assembly testing. Reduced pressure principle, double 
check, pressure vacuum breaker, reduced pressure detector fire protection, double check 
detector fire protection, and spill-resistant vacuum breaker backflow preventer 
assemblies shall be tested at the time of installation, immediately after repairs or 
relocation and at least annually. The Utah 
Cross Connection Control Commission
Division of Water Quality
 has adopted the field test procedures published by the Manual 
of Cross Connection Control, Tenth Edition. This manual is published by the University 
of Southern California's Foundation for Cross-Connection Control and Hydraulic 
Research. Test gauges shall comply with ASSE 1064.
"
(11)
In IRC, Section P2902.1, the following subsections are added as follows:
"P2902.1.1 General Installation Criteria.
Assemblies shall not be installed more than five feet above the floor unless a permanent 
platform is installed. The assembly owner, where necessary, shall provide devices or 
structures to facilitate testing, repair, and maintenance, and to insure the safety of the backflow 
technician.
P2902.1.2 Specific Installation Criteria.
P2902.1.3 Reduced Pressure Principle Backflow Prevention Assembly.
The reduced pressure principle backflow prevention assembly shall be installed as 
follows:
a. The assembly may not be installed in a pit or below grade where the relief port could 
be submerged in water or where fumes could be present at the relief port discharge.
b. The relief valve of the assembly shall not be directly connected to a waste disposal 
line, including a sanitary sewer, a storm drain, or a vent.
c. The assembly shall be installed in a horizontal position only, unless listed or approved 
for vertical installation in accordance with Section 303.4 of the International Plumbing Code 
as amended in Utah Code, Subsection 
15A-3-303
(1).
d. The bottom of the assembly shall be installed a minimum of 12 inches above the floor 
or ground.
e. The body of the assembly shall be a minimum of 12 inches from any wall, ceiling, or 
obstacle, and shall be readily accessible for testing, repair, and maintenance.
P2902.1.4 Double Check Valve Backflow Prevention Assembly.
A double check valve backflow prevention assembly shall be installed as follows:
a. The assembly shall be installed in a horizontal position only, unless listed or approved 
for vertical installation.
b. The bottom of the assembly shall be a minimum of 12 inches above the ground or 
floor.
c. The body of the assembly shall be a minimum of 12 inches from any wall, ceiling, or 
obstacle, and shall be readily accessible for testing, repair, and maintenance.
d. If installed in a pit, the assembly shall be installed with a minimum of 12 inches of 
clearance between all sides of the vault, including the floor and roof or ceiling, with adequate 
room for testing and maintenance.
P2902.1.5 Pressure Vacuum Break Assembly and Spill Resistant Pressure Vacuum 
Breaker Assembly.
A pressure vacuum break assembly or a spill resistant pressure vacuum breaker 
assembly shall be installed as follows:
a. The assembly shall not be installed in an area that could be subject to backpressure or 
back drainage conditions.
b. The assembly shall be installed a minimum of 12 inches above all downstream piping 
and the highest point of use.
c. The assembly shall be a minimum of 12 inches from any wall, ceiling, or obstacle, 
and shall be readily accessible for testing, repair, and maintenance.
d. The assembly shall not be installed below ground, in a vault, or in a pit.
e. The assembly shall be installed in a vertical position."
(12)
In IRC, Table 2903.2, the following changes are made in the column titled 
"MAXIMUM FLOW RATE OR QUANTITY":
(a)
In the row titled "Lavatory faucet" the text is deleted and replaced with "1.5 gpm at 
60 psi
.
"
.
(b)
In the row titled "Shower head" the text is deleted and replaced with "2 gpm at 80 psi
.
"
.
(13)
In IRC, Section P2903.3, the words "public water main or an" are deleted and the 
following sentence is added at the end: 
"A water pressure booster pump may not be connected to a public water main 
unless allowed by Utah Administrative Code, Rule R309-540."
(14)
In IRC, Section 2903.5, at the beginning of the second sentence, insert "If installed,".
(15)
In IRC, Section P2903.9.3, the first sentence is deleted and replaced with the 
following: 
"Unless the plumbing appliance or plumbing fixture has a wall-mount valve, 
shutoff valves shall be required on each fixture supply pipe to each plumbing appliance 
and to each plumbing fixture other than bathtubs and showers."
(16)
IRC, Section P2910.5, is deleted and replaced with the following:
"P2910.5 Potable water connections.
A system that utilizes nonpotable water (i.e., pressurized irrigation) and installs a 
connection to the potable water system for backup must install a Reduced Pressure Principle 
Assembly (RP) directly downstream of the potable water connection (Stop and Waste) and 
install a "dual source connection" directly downstream from the (RP) installed so that either 
the potable water system or the nonpotable water is connected at any time to prevent a direct 
Cross Connection and to protect the potable water from any potential hazard from the 
nonpotable water system. See Utah Code Section 
19-4-112
. Note: RP must be tested within 10 
days of installation and annually whether the drinking water is used or not."
(17)
IRC, Section P2910.9.5, is deleted and replaced with the following:
"P2910.9.5 Makeup water.
Where an uninterrupted nonpotable water supply is required for the intended application, 
potable or reclaimed water shall be provided as a source of makeup water for the storage tank. 
The makeup water supply shall be protected against backflow by means of an air gap not less 
than 4 inches (102 millimeters) above the overflow or by a reduced pressure backflow 
prevention assembly installed in accordance with Section 2902."
(18)
In IRC, Section P2911.12.4, the following words are deleted: "and backwater valves."
(19)
In IRC, Section P2912.15.6, the following words are deleted: "and backwater valves."
(20)
In IRC, Section P3007.3.3.1, the words "stainless steel, cast iron, galvanized steel, 
brass" are added after the word "PE."
(21)
IRC, Section P3009, is deleted and replaced with the following:
"P3009 Graywater soil absorption systems: Graywater recycling systems utilized for 
subsurface irrigation for single-family residences shall comply with the requirements of Utah 
Administrative Code, R317-401, Graywater Systems. Graywater recycling systems utilized for 
subsurface irrigation for other occupancies shall comply with Utah Administrative Code, 
R317-3, Design Requirements for Wastewater Collection, Treatment, and Disposal Systems, 
and Utah Administrative Code, R317-4, Onsite Wastewater Systems."
(22)
In IRC, Section P3101.4, the following sentence is added at the end of the paragraph: 
"Vents extending through the wall shall terminate not less than 12 inches from the 
wall with an elbow pointing downward."
(23)
In IRC, Section P3104.4, the following sentence is added at the end of the paragraph: 
"Horizontal dry vents below the flood level rim shall be permitted for floor drain 
and floor sink installations when installed below grade in accordance with Chapter 30, 
and Sections P3104.2 and P3104.3. A wall cleanout shall be provided in the vertical 
vent."
(24)
In IRC, Section E3401.2, the second sentence is modified by adding the words 
"townhouses"
,
 after the word "dwellings" and the word "their" before the word 
"accessory" and the following is added after "NFPA 70", "such as, but not limited to the 
following equipment:
(a)
fixed outdoor electric deicing and snow-melting equipment;
(b)
motors;
(c)
generators;
(d)
transformers;
(e)
phase converters;
(f)
stationary standby batteries;
(g)
elevators;
(h)
dumbwaiters;
(i)
platform lifts;
(j)
stairway chairlifts;
(k)
electric vehicle power transfer systems;
(l)
electric welders;
(m)
audio signal processing, amplification, and reproduction equipment;
(n)
information technology equipment;
(o)
solar photovoltaic (PV) systems;
(p)
optional standby systems;
(q)
interconnected electric power production sources;
(r)
energy storage systems; and
(s)
energy management systems."
Section 14. Section 
15A-3-302
 is amended to read:
15A-3-302
. Amendments to Chapters 1 and 2 of IPC.
(1)
In IPC, Section 202, the following definition is added: 
"Utah Certified Backflow Preventer Assembly Tester. A person who has shown 
competence to test Backflow prevention assemblies to the satisfaction of the authority 
having jurisdiction under Utah Code, Subsection 
19-4-104(4)
 and Utah Administrative 
Code, R309-305."
(2)
In IPC, Section 202, the definition for "Cross Connection" is deleted and replaced with 
the following: 
"Cross Connection. Any physical connection or potential connection or 
arrangement between two otherwise separate piping systems, one of which contains 
potable water and the other either water of unknown or questionable safety or steam, 
gas, or chemical, whereby there exists the possibility for flow from one system to the 
other, with the direction of flow depending on the pressure differential between the two 
systems (see "Backflow")."
