Rep. Norm Thurston — Voting Record

Utah House District 62 · complete roll-call record from le.utah.gov
← All votes

Bill

Fire Code Amendments
Number
H.B. 45 (2026GS)
Sponsor
Rep. Peterson, Thomas W.
Final action
Governor Signed 3/13/2026
Outcome
Became law — signed by Gov. Spencer J. Cox

Summary

This bill modifies the State Fire Code Act.

What it does

  • This bill:
  • amends the State Fire Code to address updated standards in the International Fire Code; and
  • makes technical and conforming changes.

Every vote on this bill

2026-01-26Senate Comm - Substitute Recommendation
Senate Business and Labor Committee
4-0-4not eligible / no record
2026-01-26Senate Comm - Favorable Recommendation
Senate Business and Labor Committee
5-0-3not eligible / no record
2026-02-04Senate/ passed 2nd reading
Senate 3rd Reading Calendar
25-0-4not eligible / no record
2026-02-05Senate/ passed 3rd reading
Clerk of the House
26-0-3not eligible / no record
2026-02-06House/ circled
House Concurrence Calendar
0-0-75not eligible / no record
2026-01-21House/ passed 3rd reading
Senate Secretary
70-3-2YEA
2026-02-09House/ uncircled
House Concurrence Calendar
0-0-75not eligible / no record
2026-02-09House/ concurs with Senate amendment
Senate President
68-1-6YEA

Bill text

enrolled version · official source
14
15A-5-103
15A-5-202
15A-5-202.5
15A-5-203
15A-5-204
15A-5-205
15A-5-205.5
15A-5-205.6
15A-5-302
15A-5-303
15A-5-304
1
Fire Code Amendments
2026 GENERAL SESSION
STATE OF UTAH
Chief Sponsor: Thomas W. Peterson
Senate Sponsor: Evan J. Vickers
LONG TITLE
General Description:
This bill modifies the State Fire Code Act.
Highlighted Provisions:
This bill:
amends the State Fire Code to address updated standards in the International Fire Code; 
and
makes technical and conforming changes.
Money Appropriated in this Bill:
None
Other Special Clauses:
This bill provides a special effective date.
Utah Code Sections Affected:
AMENDS:
15A-5-103
, as last amended by Laws of Utah 2024, Chapter 505
15A-5-202
, as last amended by Laws of Utah 2025, First Special Session, Chapter 15
15A-5-202.5
, as last amended by Laws of Utah 2024, Chapter 438
15A-5-203
, as last amended by Laws of Utah 2025, Chapter 74
15A-5-204
, as last amended by Laws of Utah 2023, Chapter 95
15A-5-205
, as last amended by Laws of Utah 2023, Chapter 95
15A-5-205.5
, as last amended by Laws of Utah 2024, Chapter 21
15A-5-205.6
, as last amended by Laws of Utah 2025, First Special Session, Chapter 15
15A-5-302
, as last amended by Laws of Utah 2023, Chapter 95
15A-5-304
, as last amended by Laws of Utah 2023, Chapter 95
REPEALS:
15A-5-303
, as last amended by Laws of Utah 2024, Chapter 343
Be it enacted by the Legislature of the state of Utah:
Section 1. Section 
15A-5-103
 is amended to read:
15A-5-103
. Nationally recognized codes incorporated by reference.
The following codes are incorporated by reference into the State Fire Code:
(1)
the International Fire Code, 
2021
2024
 edition, excluding appendices, as issued by the 
International Code Council, Inc., except as amended by Part 2, Statewide Amendments 
and Additions to International Fire Code Incorporated as Part of State Fire Code;
(2)
National Fire Protection Association, NFPA 1, Chapter 38, Marijuana Growing, 
Processing, and Extraction Facilities, 
2018
2024
 edition;
(3)
National Fire Protection Association, NFPA 54, National Fuel Gas Code, 2024 edition; 
and
(4)
National Fire Protection Association, NFPA 58, Liquefied Petroleum Gas Code, 2024 
edition.
Section 2. Section 
15A-5-202
 is amended to read:
15A-5-202
. Amendments and additions to IFC related to administration, 
permits, definitions, and general and emergency planning.
(1)
For IFC, Chapter 1, Scope and Administration:
(a)
IFC, Chapter 1, Section 102.5, is deleted and rewritten as follows:
"102.5 Application of residential code.
If a structure is designed and constructed in accordance with the International 
Residential Code, the provisions of this code apply only as follows:
1. The construction and design provisions of this code apply only to premises 
identification, fire apparatus access, fire hydrants and water supplies, and construction permits 
required by Section 105.7.
2. This code does not supersede the land use, subdivision, or development standards 
established by a local jurisdiction.
3. The administrative, operational, and maintenance provisions of this code apply."
(b)
IFC, Chapter 1, Section 102.9, is deleted and rewritten as follows:
"102.9 Matters not provided for.
Requirements that are essential for the public safety of an existing or proposed activity, 
building or structure, or for the safety of the occupants thereof, which are not specifically 
provided for by this code, shall be determined by the fire code official on an emergency basis 
if:
(a) the facts known to the fire code official show that an immediate and significant danger 
to the public health, safety, or welfare exists; and
(b) the threat requires immediate action by the fire code official.
102.9.1 Limitation of emergency order.
In issuing its emergency order, the fire code official shall:
(a) limit the order to require only the action necessary to prevent or avoid the danger to the 
public health, safety, or welfare; and
(b) give immediate notice to the persons who are required to comply with the order, that 
includes a brief statement of the reasons for the fire code official's order.
101.9.2 Right to appeal emergency order.
If the emergency order issued under this section will result in the continued infringement 
or impairment of any legal right or interest of any party, the party shall have a right to appeal 
the fire code official's order in accordance with IFC, Chapter 1, Section 109."
(c)
IFC, Chapter 1, Section 106.1, Submittals, is amended to add the following after the last 
sentence:
"Fire sprinkler system layout shall be prepared and submitted by a person certified by 
the National Institute for Certification in Engineering Technologies at level III or IV in 
Water-Based System Layout. Fire alarm system layout shall be prepared and submitted by a 
person certified by the National Institute for Certification in Engineering Technologies at level 
III or IV in Fire Alarm Systems."
(d)
IFC, Chapter 1, Section 105.5.18, Flammable and combustible liquids, is amended to 
add the following section: 
"12. The owner of an underground tank that is out of service for longer than 
one year shall receive a Temporary Closure Notice from the Department of 
Environmental Quality and a copy shall be given to the AHJ."
(e)
In IFC, Chapter 1, Section 102.5, a new subsection 3
.
,
 is added as follows:
"3. For development regulated by a local jurisdiction's land use authority, the fire code 
official's interpretation of this code is subject to the advisory opinion process described in Utah 
Code, Section 
13-43-205
, and to a land use appeal authority appointed under Utah Code, 
Section 
10-20-1101
 or 
17-79-1001
."
(f)
In IFC, Chapter 1, Section 
111
113
, a new Section 
111.5
112.5
, Notice of right to 
appeal, is added as follows: 
"At the time a fire code official makes an order, decision, or determination that 
relates to the application or interpretation of this chapter, the fire code official shall 
inform the person affected by the order, decision, or determination of the person's 
right to appeal under this section. Upon request, the fire code official shall provide a 
person affected by an order, decision, or determination that relates to the application 
or interpretation of this chapter a written notice that describes the person's right to 
appeal under this section."