(3)
In IPC, Section 202, the following definition is added: 
"Deep Seal Trap. A manufactured or field fabricated trap with a liquid seal of 4" 
or larger."
(4)
In IPC, Section 202, the definition for "Essentially Nontoxic Transfer Fluid" is deleted and 
replaced with the following:
"ESSENTIALLY NONTOXIC TRANSFER FLUID. Fluids, including propylene 
glycol and mineral oil."
(5)
In IPC, Section 202, the definition for "Essentially Toxic Transfer Fluid" is deleted and 
replaced with the following:
"ESSENTIALLY TOXIC TRANSFER FLUID. Soil, waste, or gray water; and any 
fluid that is not an essentially nontoxic transfer fluid under this code."
(6)
In IPC, Section 202, the following definition is added: 
"Motor Vehicle Waste Disposal Well. An injection well that discharges to the 
subsurface by way of a floor drain, septic system, French drain, dry well, or similar 
system that receives or has received fluid from a facility engaged in vehicular repair or 
maintenance activities, including an auto body repair shop, automotive repair shop, new 
and used car dealership, speciality repair shop, or any other facility that does any 
vehicular repair work. A motor vehicle waste disposal well is subject to rulemaking 
under Section 
19-5-104
 regarding underground injection."
(7)
In IPC, Section 202, the definition for "Potable Water" is deleted and replaced with the 
following: 
"Potable Water. Water free from impurities present in amounts sufficient to cause 
disease or harmful physiological effects and conforming to the Utah Code, 
Title 19, 
Chapter 4, Safe Drinking Water Act
, and 
Title 19, Chapter 5, Water Quality Act
, and the 
regulations of the public health authority having jurisdiction."
(8)
In IPC, Section 202, the following definition is added for 
Dual Source Connection
dual 
source connection
: 
"
Dual Source Connection
DUAL SOURCE CONNECTION
. A pipe that is 
installed so that either the nonpotable (i.e. secondary) irrigation water or the potable 
water is connected to a pressurized irrigation system at one time, but not both at the 
same time; or a pipe that is installed so that either the potable water or private well water 
is connected to a residence at one time, not both at the same time. The potable water 
supply line shall be protected by a reduced pressure backflow preventer."
(9)
In IPC, Section 202, the definition for individual water supply is deleted and replaced 
with the following:
"INDIVIDUAL WATER SUPPLY. A water supply that is not served by a Public 
Water System, as defined by Utah Administrative Code, R309-100."
(10)
In IPC, Section 202, the definition for public water main is deleted and replaced with 
the following:
"PUBLIC WATER MAIN. A water supply pipe owned by a Public Water System, as 
defined in Utah Administrative Code, R309-100."
(11)
In IPC, Section 202, the following definition is added for public water supply:
"PUBLIC WATER SUPPLY. A water supply that is served by a Public Water 
System, as defined in Utah Administrative Code, R309-100."
Section 15. Section 
15A-3-303
 is amended to read:
15A-3-303
. Amendments to Chapter 3 of IPC.
(1)
In IPC, Section 303.4, the following exception is added:
"Exception: Third-party 
standards and 
certification for 
approval of 
backflow prevention 
assemblies 
will
shall
 consist of any combination of two 
certifications, laboratory or field. 
Acceptable third party laboratory certifying agencies are ASSE, IAPMO, and USC-FCCCHR. 
USC-FCCCHR currently provides the only field testing of backflow protection assemblies. 
approvals from a third-party laboratory, and a recognized listed organization that performs a 
laboratory performance evaluation and a one-year field performance evaluation. 
Also see 
www.drinkingwater.utah.gov and Division of Drinking Water Rule, Utah Administrative 
Code, R309-105-12(4)."
(2)
IPC, Section 311.1, is deleted.
(3)
(2)
In IPC, Section 306.2.4, the following sentence is added after the last sentence:
"Access shall be provided to the tracer wire at both ends or both ends of the tracer 
wire shall be terminated at the cleanout."
(3)
In IPC, Section 312.3, the following is added at the end of the paragraph:
"Where water is not available at the construction site or where freezing conditions limit 
the use of water on the construction site, plastic drainage and vent pipe may be permitted to be 
tested with air. The following procedures shall be followed:
1. Contractor shall recognize that plastic is extremely brittle at lower temperatures and 
can explode, causing serious injury or death.
2. Contractor assumes all liability for injury or death to persons or damage to property 
or for claims for labor and/or material arising from any alleged failure of the system during 
testing with air or compressed gasses.
3. Proper personal protective equipment, including safety eyewear and protective 
headgear, should be worn by all individuals in any area where an air or gas test is being 
conducted.
4. Contractor shall take all precautions necessary to limit the pressure within the plastic 
piping.
5. No drain and vent system shall be pressurized in excess of 6 psi as measured by 
accurate gauges graduated to no more than three times the test pressure.
6. The pressure gauge shall be monitored during the test period, which should not 
exceed 15 minutes.
7. At the conclusion of the test, the system shall be depressurized gradually, all trapped 
air or gases should be vented, and test balls and plugs should be removed with caution."
(4)
In IPC, 
Section 312.5
Section 312.6
, the following is added at the end of the paragraph:
"Where water is not available at the construction site or where freezing conditions limit 
the use of water on the construction site, plastic water pipes may be permitted to be tested with 
air. The following procedures shall be followed:
1. Contractor shall recognize that plastic is extremely brittle at lower temperatures and 
can explode, causing serious injury or death.
2. Contractor assumes all liability for injury or death to persons or damage to property 
or for claims for labor and/or material arising from any alleged failure of the system during 
testing with air or compressed gasses.
3. Proper personal protective equipment, including safety eyewear and protective 
headgear, should be worn by all individuals in any area where an air or gas test is being 
conducted.
4. Contractor shall take all precautions necessary to limit the pressure within the plastic 
piping.
5. Water supply systems shall be pressure tested to a minimum of 50 psi but not more 
than 80 psi as measured by accurate gauges graduated to no more than three times the test 
pressure.
6. The pressure gauge shall be monitored during the test period, which should not 
exceed 15 minutes.
7. At the conclusion of the test, the system shall be depressurized gradually, all trapped 
air or gases should be vented, and test balls and plugs should be removed with caution."
(5)
IPC, 
Section 312.10.2
Section 312.11.2
, is deleted and replaced with the following:
"
312.10.2
312.11.2
 Testing. Reduced pressure principle, double check, pressure 
vacuum breaker, reduced pressure detector fire protection, double check detector fire 
protection, and spill-resistant vacuum breaker backflow preventer assemblies shall be tested at 
the time of installation or within 10 days of being placed into service, immediately after repairs 
or relocation and at least annually. The 
Utah Cross Connection Control Commission
Utah 
Division of Water Quality
 has adopted the field test procedures published by the Manual of 
Cross-Connection Control, Tenth Edition. This manual is published by the University of 
Southern California's Foundation for Cross-Connection Control and Hydraulic Research. Test 
gauges shall comply with ASSE 1064."
(6)
A new IPC, 
Section 312.10.3
Section 312.11.3
, is added as follows: 
 "
312.10.3
312.11.3
 Tester Qualifications. Testing shall be performed by a Utah 
Certified Backflow Assembly Tester in accordance with Utah Administrative Code, 
R309-305."
Section 16. Section 
15A-3-304
 is amended to read:
15A-3-304
. Amendments to Chapter 4 of IPC.
(1)
In IPC, Table 403.1, the following changes are made:
(a)
In row number "3", for in the field for "OTHER", a new footnote h is added.
(b)
In row number "5", for "Adult day care and child day care" occupancy, in the field 
for "OTHER", a new footnote h is added.
(c)
Footnote f is deleted and replaced with the following: "FOOTNOTE f: The required 
number and type of plumbing fixtures for outdoor public swimming pools shall be in 
accordance with Utah Administrative Code, R392-302
,
 Design, Construction and 
Operation of Public Pools."
(d)
A new footnote g is added as follows: 
"FOOTNOTE
:
 g: When provided, in public toilet facilities, there shall be an 
equal number of diaper changing facilities in male toilet rooms and female toilet 
rooms. Diaper changing facilities shall meet the requirements of ASTM F2285-04 
(2010) Standard Consumer Safety Performance Specifications for Diaper Changing 
Tables for Commercial Use."
(e)
A new footnote h is added to the table as follows:
"FOOTNOTE h: Non-residential child care facilities shall comply with the 
additional sink requirements of Utah Administrative Code, R381-60-9, Hourly Child 
Care Centers, R381-70-9, Out of School Time Child Care Programs, and 
R381-100-9, Child Care Centers."
(2)
In IPC, Section 403.1.1, Exception 2 is deleted and replaced with the following:
"2. Where multiple-user facilities are designed to serve all genders, the following 
shall apply:
2.1. The maximum fixture count to serve all genders shall be calculated at 50% of the 
total occupant load. The maximum fixture count for the multiple user all gender facility 
shall be calculated at 50% female and 50% male.
2.2 The remaining 50% of the required restroom fixtures shall be provided as 
required by Table 403.1."
(2)
(3)
In IPC, Section 405.3.4, the following sentence is added after the first sentence: 
"For facilities designed for use by all genders in the same room, the partitions of 
the stalls shall extend from the floor to the ceiling."
(3)
(4)
In IPC, Section 405.3.5, the following sentence is added at the end of the first 
paragraph: 
"For facilities designed for use by all genders in the same room, the partitions of 
the stalls shall extend from the floor to the ceiling."
(4)
(5)
A new IPC, Section 406.3, is added as follows: 
"406.3 Automatic clothes washer safe pans. Safe pans, when installed under 
automatic clothes washers, shall be installed in accordance with Section 504.7."
(6)
In IPC, Section 412.2, the following is added at the end of the sentence: "-2020."
(5)
(7)
A new IPC, Section 413.5, is added as follows: 
"413.5 Public toilet rooms. All public toilet rooms shall be equipped with at least 
one floor drain."
(6)
(8)
A new IPC, Section 413.6, is added as follows: 
"Prohibition of motor vehicle waste disposal wells. New and existing motor 
vehicle waste disposal wells are prohibited. A motor vehicle waste disposal well 
associated with a single family residence is not subject to this prohibition."
(7)
(9)
IPC, Section 423.3, is deleted.
Section 17. Section 
15A-3-306
 is amended to read:
15A-3-306
. Amendments to Chapter 6 of IPC.
(1)
IPC, Section 602.3, is deleted and replaced with the following: 
"602.3 Individual water supply. Where a potable public water supply is not 
available, individual sources of potable water supply shall be utilized provided that the 
source has been developed in accordance with Utah Code, Sections 
73-3-1
, 
73-3-3
, and 
73-3-25
, as administered by the Department of Natural Resources, Division of Water 
Rights. In addition, the quality of the water shall be approved by the local health 
department having jurisdiction. The source shall supply sufficient quantity of water to 
comply with the requirements of this chapter."
(2)
IPC, Sections 602.3.1, 602.3.2, 602.3.3, 602.3.4, 602.3.5, and 602.3.5.1, are deleted.
(3)
In IPC, Table 604.4, the following changes are made in the column titled "MAXIMUM 
FLOW RATE OR QUANTITY":
(a)
In the row titled "Lavatory, private" the text is deleted and replaced with "1.5 gpm at 
60 psi
.
"
.
(b)
In the row titled "Shower head" the text is deleted and replaced with "2 gpm at 80 psi
.
"
.
(c)
In the row titled "Urinal" the text is deleted and replaced with "0.5 gallon per 
flushing cycle
.
"
.
(4)
A new IPC, Section 604.4.1, is added as follows: 
"604.4.1 Manually operated metering faucets for food service establishments. 
Self closing or manually operated metering faucets shall provide a flow of water for at 
least 15 seconds without the need to reactivate the faucet."
(5)
IPC, Section 606.5, is deleted and replaced with the following: 
"606.5 Water pressure booster systems. Water pressure booster systems shall be 
provided as required by Section 606.5.1 through 606.5.11."
(6)
In IPC, Section 606.5.1, the words "public water main or" are deleted.
(7)
A new IPC, Section 606.5.11, is added as follows: 
"606.5.11 Water pressure booster pumps connected to a public water main. A 
water pressure booster pump shall not be connected to a public water main unless 
allowed by Utah Administrative Code, Rule R309-540."
(8)
In IPC, Section 608.1, the words "and pollution" are added after the word 
"contamination."
(9)
In IPC, Section 608.1, the following subsections are added as follows:
"608.1.1 General Installation Criteria.
An assembly shall not be installed more than five feet above the floor unless a 
permanent platform is installed. The assembly owner, where necessary, shall provide devices 
or structures to facilitate testing, repair, and maintenance and to insure the safety of the 
backflow technician.
608.1.2 Specific Installation Criteria.
608.1.2.1 Reduced Pressure Principle Backflow Prevention Assembly.
A reduced pressure principle backflow prevention assembly shall be installed as follows:
a. The assembly shall not be installed in a pit or below grade where the relief port could 
be submerged in water or where fumes could be present at the relief port discharge.
b. The relief valve of the assembly shall not be directly connected to a waste disposal 
line, including a sanitary sewer, storm drain, or vent.
c. The assembly shall be installed in a horizontal position, unless the assembly is listed 
or approved for vertical installation in accordance with Section 303.4.
d. The bottom of each assembly shall be installed a minimum of 12 inches above the 
ground or the floor.
e. The body of the assembly shall be a minimum of 12 inches from any wall, ceiling, or 
obstacle, and shall be readily accessible for testing, repair, and maintenance.
608.1.2.2 Double Check Valve Backflow Prevention Assembly.
A double check valve backflow prevention assembly shall be installed as follows:
a. The assembly shall be installed in a horizontal position unless the assembly is listed or 
approved for vertical installation.
b. The bottom of the assembly shall be a minimum of 12 inches above the ground or the 
floor.
c. The body of the assembly shall be a minimum of 12 inches from any wall, ceiling, or 
obstacle, and shall be readily accessible for testing, repair, and maintenance.
d. If installed in a pit, the assembly shall be installed with a minimum of 12 inches of 
clearance around all sides of the vault, including the floor and roof or ceiling, with adequate 
room for testing and maintenance.
608.1.2.3 Pressure Vacuum Breaker Assembly and Spill Resistant Pressure Vacuum 
Breaker Assembly.
A pressure vacuum breaker assembly and spill resistant pressure vacuum breaker 
assembly shall be installed as follows:
a. The assembly shall not be installed in an area that could be subject to backpressure or 
back drainage conditions.
b. The assembly shall be installed a minimum of 12 inches above all downstream piping 
and the highest point of use.
c. The assembly shall be a minimum of 12 inches from any wall, ceiling, or obstacle, 
and shall be readily accessible for testing, repair, and maintenance.
d. The assembly shall not be installed below ground or in a vault or pit.
e. The assembly shall be installed in a vertical position."
(10)
In Table 608.1, under Backflow preventer plumbing devices, the following is added:
Hand-held Showers
High or Low Hazard
Backpressure or Backsiphonage
ASME 112.18.3 or ASSE 1014
(10)
(11)
In IPC, Section 608.3, the word "and" before the word "contamination" is deleted 
and replaced with a comma and the words "
or pollution" are added after the word 
"contamination" in the first sentence.
(11)
(12)
In IPC, Section 608.6, the words "with the potential to create a condition of 
either contamination or pollution or" are added after the word "substances."
(12)
(13)
In IPC, Section 608.7, the following sentence is added at the end of the 
paragraph: 
"Any connection between potable water piping and sewer-connected waste shall 
be protected by an air gap in accordance with Section 608.14.1."
(13)
(14)
IPC, Section 608.8, is deleted and replaced with the following: 
" 608.8 Stop and Waste Valves
"608.8 Stop-and-waste valves
 installed below 
grade. Combination stop-and-waste valves shall be permitted to be installed 
underground or below grade. Freeze proof yard hydrants that drain the riser into the 
ground are considered to be stop-and-waste valves and shall be permitted. A 
stop-and-waste valve shall be installed in accordance with a manufacturer's 
recommended installation instructions."
(14)
(15)
IPC, Section 608.14.3, is deleted and replaced with the following: 
" 
"
608.14.3 Backflow preventer with intermediate atmospheric vent. Backflow preventers 
with intermediate atmospheric vents shall conform to ASSE 1012 or CSA CAN/CSA-B64.3. 
These devices shall be permitted to be installed on residential boilers, without chemical 
treatment, where subject to continuous pressure conditions, and humidifiers in accordance with 
Section 608.17.10. The relief opening shall discharge by air gap and shall be prevented from 
being submerged."
(15)
(16)
IPC, Section 608.14.4, is deleted.