(2)
For IFC, Chapter 2, Definitions:
(a)
In IFC, Chapter 2, Section 202, General Definitions, the following definition is 
added for 
Ambulatory Surgical Center
ambulatory surgical center
: 
"AMBULATORY SURGICAL CENTER. A building or portion of a building 
licensed by the Department of Health and Human Services where procedures are 
performed that may render patients incapable of self
-
preservation where care is less 
than 24 hours. See Utah Administrative Code, R432-13, Freestanding Ambulatory 
Surgical Center Construction Rule."
(b)
In IFC, Chapter 2, Section 202, General Definitions, 
"
APPROVED
"
 is modified by 
adding the words "or independent third-party licensed engineer or licensed architect 
and submitted to the fire code official" after the word "official."
(c)
In IFC, Chapter 2, Section 202, General Definitions, the following definition is added for 
Assisted Living Facility, Residential Treatment and Support
assisted living facility, residential 
treatment and support
: 
"ASSISTED LIVING FACILITY, RESIDENTIAL TREATMENT AND SUPPORT. A 
residential facility that provides a group living environment for four or more residents licensed 
by the Department of Health and Human Services and provides a protected living arrangement 
for ambulatory, non-restrained persons who are capable of achieving mobility sufficient to exit 
the facility without the physical assistance of another person.
ASSISTED LIVING FACILITY, TYPE I. A residential facility licensed by the 
Department of Health and Human Services that provides a protected living arrangement, 
assistance with activities of daily living and social care to two or more ambulatory, 
non-restrained persons who are capable of mobility sufficient to exit the facility without the 
assistance of another person.
ASSISTED LIVING FACILITY, TYPE II. A residential facility licensed by the 
Department of Health and Human Services that provides an array of coordinated supportive 
personal and health care services to two or more residents who are:
A. Physically disabled but able to direct his or her own care; or
B. Cognitively impaired or physically disabled but able to evacuate from the facility, or 
to a zone or area of safety, with the physical assistance of one person.
Subcategories are:
ASSISTED LIVING FACILITY, LIMITED CAPACITY: A Type I or Type II assisted 
living facility having two to five residents.
ASSISTED LIVING FACILITY, SMALL: A Type I or Type II assisted living facility 
having six to sixteen residents.
ASSISTED LIVING FACILITY, LARGE: A Type I or Type II assisted living facility 
having more than sixteen residents."
(d)
In IFC, Chapter 2, Section 202, General Definitions, the definition for 
Child Care 
Facility
child care facility
 is added as follows: 
"CHILD CARE FACILITY: A facility where care and supervision is provided 
for four or more children for less than 24 hours a day and for direct or indirect 
compensation in place of care ordinarily provided in their home."
(e)
In IFC, Chapter 2, Section 202, General Definitions, the definition for 
Independent 
Third-Party
independent third-party
 is added as follows: 
"INDEPENDENT THIRD-PARTY. An engineer or architect licensed in the 
State of Utah, who is not affiliated with the jurisdiction or the project owner, 
developer, architect, or engineer, and is agreeable to all parties. The independent 
third-party will provide unbiased assessments, opinions, or services based on their 
expertise and professional standards in their respective fields."
(f)
IFC, Chapter 2, Section 
202
203.4.2
, 
General Definitions, OCCUPANCY 
CLASSIFICATION, Educational Group E, 
Group E, day care facilities, is deleted and 
replaced with the following:
"
Group E, Child Care Facilities
203.4.2 Group E, day care facilities
. This group 
includes buildings and structures or portions thereof occupied by four or more children 2 years 
of age or older who receive educational, supervision, child care services or personal care 
services for fewer than 24 hours per day. See Section 429, Day Care, for special requirements 
for day care.
203.4.2.1 
Within Places of Religious Worship. Rooms and spaces within places of 
religious worship providing such day care during religious functions shall be classified as part 
of the primary occupancy.
203.4.2.2 
Four or Fewer Children. A facility having four or fewer children receiving 
such day care shall be classified as part of the primary occupancy.
203.4.2.3 
Four or Fewer Children in a Dwelling Unit. A facility such as the above within 
a dwelling unit and having four or fewer children receiving such day care shall be classified as 
a Group R-3 occupancy or shall comply with the International Residential Code.
203.4.2.4 
Child Day Care - Residential Child Care Certificate or a License. Areas used 
for child day care purposes with a residential child care certificate, as described in Utah 
Administrative Code, R430-50, Residential Certificate Child Care, or a residential child care 
license, as described in Utah Administrative Code, R430-90, Licensed Family Child Care, may 
be located in a Group R-2 or R-3 occupancy as provided in the International Building Code, 
Sections 310.3 and 310.4, or shall comply with the International Residential Code, Section 
R101.2.
203.4.2.5 
Child Care Centers. Each of the following areas may be classified as accessory 
occupancies, if the area complies with the International Building Code, Section 508.2:
1. Hourly child care center, as described in Utah Administrative Code, R381-60, Hourly 
Child Care Centers;
2. Child care centers, as described in Utah Administrative Code, R381-100, Child Care 
Centers;
3. 
Out-of-school-time
Out-of-School-Time
 programs, as described in Utah 
Administrative Code, R381-70, 
Out of School Time
Out-of-School-Time
 Child Care 
Programs; and
4. Commercial preschools, as described in Utah Administrative Code, R381-40, 
Commercial Preschool Programs."
(g)
In IFC, Chapter 2, Section 
202
203.7.1
, 
General Definitions, OCCUPANCY 
CLASSIFICATION, 
Institutional Group I-1, is amended as follows: 
In the list of items under "This group shall include," the words "Type-I Large 
and Type-II Small, see the International Building Code, Section 
308.2.5
308.2
" are 
added after "Assisted living facilities."
(h)
In IFC, Chapter 2, Section 
202
203.7.1.4
, 
General Definitions, OCCUPANCY 
CLASSIFICATION, Institutional Group I-1, 
Five or fewer persons receiving 
custodial care is 
amended as follows: On line four after "International Residential 
Code" the rest of the section is deleted.
rewritten as follows:
"A facility with five or fewer persons receiving custodial care shall be 
classified as Group R-3 or shall comply with the International Residential Code."
(i)
IFC, Chapter 2, Section 
202
203.7.2
, 
General Definitions, OCCUPANCY 
CLASSIFICATION, 
Institutional Group I-2, is deleted and replaced with the following:
"Institutional Group I-2. Institutional Group I-2 occupancy shall include buildings and 
structures used for medical care on a 24-hour basis for more than four persons who are 
incapable of self-preservation. This group shall include, but not be limited to the following:
Assisted living facilities, Type-II Large, see Section 308.3.3
Child care facilities
Foster care facilities
Detoxification facilities
Hospitals
Nursing homes (both intermediate care facilities and skilled nursing facilities)
Psychiatric hospitals."
(j)
In IFC, Chapter 2, Section 
202
203.7.2
, 
General Definitions, OCCUPANCY 
CLASSIFICATION, 
Institutional Group I-2, a new section is added as follows:
"
203.7.2.3 
Assisted Living Facilities. A Type I, Large assisted living facility is classified 
as occupancy Group I-1, Condition 1. A Type II, Small assisted living facility is classified as 
occupancy Group I-1, Condition 2. See Section 202 for definitions."