(16)
(17)
IPC, Section 608.16.3, is deleted and replaced with the following: 
" 
"
608.16.3 Protection by a backflow preventer with intermediate atmospheric 
vent. Connections to residential boilers only, without chemical treatment, and 
humidifiers shall be protected by a backflow preventer with an intermediate atmospheric 
vent."
(17)
(18)
IPC, Section 608.16.4, is deleted and replaced with the following: 
" 
"
608.16.4 Protection by a vacuum breaker. Openings and outlets shall be 
protected by atmospheric-type or pressure-type vacuum breakers. Vacuum breakers 
shall not be installed under exhaust hoods or similar locations that will contain toxic 
fumes or vapors. Fill valves shall be set in accordance with Section 415.3.1. 
Atmospheric Vacuum Breakers - The critical level of the atmospheric vacuum breaker 
shall be set a minimum of 6 inches (152 mm) above the flood level rim of the fixture or 
device. Pipe-applied vacuum breakers shall be installed at the highest point, but not less 
than 6 inches (152 mm) above the flood level rim of the fixture, receptor, or device 
served. No valves shall be installed downstream of the atmospheric vacuum breaker. 
The atmospheric vacuum breaker shall not be installed where it may be subjected to 
continuous pressure for more than 12 consecutive hours at any time. Pressure Vacuum 
Breaker - The critical level of the pressure vacuum breaker shall be set a minimum of 12 
inches (304 mm) above the flood level of the fixture device and above all downstream 
piping and the highest point of use."
(18)
(19)
In IPC, Section 608.16.4.2, the following is added after the first sentence: 
"Add-on-backflow prevention devices shall be non-removable. In climates where 
freezing temperatures occur, a listed self-draining frost proof hose bibb with an integral 
backflow preventer shall be used."
(19)
(20)
In IPC, Section 608.17.1.2, the words "or ASSE 1024" are deleted.
(20)
(21)
IPC, Section 608.17.2, is deleted and replaced as follows:
 " 
"
608.17.2 Connections to boilers. The potable supply to a boiler shall be protected 
by an air gap or a reduced pressure principle backflow preventer, complying with ASSE 1013, 
CSA B64.4 or AWWA C511.
Exception: The potable supply to a residential boiler without chemical treatment may be 
equipped with a backflow preventer with an intermediate atmospheric vent complying with 
ASSE 1012, ASSE 1081.1, or CSA CAN/CSA-B64.3."
(21)
(22)
In IPC, Section 608.17.4.1, a new exception is added as follows: 
"Exception: All class 1 and 2 systems containing chemical additives consisting of 
strictly glycerine (C.P. or U.S.P. 96.5 percent grade) or propylene glycol shall be 
protected against backflow with a double check valve assembly or double check valve 
detector assembly. Such systems shall include written certification of the chemical 
additives at the time of original installation and service or maintenance."
(22)
(23)
IPC, Section 608.17.7, is deleted and replaced with the following: 
" 
"
608.17.7 Chemical dispensers. Where chemical dispensers connect to the 
water distribution system, the water supply system shall be protected against backflow 
in accordance with Section 608.14.1, Section 608.14.2, Section 608.14.5, Section 
608.14.6 or Section 608.14.8. Installation shall be in accordance with Section 608.1.2. 
Chemical dispensers shall connect to a separate dedicated water supply line, and not 
downstream of an atmospheric vacuum breaker."
(23)
(24)
IPC, Section 608.17.8, is deleted and replaced with the following: 
" 
"
608.17.8 Portable cleaning equipment. Where the portable cleaning 
equipment connects to the water distribution system, the water supply system shall be 
protected against backflow in accordance with Section 608.14.1 or Section 608.14.2."
(24)
(25)
A new IPC, Section 608.17.11, is added as follows: 
" 
"
608.17.11 Automatic and coin operated car washes. The water supply to an 
automatic or coin operated car wash shall be protected in accordance with Section 
608.14.2."
(25)
(26)
IPC, Section 608.18, is deleted and replaced with the following: 
" 
"
608.18 Protection of individual water supplies. See Section 602.3 for 
requirements."
Section 18. Section 
15A-3-313
 is amended to read:
15A-3-313
. Amendments to Chapter 13 of IPC.
(1)
A new IPC, Section 1301.4.1, is added as follows:
"1301.4.1 Recording.
The existence of a nonpotable water system shall be recorded on the deed of ownership 
for the property. The certificate of occupancy shall not be issued until the documentation for 
the recording required under this section is completed by the property owner."
(2)
IPC, Section 1301.5, is deleted and replaced with the following:
"1301.5 Potable water connections.
Where a potable water system is connected to a nonpotable water system, the potable 
water supply shall be protected against backflow by a reduced pressure backflow prevention 
assembly or an air gap installed in accordance with Section 608."
(3)
In IPC, a new Section 1301.5.1 is added as follows: 
"1301.5.1 Potable water connections. 
A system that utilizes nonpotable water (i.e., pressurized irrigation) and installs a 
connection to the potable water system for backup must install a Reduced Pressure 
Principle Assembly (RP) directly downstream of the potable water connection (Stop and 
Waste) and install a dual source connection directly downstream from the (RP) installed 
so that either the potable water system or the nonpotable water is connected at any time 
to prevent a direct Cross Connection and to protect the potable water from any potential 
hazard from the nonpotable water system. See Utah Code Section 
19-4-112
. Note: RP 
must be tested within 10 days of installation and annually whether the drinking water is 
used or not."
(4)
IPC, Section 1301.9.4, is deleted and replaced with the following:
"
1301.9.4 Makeup water.
Where an uninterrupted supply is required for the intended application, potable or 
reclaimed water shall be provided as a source of makeup water for the storage tank. The 
makeup water supply shall be protected against backflow by a reduced pressure backflow 
prevention assembly or an air gap installed in accordance with Section 608. A full-open valve 
located on the makeup water supply line to the storage tank shall be provided. Inlets to the 
storage tank shall be controlled by fill valves or other automatic supply valves installed to 
prevent the tank from overflowing and to prevent the water level from dropping below a 
predetermined point. Where makeup water is provided, the water level shall not be permitted 
to drop below the source water inlet or the intake of any attached pump."
(5)
IPC, Section 1302.12.4, is deleted and replaced with the following:
"1302.12.4 Inspection and testing of backflow prevention assemblies.
Testing of a backflow preventer shall be conducted in accordance with 
Sections 
312.10.1, 312.10.2, and 312.10.3
Sections 312.11.1 and 312.11.2
."
(6)
IPC, Section 1303.15.6, is deleted and replaced with the following:
"1303.15.6 Inspection and testing of backflow prevention assemblies.
Testing of a backflow prevention assembly shall be conducted in accordance with 
Sections 312.10.1, 312.10.2, and 312.10.3
Sections 312.11.1, 312.11.2, and 312.11.3
."
(7)
IPC, Section 1304.4.2, is deleted and replaced with the following:
"1304.4.2 Inspection and testing of backflow prevention assemblies.
Testing of a backflow preventer or backwater valve shall be conducted in accordance 
with 
Sections 312.10.1, 312.10.2, and 312.10.3
Sections 312.11.1, 312.11.2, and 312.11.3
."
Section 19. Section 
15A-3-315
 is amended to read:
15A-3-315
. Amendments to Chapter 15 of IPC.
(1)
In IPC, 
Chapter 15
, the following reference standards are deleted: ASSE 5013-2015, 
ASSE 5015-2015, ASSE 5020-2015, ASSE 5047-2015, ASSE 5048-2015, ASSE 
5052-98, ASSE 5056-2015, CSA B64.10-17, and CSA B64.10.1-17.
(2)
In IPC, 
Chapter 15
, the following referenced standard is added:
"Standard reference number
Title
Referenced in code section number
USC-FCCCHR 10th Edition Manual of Cross Connection Control
Foundation for Cross-Connection Control and Hydraulic Research University of Southern California Kaprielian Hall 300 Los Angeles CA 90089-2531
Section 
312.10.2
312.11.2
"
Section 20. Section 
15A-3-401
 is amended to read:
15A-3-401
. General provisions.
(1)
The amendments in this part are adopted as amendments to the IMC to be applicable 
statewide.
(2)
In IMC, Section 505.4, a new subsection 505.4.1 is added as follows: 
"505.4.1 Makeup Air. Makeup air is not required in residential dwelling units 
where gas, liquid, or solid fuel-burning appliances located within a units air barrier are 
all direct-vent or use a mechanical draft venting system."