(k)
IFC, Chapter 2, Section 
202
203.7.4.1
, 
General Definitions, OCCUPANCY 
CLASSIFICATION, Institutional Group I-4, day care facilities, 
Classification as Group E
, 
Five or fewer persons receiving care, and Five or fewer occupants receiving care in a dwelling 
unit are
 is
 deleted and replaced with the following:
"
203.7.4.1 
Classification as Group E. A child day care facility that provides care for five 
or more but not more than 100 children under two years of age, where the rooms in which the 
children are cared for are located on a level of exit discharge serving such rooms and each of 
these child care rooms has an exit door directly to the exterior, shall be classified as a Group E. 
See the International Building Code, Section 429 for special requirements for Day Care.
"
(l)
IFC, Chapter 2, Section 203.7.4.3, Five or fewer persons receiving care, is deleted and 
rewritten as follows:
Four
"203.7.4.3 Four
 or Fewer Persons Receiving Care. A facility having four or 
fewer persons receiving custodial care shall be classified as part of the primary occupancy. See 
the International Building Code, Section 429, for special requirements for Day Care.
"
(m)
IFC, Chapter 2, Section 203.7.4.4, Five or fewer persons receiving care in a dwelling unit, 
is deleted and rewritten as follows:
Four
"203.7.4.4 Four
 or Fewer Persons Receiving Care in a Dwelling Unit. A 
facility such as the above within a dwelling unit and having four or fewer persons receiving 
custodial care shall be classified as a Group R-3 occupancy or shall comply with the 
International Residential Code. See the International Building Code, Section 429, for special 
requirements for Day Care."
(l)
(n)
IFC, Chapter 2, Section 
202
203.9.3
, 
General Definitions, OCCUPANCY 
CLASSIFICATION, 
Residential Group R-3, is deleted and replaced with the following:
"
203.9.3 
Residential Group R-3. Residential Group R-3 occupancies and single family 
dwellings complying with the International Residential Code where the occupants are 
primarily permanent in nature and not classified as Group R-1, R-2, R-4, or I occupancies, 
including:
Assisted Living Facilities, Type-I, limited capacity, see Section 310.5.3
Buildings that do not contain more than two dwellings
Care facilities, other than child care, that provide accommodations for five or fewer 
persons receiving care
Congregate living facilities (nontransient) with 16 or fewer occupants
Boarding houses (nontransient)
Convents
Dormitories
Fraternities and sororities
Monasteries
Congregate living facilities (transient) with 10 or fewer occupants
Boarding houses (transient)
Lodging houses (transient) with five or fewer guest rooms and 10 or fewer occupants
.
"
(m)
(o)
IFC, Chapter 2, Section 
202, General Definitions, OCCUPANCY 
CLASSIFICATION
203.9.3.1
, Residential Group R-3, Care facilities within a 
dwelling, is deleted and replaced with the following: 
"
203.9.3.1 
Care Facilities within a Dwelling. Care facilities, other than child 
care, for five or fewer persons receiving care that are within a single family dwelling 
are permitted to comply with the International Residential Code. See the International 
Building Code, Section 429, for special requirements for Child Day Care."
(n)
(p)
In IFC, Chapter 2, Section 
202, General Definitions, OCCUPANCY 
CLASSIFICATION
203.9.3
, Residential Group R-3, a new section is added as follows: 
"
203.9.3.3 
Child Care. Areas used for child care purposes may be located in a residential 
dwelling unit when all of the following conditions are met:
1. Compliance with Utah Administrative Code, R710-8, Day Care Rules, as enacted 
under the authority of the Utah Fire Prevention Board;
2. Use is approved by the Department of Health and Human Services under the 
authority of Utah Code, Title 26B, Chapter 2, Part 4, Child Care Licensing, and in any of the 
following categories:
1.1. Utah Administrative Code, R430-50, Residential Certificate Child Care; or
1.2. Utah Administrative Code, R430-90, Licensed Family Child Care; and
1.3 Compliance with all zoning regulations of the local regulator."
(o)
(q)
In IFC, Chapter 2, Section 
202, General Definitions, OCCUPANCY 
CLASSIFICATION
203.9.3
, Residential Group R-3, a new section is added as follows:
"
203.9.3.4 
Assisted Living Facilities. Type I assisted living facilities with two to five 
residents are Limited Capacity facilities classified as a Residential Group R-3 occupancy or 
are permitted to comply with the International Residential Code. See Section 202 for 
definitions."
(p)
(r)
In IFC, Chapter 2, Section 
202, General Definitions, OCCUPANCY 
CLASSIFICATION
203.9.4
, Residential Group R-4, the words "Type II Limited 
Capacity and Type I Small, see R-4 Assisted Living Facility Occupancy Groups" are 
added after the words "Assisted 
Living Facilities
living facilities
."
(q)
(s)
In IFC, Chapter 2, Section 
202, General Definitions, OCCUPANCY 
CLASSIFICATION
203.9.4
, Residential Group R-4, a new section is added as follows: 
"
203.9.4.3 
Group R-4 - Assisted Living Facility Occupancy Groups. The following 
occupancy groups shall apply to Assisted Living Facilities:
Type II Assisted Living Facilities with two to five residents are Limited Capacity 
Facilities classified as a Residential Group R-4, Condition 2 occupancy.
Type I assisted living facilities with six to sixteen residents are Small Facilities 
classified as Residential Group R-4, Condition 1 occupancies. See Section 202 for definitions."
Section 3. Section 
15A-5-202.5
 is amended to read:
15A-5-202.5
. Amendments and additions to Chapters 3 and 4 of IFC.
(1)
For IFC, Chapter 3, General Requirements:
(a)
IFC, Chapter 3, Section 
304.1.2
304.1.3
, Vegetation, is amended as follows: Delete 
line six and replace it with: "Utah Administrative Code, R652-122-1300, Minimum 
Standards for County Wildland Fire Ordinance
".
."
(b)
IFC, Chapter 3, Section 310.8, Hazardous environmental conditions, is deleted and 
rewritten as follows: 
"1. When the fire code official determines that existing or historical hazardous 
environmental conditions necessitate controlled use of any ignition source, including 
fireworks, lighters, matches, sky lanterns, and smoking materials, any of the following may 
occur:
1.1. If the existing or historical hazardous environmental conditions exist in a 
municipality, the legislative body of the municipality may prohibit the ignition or use of an 
ignition source in:
1.1.1. mountainous, brush-covered, forest-covered, or dry grass-covered areas;
1.1.2. within 200 feet of waterways, trails, canyons, washes, ravines, or similar areas;
1.1.3. the wildland urban interface area, which means the line, area, or zone where 
structures or other human development meet or intermingle with undeveloped wildland or land 
being used for an agricultural purpose; or
1.1.4. a limited area outside the hazardous areas described in this paragraph 1.1 to 
facilitate a readily identifiable closed area, in accordance with paragraph 2.
1.2. If the existing or historical hazardous environmental conditions exist in an 
unincorporated area, the state forester may prohibit the ignition or use of an ignition source in 
all or part of the areas described in paragraph 1.1 that are within the unincorporated area, after 
consulting with the county fire code official who has jurisdiction over that area.
2. If a municipal legislative body or the state forester closes an area to the discharge of 
fireworks under paragraph 1, the legislative body or state forester shall:
2.1. designate the closed area along readily identifiable features like major roadways, 
waterways, or geographic features;
2.2. ensure that the boundary of the designated closed area is as close as is practical to 
the defined hazardous area, provided that the closed area may include areas outside of the 
hazardous area to facilitate a readily identifiable line; and
2.3. identify the closed area through a written description or map that is readily 
available to the public.