(3)
In IMC, Section 1004.2, the first sentence is deleted and replaced with the following: 
"
In accordance with Title 34A, Chapter 7, Safety, and requirements made by 
rule by the Labor Commission, boilers and pressure vessels in Utah are regulated by the 
Utah Labor Commission, Division of Boiler, Elevator and Coal Mine Safety, except 
those located in private residences or in apartment houses of less than five family units. 
Boilers shall be installed in accordance with their listing and labeling, with minimum 
clearances as prescribed by the manufacturer's installation instructions and the state 
boiler code, whichever is greater."
(4)
In IMC, Section 1004.3.1, the word "unlisted" is inserted before the word "boilers
.
"
.
(5)
In IMC, Section 1109.2.5, Exception 2, the words "using Group A1 refrigerant" are 
deleted.
(5)
(6)
In IMC, Section 1209.3, the following words are added at the end of the section: 
"or other methods approved for the application."
Section 21. Section 
15A-3-402
 is amended to read:
15A-3-402
. Amendments to Chapters 1 through 5 of IMC.
(1)
In IMC, Table 403.3.1.1, note "h" is deleted and replaced with the following:
"h. 1. A nail salon shall provide each manicure station where a nail technician files or 
shapes an acrylic nail, as defined by rule by the Division of Professional Licensing, in 
accordance with Title 63G, Chapter 3, Utah Administrative Rulemaking Act, with:
a. a source capture system equipped with, at minimum, a MERV 8 particulate filter and 
an activated carbon filter that is capable of filtering and recirculating air to inside space at a 
rate not less than 50 cfm per station; or
b. a source capture system capable of exhausting not less than 50 cfm per station.
c. A nail salon that complies with Note h. la or h. lb is not required to comply with the 
labeling, listing, or testing requirements described in International Mechanical Code sections 
301.7 or 301.8.
2. For a source capture system described in paragraph 1, the source capture system inlets 
for exhausting or recirculating air shall be located in accordance with Section 502.20.
3. Where one or more exhausting source capture systems described in paragraph 1 
operate continuously during occupancy, the source capture system exhaust rate shall be 
permitted to be applied to the exhaust flow rate required by Table 403.3.1.1 for the nail salon.
4. The requirements of this note apply to:
a. an existing nail salon that remodels the nail salon after July 1, 2017;
b. a new nail salon that begins construction after July 1, 2017; and
c. all nail salons beginning on July 1, 2020."
(2)
 IMC, Section 502.20 is deleted and rewritten as follows:
"502.20 Manicure stations. A nail salon that files or shapes an acrylic nail shall provide 
each manicure station with a source capture system in accordance with Table 403.3.1.1, note h. 
For a manicure table that does not have factory-installed source capture system inlets for 
recirculating or exhausting air, a nail salon shall provide the manicure table with inlets for 
recirculating or exhausting air located not more than 12 inches (305 mm) horizontally and 
vertically from the point of any acrylic chemical application.
Exception: Section 502.20 applies to a manicure station in:
a. an existing nail salon that remodels the nail salon after July 1, 2017;
b. a new nail salon that begins construction after July 1, 2017; and
c. all nail salons beginning on July 1, 2020."
(3)
In IMC, Section 908.1, the following words are added at the end of the last sentence: "or 
UL/CSA 60335-2-40."
(4)
In IMC, Section 918.1, the following words are added after "1995": "or UL/CSA 
60335-2-40."
(5)
In IMC, Section 918.2, the following words are added at the end of the sentence: "or 
UL/CSA 60335-2-40."
(6)
In IMC, Section 1101.6, the following sentence is added at the end of the paragraph: 
"High probability systems utilizing A2L refrigerants shall comply with ASHRAE 15."
(7)
 IMC, Chapter 15 is amended by adding the following referenced standard to CSA:
"Standard reference number
Title
Referenced in code section number
CSA: CSA C22.2 60335-2-40-2019
Standard for Household and Similar Electrical Appliances, Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers - 3rd Edition
M1403.1, M1412.1, M1413.1"
(8)
In IMC, Section 1109.2.5, the words using "Group A1 refrigerant" are deleted in 
Exception 2.
(9)
IMC, Chapter 15 is amended by adding the following referenced standard to UL:
"Standard reference number
Title
Referenced in code section number
UL: 60335-2-40-2019
Standard for Household and Similar Electrical Appliances, Part 2-40: Particular Requirements for Electrical Heat Pumps, Air-Conditioners and Dehumidifiers - 3rd Edition
M1403.1, M1412.1, M1413.1"
Section 22. Section 
15A-3-501
 is amended to read:
15A-3-501
. General provisions.
The following are adopted as an amendment to the IFGC to be applicable statewide:
(1)
In IFGC, Section 404.9, a new Section 404.9.1, is added as follows: 
"404.9.1 Meter protection. Fuel gas services shall be in an approved location 
and/or provided with structures designed to protect the fuel gas meter and surrounding 
piping from physical damage, including falling, moving, or migrating ice and snow. If 
an added structure is used, it must still provide access for service and comply with the 
IBC or the IRC."
(2)
IFGC, Section 409.5.3, is deleted.
(3)
In IFGC, Section 502.1, the last sentence is deleted and replaced with "Plastic vents for 
Category IV appliances shall not be required to be listed and labeled where such vents comply 
with all of the following:
1. specified by the appliance manufacturer;
2. installed in accordance with the appliance manufacturer's instructions; and
3. the vent gas temperatures do not exceed 140 degrees Fahrenheit."
(4)
In IFGC, Section 503.4.1, in the last sentence after "appliance manufacturer" insert: 
"where the appliance vent gas temperatures do not exceed 140 degrees Fahrenheit,".
(5)
(3)
In IFGC, Section 503.6.11.1, the following exception is added:
"Exception: Existing and replacement Category I appliances may be located in rooms 
within the occupiable space provided all the following are met:
1. The original installation was compliant with existing codes at the time of installation.
2. The dwelling is equipped with a current, operable carbon monoxide detector, installed in 
accordance with Section 915 of the International Building Code.
3. The AHJ has approved a replacement based on the extreme difficulty of an installing 
individual Category I vent system or a direct vent Category IV appliance.
4. The room or space is used for no other purpose.
5. Combustion air is provided in accordance with Section 304. Where outdoor combustion 
air is provided, the room has a solid weather-stripped door equipped with an approved 
self-closure device.
6. Common vents terminate with a listed cap."
(6)
(4)
In IFGC, Section 631.2, the following sentence is inserted before the first sentence: 
"
In accordance with 
Title 34A, Chapter 7, Safety
, and requirements made by 
rule by the Labor Commission, boilers and pressure vessels in Utah are regulated by the 
Utah Labor Commission, Division of Boiler, Elevator and Coal Mine Safety, except 
those located in private residences or in apartment houses of less than five family units. 
Boilers shall be installed in accordance with their listing and labeling, with minimum 
clearances as prescribed by the manufacturer's installation instructions and the state 
boiler code, whichever is greater."
Section 23. Section 
15A-3-701
 is amended to read:
15A-3-701
. General provisions.
The following is adopted as an amendment to the IECC to be applicable statewide:
(1)
IECC, Section C405.11, is deleted and replaced with the following: "C405.11 
Automatic receptacle control. Automatic receptacle control to be optional and decided 
by property owner."
(2)
(1)
In IECC, Section R102.1.1, a new section R102.1.1 is added as follows: 
"R102.1.1 National Green Building Standard complying with ICC 700-2020 
National Green Building Standard and achieving the Gold rating level for the energy 
efficiency category shall be deemed to exceed the energy efficiency required by this 
code. The building shall also meet the requirements identified in table N1105.2 and the 
building thermal envelope efficiency is greater than or equal to levels of efficiency and 
solar heat gain coefficients (SHGC) in Tables N1102.2.2 and N1102.1.3 of the 2009 
IRC."
(3)
(2)
In IECC, Section R103.2, all words after the words "herein governed
.
,
" are 
deleted and replaced with the following: 
"Construction documents include all documentation required for building permits 
shall include only those items specified in 
10-5-132(8)
 of the Utah Municipal Code."
(4)
(3)
In IECC, Section R303.1.3, the following changes are made:
(a)
The following is added at the end of the first sentence: "or EN 
14351-1:2006+A1:2010."
(b)
The word "accredited" is replaced with "approved" in the third sentence.
(c)
The following sentence is added after the third sentence: "A conversion factor of 
5.678 shall be used to convert from U values expressed in SI units: ()/53678=."