3. A municipal legislative body or the state forester may close a defined area to the 
discharge of fireworks due to a historical hazardous environmental condition under paragraph 
1 if the legislative body or state forester:
3.1. makes a finding that the historical hazardous environmental condition has existed 
in the defined area before July 1 of at least two of the preceding five years;
3.2. produces a map indicating the boundaries, in accordance with paragraph 2, of the 
defined area described; and
3.3. before May 1 of each year the defined area is closed, provides the map described in 
paragraph 3.2 to the county in which the defined area is located.
4. A municipal legislative body or the state forester may not close an area to the 
discharge of fireworks due to a historical hazardous environmental condition unless the 
legislative body or state forester provides a map, in accordance with paragraph 3."
(c)
IFC, Chapter 3, Section 311.1.1, Abandoned premises, is amended as follows: 
On line 10 delete the words "International Property Maintenance Code and the
".
."
(d)
IFC, Chapter 3, Section 311.5, Placards, is amended as follows: 
On line three delete the word "shall" and replace it with the word "may
".
."
(2)
IFC, Chapter 4, Emergency Planning and Preparedness:
(a)
In IFC, Chapter 4, the following new Sections are added:
"401.3.1.1 Special Education Classrooms. Special education classrooms may shelter in 
place, or delay evacuation when all of the following conditions are met:
401.3.1.1.1 There is no visible flame or evidence of products of combustion (smoke).
401.3.1.1.2 The building is completely protected by an approved fire sprinkler system.
401.3.1.1.3 The building is completely protected by an approved fire alarm system.
401.3.1.1.4 The classroom has a minimum of one approved exit that discharges 
directly to the exterior.
401.3.1.1.5 The classroom has been approved to shelter in place by the fire code 
official."
(b)
(a)
In IFC, Chapter 4, Section 401.3.3, Delayed notification, a new exception is added:
"Exception: Group E Occupancies. Teachers may delay evacuation upon fire alarm 
activation for up to 60 seconds when all of the following conditions are met:
A. There is no visible flame or evidence of products of combustion (smoke).
B. The building is protected throughout by an approved fire sprinkler system.
C. The building is protected throughout by an approved fire alarm system.
D. Students are in the safe zone of the room lined up and prepared for immediate 
evacuation."
(c)
(b)
IFC, Chapter 4, Section 403.9.2.1, College and university buildings, is deleted and 
replaced with the following:
"403.9.2.1 College and university buildings and fraternity and sorority houses.
(i)
College and university buildings, including fraternity and sorority houses, shall 
prepare an approved fire safety and evacuation plan, in accordance with Section 
404.
(ii)
Group R-2 college and university buildings, including fraternity and sorority 
houses, shall comply with Sections 403.9.2.1.1 and 403.9.2.1.2."
(c)
In IFC, Chapter 4, the following new sections are added:
"403.4.4 Special Education Classrooms. Special education classrooms may 
shelter in place, or delay evacuation when all of the following conditions are met:
403.4.4.1 There is no visible flame or evidence of products of combustion 
(smoke).
403.4.4.2 The building is completely protected by an approved fire sprinkler 
system.
403.4.4.3 The building is completely protected by an approved fire alarm system.
403.4.4.4 The classroom has a minimum of one approved exit that discharges 
directly to the exterior.
403.4.4.5 The classroom has been approved to shelter in place by the fire code 
official."
(d)
IFC, Chapter 4, Section 405.3, Table 405.3, is amended to add the following 
footnotes:
(i)
"
c
d
. Secondary schools in Group E occupancies shall have an emergency 
evacuation drill conducted at least every two months, to a total of four emergency 
evacuation drills during the nine-month school year. The first emergency 
evacuation drill shall be conducted within 10 school days after the beginning of 
classes. The third emergency evacuation drill, weather permitting, shall be 
conducted 10 school days after the beginning of the next calendar year. The 
second and fourth emergency evacuation drills may be substituted by a security or 
safety drill to include shelter in place, earthquake drill, or lock down for violence. 
If inclement weather causes a secondary school to miss the 10-day deadline for 
the third emergency evacuation drill, the secondary school shall perform the third 
emergency evacuation drill as soon as practicable after the missed deadline."
(ii)
"
d
e
. In Group E occupancies, excluding secondary schools, if the AHJ 
approves, the monthly required emergency evacuation drill can be substituted by a 
security or safety drill to include shelter in place, earthquake drill, or lock down 
for violence. The routine emergency evacuation drill must be conducted at least 
every other drill."
(iii)
"
e
f
. A-3 occupancies in academic buildings of institutions of higher learning 
are required to have one emergency evacuation drill per year, provided the 
following conditions are met:
(A)
(A) 
The building has a fire alarm system in accordance with Section 907.2.
(B)
(B) 
The rooms classified as assembly shall have fire safety floor plans as required in 
Subsection 404.2.2(4) posted.
(C)
(C) 
The building is not classified a high-rise building.
(D)
(D) 
The building does not contain hazardous materials over the allowable quantities 
by code."
Section 4. Section 
15A-5-203
 is amended to read:
15A-5-203
. Amendments and additions to IFC related to fire safety, building, 
and site requirements.
(1)
For IFC, Chapter 5, Fire Service Features:
(a)
In IFC, Chapter 5, a new Section 501.5, Access grade and fire flow, is added as 
follows: 
"An authority having jurisdiction over a structure built in accordance with the 
requirements of the International Residential Code as adopted in the State 
Construction Code, may require an automatic fire sprinkler system for the structure 
only by ordinance and only if any of the following conditions exist:
(i)
the structure:
(A)
is located in an urban-wildland interface area as provided in the Utah 
Wildland Urban Interface Code adopted as a construction code under the State 
Construction Code; and
(B)
does not meet the requirements described in Utah Code, Subsection 
65A-8-203
(4)(f) and Utah Administrative Code, R652-122-1300, Minimum Standards for 
County Wildland Fire Ordinance;
(ii)
the structure is in an area where a public water distribution system with fire 
hydrants does not exist as required in Utah Administrative Code, R309-550-5, 
Water Main Design;
(iii)
the only fire apparatus access road has a grade greater than 10% for more than 
500 continual feet;
(iv)
the total floor area of all floor levels within the exterior walls of the dwelling unit 
exceeds 10,000 square feet; or
(v)
the total floor area of all floor levels within the exterior walls of the dwelling unit 
is double the average of the total floor area of all floor levels of 
unsprinkled
unsprinklered
 homes in the subdivision that are no larger than 10,000 square feet.
(vi)
Exception: A single family dwelling does not require a fire sprinkler system if 
the dwelling:
(A)
is located outside the wildland urban interface;
(B)
is built in a one-lot subdivision; and
(C)
has 50 feet of defensible space on all sides that limits the propensity of fire 
spreading from the dwelling to another property."
(b)
In IFC, Chapter 5, Section 503.4.1, is deleted. 
(c)
In IFC, Chapter 5, Section 506.1, Where Required, is deleted and rewritten as 
follows: 
"Where access to or within a structure or an area is restricted because of 
secured openings or where immediate access is necessary for life-saving or 
fire-fighting purposes, the fire code official, after consultation with the building 
owner, may require a key box to be installed in an approved location. The key box 
shall contain keys to gain necessary access as required by the fire code official. For 
each fire jurisdiction that has at least one building with a required key box, the fire 
jurisdiction shall adopt an ordinance, resolution, or other operating rule or policy that 
creates a process to ensure that each key to each key box is properly accounted for 
and secure."