(d)
After "NFRC 200" the following words are added: "or EN 14351-1:2006+A1:2010", 
and in the sentence the word "accredited" is replaced with the word "approved
.
"
.
(e)
The following new sentence shall be inserted immediately prior to the last sentence: 
"Total Energy Transmittance values may be substituted for SHGC, and 
Luminous Transmission values may be substituted for VT."
(5)
(4)
In IECC, Section R303.3, all wording after the first sentence is deleted.
(6)
(5)
In IECC, Section R401.2, in the first sentence, the words "Section R401.13.5 and" 
are deleted.
(7)
(6)
In IECC, Section R401.2.5 is deleted.
(8)
(7)
In IECC, Section R401.3 Number 7, the words "and the compliance path used" are 
deleted.
(9)
(8)
In IECC Table R402.1.2, the following changes are made:
(a)
in the column titled "Fenestration U-Factor", the following changes are made:
(i)
in the row titled "Climate Zone 3", delete 0.30 and replace it with 0.32;
(ii)
in the row titled "Climate Zone 5 and Marine 4", delete 0.30 and replace it with 
0.32; and
(iii)
in the row titled "Climate Zone 6", delete 0.30 and replace it with 0.32;
(b)
in the column titled "Glazed Fenestration SHGC", the following change is made: in 
the row titled "Climate Zone 3" delete 0.25 and replace it with 0.35;
(c)
in the column titled "Climate U-Factor", the following changes are made:
(i)
in the row titled "Climate Zone 3", delete 0.026 and replace it with 0.030;
(ii)
in the row titled "Climate Zone 5 and Marine 4", delete 0.024 and replace it with 
0.026; and
(iii)
in the row titled "Climate Zone 6", delete 0.024 and replace it with 0.026;
(d)
in the column titled "Wood Frame Wall U Factor", the following changes are made:
(i)
in the row titled "Climate Zone 3", delete 0.060 and replace it with 0.060;
(ii)
in the row titled "Climate Zone 5 and Marine 4", delete 0.045 and replace it with 
0.060; and
(iii)
in the row titled "Climate Zone 6", delete 0.045 and replace it with 0.060;
(e)
in the column titled "Basement wall U-Factor", the following changes are made:
(i)
in the row titled "Climate Zone 5 and Marine 4", delete 0.050 and replace it with 
0.075; and
(ii)
in the row titled "Climate Zone 6", delete 0.50 and replace it with 0.065; and
(f)
in the column titled "Crawl Space Wall U-Factor", the following changes are made:
(i)
in the row titled "Climate Zone 5 and Marine 4", delete 0.055 and replace it with 
0.078; and
(ii)
in the row titled "Climate Zone 6", delete 0.55 and replace it with 0.065.
(10)
(9)
In IECC, Table R402.1.3, the following changes are made:
(a)
in the column titled "Fenestration U-Factor", the following changes are made:
(i)
in the row titled "Climate Zone 3", delete 0.30 and replace it with 0.32;
(ii)
in the row titled "Climate Zone 5 and Marine 4", delete 0.30 and replace it with 
0.32; and
(iii)
in the row titled "Climate Zone 6", delete 0.30 and replace it with 0.32;
(b)
in the column titled "Glazed Fenestration SHGC", the following change is made: in 
the row titled "Climate Zone 3" delete 0.25 and replace it with 0.35;
(c)
in the column R-Value the following changes are made:
(i)
in the row titled "Climate Zone 3", delete 49 and replace it with 38;
(ii)
in the row titled "Climate Zone 5 and Marine 4", delete 60 and replace it with 49; 
and
(iii)
in the row titled "Climate Zone 6", delete 60 and replace it with 49;
(d)
in the column titled "Wood Frame Wall R-Value", the following changes are made:
(i)
in the row titled "Climate Zone 3", delete all values and replace with "20+Oci or 
13+5ci or 0+15ci";
(ii)
in the row titled "Climate Zone 5 or Marine 4", delete all values and replace with 
"21+Oci or 15+5ci or 0+15ci"; and
(iii)
in the row titled "Climate Zone 6", delete all values and replace with "21+Oci or 
15+5ci or 0+15ci";
(e)
in the column titled "Basement Wall R-Value", the following changes are made:
(i)
in the row titled "Climate Zone 5 or Marine 4", delete all values and replace with 
"15+Oci or 0+11ci or 11+5ci"; and
(ii)
in the row titled "Climate Zone 6", delete all values and replace with "19+Oci or 
0+13ci or 11+5ci";
(f)
in the column titled "Slab R-Value and Depth", the following changes are made:
(i)
in the row titled "Climate Zone 3", delete "10ci. 2ft" and replace it with "NR"; and
(ii)
in the row titled "Climate Zone 5 
 Marine 4", delete "4 ft" and replace it with 
"2 ft";
(g)
in the column titled "Crawl Space Wall R-Value", the following changes are made:
(i)
in the row titled "Climate Zone 5 or Marine 4", delete all values and replace with 
"15+Oci or 0+11ci or 11+5ci"; and
(ii)
in the row titled "Climate Zone 6", delete all values and replace with "19+Oci or 
0+13ci or 0+11+5ci"; and
(h)
in IECC, Table R402.2, in the column titled "MASS WALL R-VALUE", a new 
footnote "j" is added as follows: 
"j Log walls complying with ICC400 and with a minimum average wall 
thickness of 5 inches or greater shall be permitted in "Zones 5 through 8" when 
overall window glazing has a .31 U-factor or lower, minimum heating equipment 
efficiency is 90 AFUE (gas) or 84 AFUE (oil), and all other component requirements 
are met."
(11)
(10)
In IECC, a new subsection R402.1.5.1 is added as follows: 
"R402.1.5.1 RESCheck 2012 Utah Energy Conservation Code. Compliance with 
section N1102.1.5 (R402.1.5) may be satisfied using the software RESCheck 2012 Utah 
Energy Conservation Code, which shall satisfy the R-value and U-factor requirements of 
N1102.1, N1102.2, and N1102.3, provided the following conditions are met:
(a)
In Climate Zone 5 and 6 the software result shall show 5% better than code; and
(b)
In Climate Zone 3, the software result shall show 5% better than code when software 
inputs for window U-factor = 0.65 and window SHGC = 0.40, notwithstanding actual 
windows installed shall conform to requirements of Tables N1102.1.2 (R402.1.2) and 
N1102.1.3 (R402.1.3)."
(12)
(11)
In IECC, Section R402.2.1, a new section is added as follows: 
"R402.2.1.1. Unvented attic and unvented enclosed rafter assemblies. Unvented attic and 
unvented enclosed rafter assemblies conforming to Section R806.5 shall be provided with an 
R-value of R-22 (maximum U-Factor of 0.045) in Climate Zone 3-B or an R-value of R-26 
(maximum U-factor of 0.038) in Climate Zones 5-B and 6-B shall be permitted provided all 
the following conditions are met:
1. The unvented attic assembly complies with the requirements of the International 
Residential Code, Section R806.5.
2. The house shall attain a blower door test result 
 2.5ACH 50.
3. The house shall require a whole house mechanical ventilation system that does not 
rely solely on a negative pressure strategy (must be positive, balanced or hybrid).
4. Where insulation is installed below the roof deck and the exposed portion of roof 
rafters are not already covered by the R-20 depth of the air-impermeable insulation, the 
exposed portion of the roof rafters shall be wrapped (covered) by minimum R-3 unless directly 
covered by drywall/finished ceiling. Roof rafters are not required to be covered by minimum 
R-3 if a continuous insulation is installed above the roof deck.
5. Indoor heating, cooling and ventilation equipment (including ductwork) shall be 
inside the building thermal envelope.
"
(13)
(12)
A new IECC, Section R402.2.1.3 is added as follows:
"R402.2.1.3 Walls with Air-Impermeable Insulation. Where IECC Table R402.1.2 
requires R-20 for wood framed walls in climate zones 3-B and 5-B or R-20+5CI for 
climate zone 6-B, an air-impermeable insulation installed in the wall cavity with R-value 
of R-15 for climate zones 3-B and 5-B or R-20 for climate zone 6-B shall be deemed 
equivalent to the provisions in IECC Table R402.1.2, provided the home attains a 
blower door test 
 2.5ACH."
(14)
(13)
In IECC, Section R402.2.9.1, the numeral "(i)" is added before the words "cut at 
a 45 degree" and the following is added after the words "exterior wall:": "or (ii) lowered 
from top of slab 4" when a 4" thermal break material such as, but not limited to, felt or 
asphalt impregnated fiber board, with a minimum thickness of 1/4" is installed at the 
upper 4" of slab."