(c)
(d)
In IFC, Chapter 5, a new Section 507.1.1, Isolated one- and two-family 
dwellings, is added as follows: 
"Fire flow may be reduced for an isolated one- and two-family dwelling when 
the authority having jurisdiction over the dwelling determines that the development 
of a full fire-flow requirement is impractical."
(d)
(e)
In IFC, Chapter 5, a new Section 507.1.2, Pre-existing subdivision lots, is added as 
follows:
"507.1.2 Pre-existing subdivision lots.
The requirements for a pre-existing subdivision lot shall not exceed the requirements 
described in Section 501.5."
(e)
(f)
In IFC, Chapter 5, Section 507.5.1, here required, a new exception is added
 as 
follows
: 
"3. One interior and one detached accessory dwelling unit on a single 
residential lot."
(f)
(g)
(i)
IFC, Chapter 5, Section 510.1, Emergency responder communication 
coverage in new buildings, is amended by adding:
 "When required by the fire code official, unless the new building is a public 
school as that term is defined in Section 
53G-9-205.1
 or a private school, if 
determined by the fire code official to be necessary after construction of the new 
building is completed, then the fire code official shall require," at the beginning of 
the first paragraph.
(ii)
"
For public and private schools, an initial radio coverage test must be conducted 
by a qualified professional using appropriate testing equipment, and a report of the 
results must be submitted to the fire code official. Subsequent routine testing may 
be conducted by the fire code official using basic equipment. The fire code official 
may require additional professional testing if routine testing indicates potential 
issues with radio coverage.
"
(2)
For IFC, Chapter 6, Building Services and Systems:
(a)
IFC, Chapter 6, Section 604.6.1, Elevator key location, is deleted and rewritten as 
follows: 
"Firefighter service keys shall be kept in a "Supra-Stor-a-key" elevator key box 
or similar box with corresponding key system that is adjacent to the elevator for 
immediate use by the fire department. The key box shall contain one key for each 
elevator, one key for lobby control, and any other keys necessary for emergency 
service. The elevator key box shall be accessed using a 6049 numbered key."
(b)
IFC, Chapter 6, Section 606.1, General, is amended as follows: 
On line three, after the word "Code", add the words "and NFPA 96
".
."
(c)
IFC, Chapter 6, Section 
607.2
606.2
, a new 
exception
Exception
 5 is added as 
follows: 
"5. A Type 1 hood is not required for a cooking appliance in a microenterprise 
home kitchen, as that term is defined in Utah Code, Section 
26B-7-401
, for which the 
operator obtains a permit in accordance with Section 
26B-7-416
."
(3)
IFC, Chapter 7, Fire and Smoke Protection Features, Section 702.5, is deleted.
Section 5. Section 
15A-5-204
 is amended to read:
15A-5-204
. Amendments and additions to IFC related to fire protection and life 
safety systems.
For IFC, 
Chapter 9
, Fire Protection and Life Safety Systems:
(1)
IFC, 
Chapter 9
, Section 901.4.7, Pump and riser room size, is deleted and replaced with the 
following:
"901.4.7 Pump and Riser Room Size.
901.4.7.1 Fire pump rooms and automatic sprinkler system riser rooms shall be designed 
with adequate space for all installed equipment necessary for the installation and to provide 
sufficient working room around the stationary equipment. Clearances around equipment to 
elements of permanent construction, including other installed equipment and appliances, shall 
be sufficient to allow inspection, service, repair or replacement without removing such 
elements of permanent construction or disabling the function of a required fire-resistance-rated 
assembly and not less than the following minimum elements:
901.4.7.1.1 A minimum clear and unobstructed distance of 12 inches shall be provided 
from the installed equipment to the elements of permanent construction.
901.4.7.1.2 A minimum clear and unobstructed distance of 12 inches shall be provided 
between all other installed equipment and appliances.
901.4.7.1.3 A clear and unobstructed width of 36 inches shall be provided in front of all 
installed equipment and appliances, to allow for inspection, service, repair or replacement 
without removing such elements of permanent construction or disabling the function of a 
required fire resistance-rated assembly.
901.4.7.2 Fire Pump Room. Fire pumps and controllers shall be provided with ready 
access. Fire pump rooms shall be provided with doors and an unobstructed passageway large 
enough to allow for the removal of the largest piece of equipment. The passageway shall have 
a clear width not less than 72 inches. Openings into the room shall be clear and unobstructed, 
with doors swinging in the outward direction from the fire pump room and the opening 
providing a clear width of not less than 68 inches and a clear height of the door opening shall 
not be less than 80 inches. The door shall be permitted to be locked provided that the key is 
available at all times and located in a Key Box in accordance with IFC, Section 506.
901.4.7.3 Automatic Sprinkler Riser Room. Automatic sprinkler system risers shall be 
provided with ready access. Automatic sprinkler system riser rooms shall be provided with 
doors and an unobstructed passageway large enough to allow for the removal of the largest 
piece of equipment. The passageway shall have a clear width not less than 36 inches. Openings 
into the room shall be clear and unobstructed, with doors swinging in the outward direction 
from the riser room and the opening providing a clear width of not less than 32 inches and a 
clear height of the door opening shall not be less than 80 inches. The door shall be permitted to 
be locked provided that the key is available at all times and located in a Key Box in 
accordance with IFC, Section 506.
901.4.7.4 Marking on Access Doors. Access doors for automatic sprinkler system riser 
rooms and fire pump rooms shall be labeled with an approved sign. The lettering shall be in 
contrasting color to the background. Letters shall have a minimum height of 2 inches (51 mm) 
with a minimum stroke of 3/8 inch (10 mm).
901.4.7.5 Environment. Automatic sprinkler system riser rooms and fire pump rooms 
shall be maintained at a temperature of not less than 40 degrees F (4 degrees C). Heating units 
shall be permanently installed.
902.6 Lighting. Permanently installed artificial illumination shall be provided in the 
automatic sprinkler system riser rooms and fire pump rooms."
(2)
IFC, 
Chapter 9
, Section 903.2.1.2, Group A-2, is amended to add the following 
subsection: 
"4. An automatic fire sprinkler system shall be provided throughout Group A-2 
occupancies where indoor pyrotechnics are used."
(3)
IFC, 
Chapter 9
, Section 903.2.2, Ambulatory care facilities, is amended as follows: 
On line two delete
Delete
 the words "entire floor" and replace with the word 
"building" and delete the last paragraph.
(4)
IFC, 
Chapter 9
, Section 903.2.4, Group F-1, Subsection 2, is deleted and rewritten as 
follows: 
"A Group F-1 fire area is located more than three stories above the lowest level of 
fire department vehicle access."
(5)
IFC, 
Chapter 9
, Section 903.2.7, Group M, Subsection 2, is deleted and rewritten as 
follows: 
"A Group M fire area is located more than three stories above the lowest level of 
fire department vehicle access."
(6)
IFC, 
Chapter 9
, Section 903.2.8 Group R, including all subsections, is deleted and rewritten 
as follows:
"903.2.8 Group R.
An automatic sprinkler system installed in accordance with Section 903.3 shall be 
proved throughout all buildings with a Group R fire area.
Exceptions:
1. Detached one- and two-family dwellings and multiple single-family dwellings 
(townhouses) constructed in accordance with the International Residential Code for One- and 
Two-Family Dwellings.
2. Single story Group R-1 occupancies with fire areas not more than 2,000 square feet 
that contain no installed plumbing or heating, where no cooking occurs, and constructed of 
Type I-A, I-B, II-A, or II-B construction.