(15)
(14)
In IECC, Section R402.4.1, in the first sentence, the word "and" is deleted and 
replaced with the word "or
.
"
.
(16)
(15)
In IECC, Section R402.4.1.1, the second and the last sentences are deleted and 
replaced with the following: 
"Where required by the code official, the builder shall certify compliance with 
criteria indicated in Table R1102.4.1 for items which are not readily visible during 
regularly scheduled inspections."
(17)
(16)
In IECC, Table R402.4.1.1 in the column titled "COMPONENT", the following 
changes are made:
(a)
in the row "Rim Joists" the word "exterior" in the first sentence is deleted, and the 
second sentence is deleted.
(b)
In the row "Electrical/phone box on the exterior walls" the last sentence is deleted 
and replaced with: "Alternatively, close cell foam, caulking or gaskets may be used, 
or air sealed boxes may be installed."
(18)
(17)
In IECC, Section R402.4.1.2, the following changes are made:
(a)
In the fourth sentence, the word "third" is deleted.
(b)
The following sentence is added after the fourth sentence:
"The following parties shall be approved to conduct testing: Parties certified by 
BPI or RESNET, or licensed contractors who have completed training provided by 
Blower Door Test equipment manufacturers or other comparable training."
(c)
In the first Exception the second sentence is deleted.
(19)
(18)
In IECC, Section R402.4.1.3
,
 the following changes are made:
(a)
in the first sentence, the words 5.0 air changes per hour in Climate Zones 0, 1 and 2, 
and 3.0 are deleted and replaced with 4.0., and the words in Climate Zone 3 through 
8 are deleted;
(b)
in the first sentence of the Exception, 0.28 is replaced with 5.0 air changes per hour 
or 0.30; and
(c)
in Number 2, the words of "conditioned floor area" are inserted before the words "or 
smaller."
(20)
(19)
In IECC, Section R402.6 is deleted.
(21)
(20)
In IECC, Section R403.3.1 is deleted and replaced with the following: 
"Ducts located outside conditioned space. Supply and return ducts in attics shall be 
insulated to a minimum of R-8 where 3 inches (76.2 mm) in diameter and greater and 
R-6 where less than 3 inches (76.2 mm) in diameter. Supply and return ducts in other 
portions of the building shall be insulated to a minimum of R-6 where 3 inches (76.2 
mm) in diameter or greater and R-4.2 where less than 3 inches (76.2 mm) in diameter. 
Exception: Ducts or portions thereof located completely inside the building thermal 
envelope."
(22)
(21)
In IECC, Section R403.3.3, is deleted.
(23)
(22)
In IECC, Section R403.3.3.1 is deleted.
(24)
(23)
In IECC, Section R403.3.5, the following changes are made:
(a)
a second Exception is added as follows: 
"A duct leakage test shall not be required for any system designed such that no air 
handlers or ducts are located within unconditioned attics."
(b)
the following is added at the end of the section: 
"The following parties shall be approved to conduct testing:
(i)
Parties certified by BPT or RESNET
(ii)
Licensed contractors who have completed training provided by Duct Test 
equipment manufacturers or other comparable training."
(25)
(24)
In IECC, Section N1103.3.6 (R403.3.6) the following changes are made:
(a)
in Subsection 1:
(i)
the number 4.0 is changed to 6.0;
(ii)
the number 113.3 is changed to 170;
(iii)
the number 3.0 is changed to 5.0; and
(iv)
the number 85 is changed to 141;
(b)
in Subsection 2:
(i)
the number 4.0 is changed to 5.0; and
(ii)
the number 113.3 is changed to 141; and
(c)
Subsection 3 is deleted.
(26)
(25)
In IECC, Section N1103.3.7 (R403.3.7) the words "or plenums" are deleted.
(27)
(26)
In IECC, Section N1103.5.1.1 (R403.5.1.1) the words "Where installed" are 
added at the beginning of the first sentence.
(28)
(27)
IECC, Section R403.6.2, is deleted and replaced with the following: 
"R403.6.2 Whole-house mechanical ventilation system fan efficacy. Fans used to 
provide whole-house mechanical ventilation shall meet the efficacy requirements of Table 
R403.6.2.
"
"
Exception: Where an air handler that is integral to tested and listed HVAC equipment 
is used to provide whole-house mechanical ventilation, the air handler shall be powered by an 
electronically commutated motor."
(29)
(28)
In IECC, Section R403.6.2, the table is deleted and replaced with the following:
"TABLE R403.6.2
"
"
MECHANICAL VENTILATION SYSTEM FAN EFFICACY
"
FAN LOCATION
AIR FLOW RATE MINIMUM (CFM)
MINIMUM EFFICACY (CFM/WATT)
AIR FLOW RATE MAXIMUM (CFM)
HRV or ERV
Any
1.2 cfm/watt
Any
Range hoods
Any
2.8 cfm/watt
Any
In-line fan
Any
2.8 cfm/watt
Any
Bathroom, utility room
10
1.4 cfm/watt
90
Bathroom, utility room
90
2.8 cfm/watt
Any"
(30)
(29)
In IECC, Section R403.6.3 is deleted.
(31)
(30)
In IECC, Section R403.7, the word "approved" is deleted in the first sentence 
and the following is added after the word "methodologies": "complying with R403.7.1."
(32)
(31)
A new IECC, Section R403.7.1, is added as follows: 
"R403.7.1 Qualifications. An individual performing load calculations shall be qualified 
by completing HVAC training from one of the following:
1. HVAC load calculation education from ACCA;
2. A recognized educational institution;
3. HVAC equipment manufacturer's training; or
4. Other recognized industry certification."
(33)
(32)
In IECC, Section R404.1, the word "All" is replaced with "Not less than 90 
percent of the lamps in."
(34)
(33)
In IECC, Section R404.1.1 is deleted.
(35)
(34)
In IECC, Section R404.2 is deleted.
(36)
(35)
In IECC, Section R404.3 is deleted.
(37)
(36)
In IECC, Section R405.2 the following changes are made:
(a)
in Subsection 3, the words "approved by the code official" are deleted; and
(b)
in Subsection 3, the following words are added at the end of the sentence: "when 
applicable and readily available."
(38)
(37)
In IECC, Section R406.3 "Building thermal envelope" is deleted, and replaced 
with the following: 
"Building thermal envelope and on-site renewables. The proposed total building 
thermal envelope UA, which is the sum of U-factor times assembly area, shall be less 
than or equal to the building thermal envelope UA using the prescriptive U-factors From 
Table N1102.1.2 multiplied by 1.15 in accordance with Equation 11-4. The 
area-weighted maximum fenestration SHGC permitted in Climate Zones 0 through 3 
shall be 0.30.UAProposed design = 1.15 x UAPrescriptive reference design (Equation 
11-4)."
(39)
(38)
 In IECC, Section R406.3.1 is deleted.
(40)
(39)
In IECC, Section R406.3.2 is deleted.
(41)
(40)
In IECC, Section R406.4 the following changes are made:
(a)
in the first sentence, the words "in accordance with Equation 11-5" are deleted and 
replaced with: "permitted to be calculated using the minimum total air exchange Rate 
for the rated home (Qtot) and for the index adjustment factor in accordance with 
Equation 11.5.";
(b)
in equation 11-5, the words "Ventilation rate, CFM" are deleted and replaced with: 
"Qtot"; and
(c)
in the last sentence, the number "5" is deleted and replaced with "15
.
"
.
(42)
(41)
In IECC, Section R406.5 in the column titled ENERGY RATING INDEX of 
Table R406.5, the following changes are made:
(a)
in the row for Climate Zone 3, "51" is deleted and replaced with "65";
(b)
in the row for Climate Zone 5, "55" is deleted and replaced with "69"; and
(c)
in the row for Climate Zone 6, "54" is deleted and replaced with "68
.
"
.
(43)
(42)
In IECC, Section R408 is deleted.
(a)
(i)
(A)
In IECC, Chapter 6, the standard for ANSI/RESNET/ICC 201-2019 
section 4.4.4 is added as follows: 
"4.4.4. Air Source Heat Pumps and Air Conditioners. For Heat Pumps and 
Air Conditioners with the more recent Manufacturers Equipment Performance 
Ratings (HSPF2 or SEER2) available, and HSPF and SEER are not available, 
these ratings shall be converted to HSPF and SEER values by dividing HSPF2 
or SEER2 by the conversion factors in Table 4.4.4.1(1). If the type of 
equipment is not determined, the conversion shall default to the Ducted Split 
System factors. All calculations, including Equation 4.1-1a shall use HSPF or 
SEER values as made available by the Manufacturer or converted as specified 
in this section. Table 4.4.4.1(1) SEER2 and HSPF2 Conversion
"
Equipment Type
SEER2/SEER
EER2/EER4
HSPF2/HSPF
Ductless Systems
1.00
1.00
0.90
Ducted Split System
0.95
0.95
0.85
Ducted Packaged System
0.95
0.95
0.84
Small Duct High Velocity System
1.00
Not Applicable
0.85
Ducted Space-Constrained Air Conditioner
0.97
Not Applicable
Not Applicable
Ducted Space-Constrained Heat Pump
0.99
Not Applicable
0.85"
Section 24. Section 
15A-3-801
 is amended to read:
15A-3-801
. General provisions.
The following are adopted as amendments to the IEBC and are applicable statewide:
(1)
In IEBC, Section 202, the definition for "Approved" is modified by adding the words 
"or independent third-party licensed engineer or architect and submitted to the building 
official" after the word official.
(2)
In 
IEBC, 
Section 202, the following definition is added:
"BUILDING OFFICIAL. See Code official."
(3)
In 
IEBC, 
Section 202, the definition for "
Code official
CODE OFFICIAL
" is deleted and 
replaced with the following:
"CODE OFFICIAL. The officer or other designated authority having jurisdiction (AHJ) 
charged with the administration and enforcement of this code."
(4)
In 
IEBC, 
Section 202, the definition for "
Existing buildings
EXISTING BUILDINGS
" is 
deleted and replaced with the following:
"EXISTING BUILDING. A building that is not a dangerous building and that was 
either lawfully erected under a prior adopted code, or deemed a legal non-conforming building 
by the code official."
(5)
In IEBC, Section 302.3, the following is added after the words "code official" in the last 
sentence: 
"or independent third-party licensed engineer or architect and submitted to the 
building official."
(6)
In 
IEBC, 
Section 301.3, the exception is deleted.
(7)
In IEBC, Section 503.5, the following is added after the words "BSE-1E earthquake 
hazard level" in the last sentence:
"and using an objective of Life Safety Nonstructural Performance with the BSE-2E 
earthquake hazard level."
(7)
(8)
IEBC, 
Section 503.6 is deleted and replaced with the following:
"503.6 Bracing for unreinforced masonry parapets and other appendages upon reroofing.
Where the intended alteration requires a permit for reroofing and involves removal of 
roofing materials from more than 25% of the roof area of a building assigned to Seismic 
Design Category D, E, or F that has parapets constructed of unreinforced masonry or 
appendages such as cornices, spires, towers, tanks, signs, statuary, etc., the work shall include 
installation of bracing to resist out-of-plane seismic forces, unless an evaluation demonstrates 
compliance of such items. Reduced seismic 
forces are permitted for design purposes
criteria 
of IEBC, Section 304.3.2 is permitted
."
(9)
In IEBC, Section 503.11, the following is added after the words "BSE-1E earthquake 
hazard level" in the last sentence:
"and using an objective of Life Safety Nonstructural Performance with the BSE-2E 
earthquake hazard level."
(10)
In IEBC, Section 705.2, a new Exception 2 is added as follows:
"(2) Any existing layers of polyisocyanurate insulation shall be permitted to remain 
in place if the roof decking is in serviceable condition and the insulation is not damaged, 
deteriorated or water soaked. All other types of roof insulation and any areas of 
damaged, deteriorated, or water soaked polyisocyanurate insulation are to be removed 
and replaced with new."
(8)
(11)
IEBC, 
Section 706.3.1 is deleted and replaced with the following:
"706.3.1 Bracing for unreinforced masonry bearing wall parapets and other appendages.
Where a permit is issued for reroofing more than 25 percent of the roof area of a 
building assigned to Seismic Design Category D, E, or F that has parapets constructed of 
unreinforced masonry or appendages such as cornices, spires, towers, tanks, signs, statuary, 
etc., the work shall include installation of bracing to resist the reduced International Building 
Code level seismic forces as specified in 
Section 303
Section 304.3.2
 of this code unless an 
evaluation demonstrates compliance of such items."
(12)
In IEBC, Section 906.2, the following is added after the words "BSE-1E earthquake 
hazard level" in the last sentence:
"and using an objective of Life Safety Nonstructural Performance with the BSE-2E 
earthquake hazard level."
(13)
In IEBC, Section 906.3, the following is added after the words "BSE-1E earthquake 
hazard level" in the last sentence:
"and using an objective of Life Safety Nonstructural Performance with the BSE-2E 
earthquake hazard level."
(9)
(14)
IEBC, 
Section 906.6 is deleted and replaced with the following:
"906.6 Bracing for unreinforced masonry parapets and other appendages upon reroofing.
Where the intended alteration requires a permit for reroofing and involves removal of 
roofing materials from more than 25% of the roof area of a building assigned to Seismic 
Design Category D, E, or F that has parapets constructed of unreinforced masonry or 
appendages such as cornices, spires, towers, tanks, signs, statuary, etc., the work shall include 
installation of bracing to resist out-of-plane seismic forces, unless an evaluation demonstrates 
compliance with such items. Reduced seismic 
forces are permitted for design purposes
criteria of IEBC, Section 304.3.2, is permitted
."
(10)
(15)
(a)
Section 1006.3 is deleted and replaced with the following:
"1006.3 Seismic loads. Where a change of occupancy results in a building being 
assigned to a higher risk category, or when a change of occupancy results in a design occupant 
load increase of 100% or more, the building shall satisfy the requirements of Section 1613 of 
the International Building Code using full seismic forces."
In IEBC, Section 1006.3, Seismic 
Loads, the following is added after the words "higher risk category" in the first sentence: 
"or when a change of occupancy results in a design occupant load increase of 100% or 
more."
(b)
In 
IEBC, 
Section 1006.3, 
exceptions
Exceptions
 1 through 4 remain unchanged.
(c)
In 
IEBC, 
Section 1006.3, add a new 
exception
Exception
 5 as follows:
"5. Where the design occupant load increase is less than 25 occupants and the occupancy 
category does not change."
(11)
(16)
In 
IEBC, 
Section 1011.7.3, 
exception
Exception
 2 is deleted.
Section 25. Section 
15A-3-1001
 is amended to read:
15A-3-1001
. General provisions.
(1)
In ISPSC, Section 202, the following definition is added for private residential 
swimming pool: 
"PRIVATE RESIDENTIAL SWIMMING POOL
 (Residential Pool)
. A swimming 
pool, spa pool, or wading pool used only by an individual, family, or living unit 
members and guests, but not serving any type of multiple unit housing complex of four 
or more living units."
(2)
In ISPSC, Section 202, the definition for Residential Swimming Pool (Residential Pool) 
is deleted and replaced with the following: 
"See the definition for Private Residential Swimming Pool
 (Residential Pool)
."
(3)
In ISPSC, Section 306.3, in the first sentence, the words "or private residential pools" 
are added after the word "pools" and the last sentence is deleted.
(3)
(4)
In ISPSC, 
Section 320.1
Section 321.1
, the following changes are made:
(a)
the words "or storm" are deleted;
(b)
the words "onsite waste water" are added before the word "disposal"; and
(c)
the words "or shall be disposed of by other means approved by the state or local 
authority" are deleted.
(5)
In ISPSC, Section 326.1, the following words are added after the word "indoor": 
"residential or."
(6)
In ISPSC, a new Section 326.2 is added as follows:
"326.2 Recirculation of Air. Supply air to residential or public pool and spa and 
associated deck areas shall not be recirculated unless such air is dehumidified to 
maintain the relative humidity of the area at 60% or less. Air from this area shall not be 
recirculated to other spaces where more than 10% of the resulting supply airstream 
consists of air recirculated from these spaces. The design and installation of ventilation 
systems shall comply with ANSI/ACCA 10 Manual SPS.
(7)
In Chapter 11, the following reference standard is added:
Standard Reference Number
Title
Referenced in Code Section Number
ANSI/ACCA 10 Manual SPS - 2023
HVAC Design for Swimming Pools and Spas, Publisher: 
Air Conditioning Contractors of America (ACCA) 2800 Shirlington Road, Ste 300, Arlington, VA 22206
Section 326.2
Section 26. 
Effective Date.
This bill takes effect on 
May 6, 2026
.