3. Group R-4 fire areas not more than 4,500 gross square feet and not containing more 
than 16 residents, provided the building is equipped throughout with an approved fire alarm 
system that is interconnected and receives its primary power from the building wiring and a 
commercial power system."
(7)
IFC, 
Chapter 9
, Section 903.2.9, Group S-1, Subsection 2, is deleted and rewritten as 
follows: 
"A Group S-1 fire area is located more than three stories above the lowest level of 
fire department vehicle access."
(8)
IFC, 
Chapter 9
, Section 903.3.1.2, NFPA 13R sprinkler systems, Subsections 2 and 3, are 
deleted and rewritten as follows:
"2. The floor level of the highest story is 40 feet (12192 mm) or less above the lowest 
level of fire department vehicle access.
3. The floor level of the lowest story is 40 feet (12192 mm) or less below the lowest 
level of fire department vehicle access."
(9)
IFC, 
Chapter 9
, Section 903.3.1.2.3, Attics, is amended by adding the following: 
"Exception: Sprinkler protection in attics is not required in buildings that are not 
required to be sprinklered by another section of this code."
(10)
IFC, 
Chapter 9
, Section 903.3.5, Water supplies, is amended as follows: 
On line six, after the word "Code", add "and as amended in the State Construction 
Code
".
."
(11)
IFC, 
Chapter 9
, Section 903.5, Testing and maintenance, is amended to add the 
following subsection: 
"903.5.1 Tag and Information. A tag shall be attached to the riser indicating the 
date the antifreeze solution was tested. The tag shall also indicate the type and 
concentration of antifreeze solution by volume with which the system is filled, the name 
of the contractor that tested the antifreeze solution, the contractor's license number, and 
a warning to test the concentration of the antifreeze solutions at yearly intervals."
(12)
IFC, 
Chapter 9
, Section 
904.13.5.2
904.14.5.2
, Extinguishing system service, is 
amended to add the following: 
"Exception: Automatic fire extinguishing systems located in occupancies where 
usage is limited and less than six consecutive months may be serviced annually if the 
annual service is conducted immediately before the period of usage, and approval is 
received from the AHJ."
(13)
IFC, 
Chapter 9
, Section 905.3.9
,
 is a new subsection as follows: 
"Open Parking Garages. Open parking garages shall be equipped with an approved Class 
I manual standpipe system when fire department access is not provided for firefighting 
operations to within 150 feet of all portions of the open parking garage as measured from the 
approved fire department vehicle access. Class I manual standpipe shall be accessible 
throughout the parking garage such that all portions of the parking structure are protected 
within 150 feet of a hose connection.
Exception: Open parking garages equipped throughout with an automatic sprinkler 
system in accordance with Section 903.3.1.1."
(14)
IFC, 
Chapter 9
, Section 905.12, Existing buildings, is deleted.
(15)
In IFC, 
Chapter 9
, Section 906.1, Exception 2
,
 is amended as follows: 
on
On
 line three after the word "6," delete the remainder of the paragraph.
(16)
IFC, 
Chapter 9
, Section 907.2.3
,
 Group E:
(a)
907.2.3 Group E is deleted and rewritten as follows: 
"A manual fire alarm system that initiates the occupant notification signal 
using an emergency voice/alarm communication system that meets the requirements 
of Section 907.5.2.2, or a manual fire alarm system that initiates an approved audible 
and visual occupant notification signal that meets the requirements of Sections 
907.5.2.1, 907.5.2.1.1, 907.5.2.1.2, and 907.5.2.3, and is installed in accordance with 
Section 907.6, and with rules made by the Utah Fire Prevention Board in accordance 
with 
Title 63G, Chapter 3, Utah Administrative Rulemaking Act
, shall be installed in 
Group E occupancies. Where automatic fire sprinkler systems or smoke detectors are 
installed, the fire sprinkler systems and smoke detectors shall be connected to the 
building fire alarm system."
(b)
Exception 2, 
delete entirely
is deleted
 and the remaining exceptions are renumbered.
(c)
Exception 
number 
4.2, is deleted and rewritten as follows: 
"The fire alarm system will activate on sprinkler water flow."
(d)
New Sections 907.2.3.1 through 907.2.3.7 are added as follows:
"907.2.3.1 Automatic detection devices that detect smoke shall be installed throughout 
all corridors and spaces open to the corridor at the maximum prescribed spacing of thirty feet 
on center and no more than fifteen feet from the walls or smoke detectors shall be installed as 
required in NFPA, Standard 72, Section 17.7.
907.2.3.2 Where structures are not protected or are partially protected with an automatic 
fire sprinkler system, approved automatic smoke detectors shall be installed in accordance 
with the complete coverage requirements of NFPA, Standard 72.
907.2.3.3 An approved key plan drawing and operating instructions shall be posted at 
the main fire alarm panel which displays the location of all alarm zones and if applicable, 
device addresses.
907.2.3.4 The main panel shall be located in a normally attended area such as the main 
office or lobby. Location of the Main Panel other than as stated above, shall require the review 
and authorization of the State Fire Marshal Division. Where location as required above is not 
possible, an electronically supervised remote annunciator from the main panel shall be located 
in a supervised area of the building. The remote annunciator shall visually indicate system 
power status, alarms for each zone, and give both visual and audible indication of trouble 
conditions in the system. All indicators on both the main panel and remote annunciator shall be 
adequately labeled.
907.2.3.5 All system wiring shall be as follows:
(A) The initiating device circuits shall be designated and installed Class A as defined in 
NFPA Standard 72.
(B) The notification appliance circuits shall be designated
,
 and installed Class A as 
defined in NFPA Standard 72.
(C) Signaling line circuits shall be designated and installed Class A loop as defined in 
NFPA Standard 72.
907.2.3.6 Fan Shutdown shall be as follows:
(A) Fan shut
down shall be as required in the International Mechanical Code, 
Chapter 6
, 
Section 606.
(B) Duct detectors required by the International Mechanical Code shall be interconnected 
and compatible with the fire alarm system."
(17)
In IFC, 
Chapter 9
, a new Section 907.5.2.3.4
,
 is added as follows: 
"907.5.2.3.4 Special Education Classrooms. Visible and audible alarm notification 
appliances in Special Education classrooms may be replaced with a solid red light when 
approved by the fire code official."
(18)
IFC, 
Chapter 9
, Section 907.8, Inspection, testing, and maintenance, is amended to add 
the following sentences at the end of the section: 
"Increases in nuisance alarms shall require the fire alarm system to be tested for 
sensitivity. Fire alarm systems that continue after sensitivity testing with unwarranted 
nuisance alarms shall be replaced as directed by the AHJ."
(19)
IFC, 
Chapter 9
, Section 915.2.3, Group E occupancies and Exception
,
 is deleted and 
replaced with the following:
"915.2.3 Group E Occupancies. Carbon monoxide detectors shall be installed in the 
following areas within Group E occupancies:
(1) Boiler rooms, furnace rooms, and similar rooms, or in adjacent areas where carbon 
monoxide is likely to spread. (The installation of carbon monoxide detectors in boiler rooms 
and furnace rooms may cause a false alarm problem. Locating these detectors in adjacent 
spaces where the carbon monoxide is likely to spread may be a better option.)
(2) Home economics rooms with gas appliances.
(3) School kitchens with gas appliances. (Commercial kitchens).
(4) Arts rooms and other areas with a gas kiln or open flame.
(5) Gas roof top units, and other carbon monoxide producing HVAC units, one per zone. 
(The zone shall be the area covered by the HVAC unit.)
(6) In areas with gas wall units.
(7) In areas with a gas water heater or boiler.
(8) Areas with a forge or foundry.
(9) Metal shop or auto shop areas or in adjacent areas where carbon monoxide is likely to 
spread. (The installation of carbon monoxide detectors in metal shop or auto shop areas may 
cause a false alarm problem. Locating these detectors in adjacent spaces, i.e. class rooms or 
corridors, where the carbon monoxide is likely to spread from these spaces may be a better 
option.)
(10) Labs with open flame.
(11) HVAC units drawing outside air that could be contaminated with carbon monoxide.
(12) Other areas with an open flame or fuel fired appliance.
(F) 915.2.3.1 Carbon monoxide alarm signals shall be automatically transmitted to an onsite 
location that is staffed by school personnel.
Exception: Carbon monoxide alarm signals shall not be required to be automatically 
transmitted to an onsite location that is staffed by school personnel in Group E occupancies 
with an occupant load of 30 or less."
(20)
In IFC, 
Chapter 9
, a new Section 915.7
,
 is added as follows:
"915.7 Carbon Monoxide Systems in Group E Occupancies. Carbon monoxide systems 
may be part of a fire alarm system or standalone system.
915.7.1 Power and Wiring.
915.7.1.1 Power. Carbon monoxide detection systems shall require a primary and 
secondary power source.
915.7.1.2 Wiring. Class "A" wiring is required when the carbon monoxide system is part 
of, or connected to, a fire alarm system. Standalone carbon monoxide detection systems may 
use Class "B" wiring. All wiring shall be Class "A" or "B
".
."
915.7.2 Equipment Shut Down. Equipment and appliances that are producing carbon 
monoxide shall shut down automatically in the zone involved upon carbon monoxide system 
activation.
915.7.3 Notification.
915.7.3.1 Local Alarm. Each occupied space shall sound an audible alarm when 
detecting carbon monoxide at a level in excess of 70 ppm for one hour.
915.7.3.2 General Alarm. A blue strobe, visual alarm, is required in a normally occupied 
location, similar to the administrative offices, when carbon monoxide is detected in the facility 
in excess of 70 ppm for one hour.
915.7.3.2.1 The general alarm shall require a manual reset following an alarm activation.
915.7.3.3 Digital Notification. Portable carbon monoxide detectors, with digital read out 
indicating parts per million of carbon monoxide, in a space to determine the level of hazard in 
a given space.
915.7.4 Monitoring. System monitoring is not required. If the system is monitored, the 
signal should be a supervisory signal indicating carbon monoxide.
915.7.5 Inspection.
915.7.5.1 The carbon monoxide detection system shall be tested in the presence of a 
Deputy or Special Deputy of the State Fire Marshal Division. The Deputy shall require "spot 
testing" of the system and its components.
915.7.5.2 Before requesting final inspection and approval, the installing contractor shall 
test each component of the system and issue a statement of compliance, in writing, to the State 
Fire Marshal Division that the carbon monoxide detection system has been installed in 
accordance with approved plans and has been tested in accordance with the manufacturer's 
specifications, and the appropriate installation standard.
915.7.5.3 Systems shall be tagged with the State approved tag for fire alarm systems, 
upon final approval and shall be inspected and tagged annually by an individual certified as a 
Master Fire Alarm Technician, by the State Fire Marshal Division.
915.7.6 Evacuation. The affected area within Group E Occupancies shall be evacuated 
when carbon monoxide is detected at a level in excess of 70 ppm for one hour in that area."
Section 6. Section 
15A-5-205
 is amended to read:
15A-5-205
. Amendments and additions to IFC related to means of egress and 
special processes and uses.
(1)
IFC, Chapter 10, Section 1010.2.12.1, Delayed egress locking system, Item 9 is added 
after the existing Item 8 as follows: 
"9. The secure area or unit with delayed egress locks shall be located at the level 
of exit discharge in Type V construction."
(2)
IFC, 
Chapter 10
, Section 
1010.2.14
1010.2.13
, Controlled egress doors in Groups I-1 
and I-2, after existing Item 8 add Item 9 as follows: 
"9. The secure area or unit with special egress locks shall be located at the level of 
exit discharge in Type V construction."
(2)
IFC, 
Chapter 10
, Section 1010.2.13.1, Delayed egress locking system, Item 9 is added 
after the existing Item 8 as follows: 
"9. The secure area or unit with delayed egress locks shall be located at the level 
of exit discharge in Type V construction."
(3)
IFC, 
Chapter 10
, Section [BE] 1011.5.2, Riser height and tread depth, Exception 3
,
 is 
deleted and replaced with the following: 
"3. In Group R-3 occupancies, within dwelling units in Group R-2 occupancies, 
and in Group U occupancies that are accessory to a Group R-3 occupancy, or accessory 
to individual dwelling units in Group R-2 occupancies, the maximum riser height shall 
be 8 inches (203 mm) and the minimum tread depth shall be 9 inches (229 mm). The 
minimum winder tread depth at the walk line shall be 10 inches (254 mm), and the 
minimum winder tread depth shall be 6 inches (152 mm). A nosing not less than 0.75 
inch (19.1 mm) but not more than 1.25 inches (32 mm) shall be provided on stairways 
with solid risers where the tread depth is less than 10 inches (254 mm)."
(4)
IFC, 
Chapter 10
, Section [BE] 1011.11, Handrails, is amended to add the following 
exception: 
"
6. In occupancies in Group R-3, as applicable in Section 1014 and in 
occupancies in Group U, which are accessory to an occupancy in Group R-3, as 
applicable in Section 1014, handrails shall be provided on at least one side of stairways 
consisting of four or more risers."
(5)
IFC, 
Chapter 10
, Section 1032.2.1, Security devices and egress locks, is amended to add 
the following: 
On line three, after the word "fire
",
,"
 add the words "and building."
Section 7. Section 
15A-5-205.5
 is amended to read:
15A-5-205.5
. Amendments to Chapters 11 and 12 of IFC.
(1)
For IFC, Chapter 11, Construction Requirements for Existing Buildings:
(a)
IFC, Chapter 11, Section 1103.2, Emergency Responder Communication Coverage 
in Existing Buildings, 
is amended as follows: On 
on 
line two after the title, the 
following is added: 
"When required by the fire code official, unless the existing building is a public 
school as that term is defined in Section 
53G-9-205.1
 or a private school, then the fire 
code official shall require,".
(b)
IFC, Chapter 11, Section 1103.5.1, Group A-2, is deleted and replaced with the following:
"1103.5.1 Group A-2. An automatic fire sprinkler system shall be provided throughout 
existing Group A-2 occupancies where indoor pyrotechnics are used."
(c)
IFC, Chapter 11, Section 1103.6, Standpipes, is deleted.
(d)
IFC, Chapter 11, 1103.7, Fire Alarm Systems, is deleted and rewritten as follows: 
"1103.7, Fire Alarm Systems. The following shall have an approved fire alarm system 
installed in accordance with Utah Administrative Code, R710-4, Buildings Under the 
Jurisdiction of the Utah Fire Prevention Board:
1. a building with an occupant load of 300 or more persons that is owned or operated by 
the state;
2. a building with an occupant load of 300 or more persons that is owned or operated by 
an institution of higher education; and
3. a building with an occupant load of 50 or more persons that is owned or operated by 
a school district, private school, or charter school.
Exception: the requirements of this section do not apply to a building designated as an 
Institutional Group I (as defined in IFC 202) occupancy."
(e)
IFC, Chapter 11, 1103.7.1 Group E, 1103.7.2 Group I-1, 1103.7.3 Group I-2, 
1103.7.4 Group I-3, 1103.7.5 Group R-1, 1103.7.5.1 Group R-1 hotel and motel 
manual fire alarm system, 1103.7.5.1.1 Group R-1 hotel and motel automatic smoke 
detection system, 1103.7.5.2 Group R-1 boarding and rooming houses manual fire 
alarm system, 
and 
1103.7.5.2.1 Group R-1 boarding and rooming houses automatic 
smoke detection system, 1103.7.6 Group R-2 are deleted.
(f)
IFC, Chapter 11, Section 1103.5.4, High-rise buildings, is amended as follows: 
On line two, delete "not been adopted" and replace with "been adopted."
(g)
IFC, Chapter 11, Section 1103.9, Carbon monoxide 
alarms
detection
, is deleted and 
rewritten as follows:
"1103.9 Carbon Monoxide Detection.
Existing Groups E, I-1, I-2, I-4, and R occupancies shall be equipped with carbon 
monoxide detection in accordance with Section 915."
(2)
For IFC, Chapter 12, Energy Systems:
(a)
Delete the section title "1205.2.1 Solar photovoltaic systems for Group R-3 
buildings" and replace with the section title "1205.2.1 Solar photovoltaic systems for 
Group R-3 and buildings constructed in accordance with IRC."
(b)
Section 1205.2.1, Solar photovoltaic systems for Group R-3 buildings, Exception 1 is 
deleted, Exception 2 is renumbered to 1 and a second exception is added as follows: 
"2. Reduction in pathways and clear access width are permitted where a 
rational approach has been used and the reduction is warranted and approved by the 
Fire Code Official."
(c)
Section 1205.3.1 Perimeter pathways, and 1205.3.2 Interior pathways, are deleted and 
rewritten as follows: 
"1204.3.1 Perimeter pathways. There shall be a minimum three foot wide (914 mm) 
clear perimeter around the edges of the roof. The solar installation shall be designed to provide 
designated pathways. The pathways shall meet the following requirements:
1. The pathway shall be over areas capable of supporting the live load of fire fighters 
accessing the roof.
2. The centerline axis pathways shall be provided in both axes of the roof. Centerline 
axis pathways shall run where the roof structure is capable of supporting the live load of fire 
fighters accessing the roof.
3. Smoke and heat vents required by Section 910.2.1 or 910.2.2 shall be provided with a 
clear pathway width of not less than three feet (914 mm) to the vents.
4. Access to roof area required by Section 504.3 or 1011.12 shall be provided with a 
clear pathway width of not less than three feet (914 mm) around access opening and at least 
three feet (914 mm) clear pathway to parapet or roof edge."
(d)
Section 1205.3.3, Smoke ventilation, is deleted and rewritten as follows: 
"1205.3.2, Smoke ventilation. The solar installation shall be designed to meet the 
following requirements:
1. Arrays shall be no greater than 150 feet (45720 mm) by 150 feet (45720 mm) in 
distance in either axis in order to create opportunities for fire department smoke ventilation 
operations.
2. Smoke ventilation options between array sections shall be one of the following:
2.1 A pathway six feet (1829 mm) or greater in width.
2.2 A pathway three feet (914 mm) or greater in width and bordering roof skylights or 
smoke and heat vents when required by Section 910.2.1 or Section 910.2.2.
2.3 Smoke and heat vents designed for remote operation using devices that can be 
connected to the vent by mechanical, electrical, or any other suitable means, protected as 
necessary to remain operable for the design period. Controls for remote operation shall be 
located in a control panel, clearly identified and located in an approved location.
3. Where gravity-operated dropout smoke and heat vents occur, a pathway three feet 
(914 mm) or greater in width on not fewer than one side."
Section 8. Section 
15A-5-205.6
 is amended to read:
15A-5-205.6
. Amendments and additions to Chapter 33 of IFC.
(1)
IFC, 
Chapter 33
, Section 3311.1, Required access, is deleted and rewritten as follows:
"3311.1 Required access.
3311.1.1 Approved vehicle access. Approved vehicle access for fire fighting shall be 
provided as described in 
Chapter 5
 of this code to all construction or demolition sites.
3311.1.2 Fire department connections. Vehicle access shall be provided to within 100 
feet of temporary or permanent fire department connections.
3311.1.3 Type of access. Vehicle access shall be provided by either temporary or 
permanent roads.
3311.3.1 Temporary road requirements. Temporary roads shall be constructed with a 
minimum of site specific required structural fill for permanent roads and road base, or other 
approved material complying with local standards.
3311.3.2 Reports. Compaction reports may be required. An engineer's review and 
certification of a temporary fire department access road is not required.
3311.3.3 Local jurisdictions. A local jurisdiction may not require:
(a)
permanent roads, or asphalt or concrete on temporary roads before final approval of 
the structure served by the road; or
(b)
permanent roads, or asphalt and concrete on temporary roads, during construction of the 
structure served by the road.
3311.1.4 Maintenance. Temporary roads shall be maintained until permanent fire 
apparatus access roads are available.
3311.1.5 Time line. Temporary or permanent fire department access roads shall be 
functional before construction above the foundation begins and before an appreciable amount 
of combustible construction materials are on site."
(2)
IFC, 
Chapter 33
, Section 3311.2, Key boxes, is deleted.
(3)
(1)
IFC, Chapter 33, Section 3307.1, Required access, is rewritten as follows:
"3307.1 Required access. Approved vehicle access for firefighting shall be 
provided as described in Chapter 5 of this code to all construction or demolition sites. 
Vehicle access shall be provided to within 100 feet (30,480 mm) of temporary or 
permanent fire department connections. Vehicle access shall be provided by either 
temporary or permanent roads, capable of supporting vehicle loading under all weather 
conditions."
(2)
IFC, Chapter 33, Section 3301.1.1, is rewritten as follows:
"3307.1.1.1 Temporary road requirements. Temporary roads shall be constructed 
with a minimum of site specific required structural fill for permanent roads and road 
base, or other approved material complying with local standards.
3307.1.1.2 Reports. Compaction reports may be required. An engineer's review 
and certification of a temporary fire department access road is not required.
3307.1.1.3 Local jurisdictions. If an improvement completion assurance has been 
posted in accordance with Section 
10-9a-604.5
, a local jurisdiction may not require 
permanent roads, or asphalt or concrete on temporary roads, before final approval of the 
structure served by the road.
3307.1.1.4 Maintenance. Temporary roads shall be maintained until permanent 
fire apparatus access roads are available.
3307.1.1.5 Time line. Temporary or permanent fire department access roads shall 
be functional before construction above the foundation begins and before an appreciable 
amount of combustible construction materials are on site."
(3)
Notwithstanding IFC 3311.3.1, a temporary road that meets the requirements of Section 
10-20-1001
 or 
17-79-901
, and any local regulation adopted in accordance with Section 
10-20-1001
 or 
17-79-901
, may be constructed.
Section 9. Section 
15A-5-302
 is amended to read:
15A-5-302
. Amendments and additions to NFPA related to National Fire Alarm 
and Signaling Code.
For NFPA 72, National Fire Alarm and Signaling Code, 
2019
2022
 edition:
(1)
NFPA 72, 
Chapter 10
, Section 10.5.1, System Designer, Subsection 10.5.1.3(2), is 
deleted and rewritten as follows: 
"Certification by the National Institute for Certification in Engineering 
Technologies at level III or IV in Fire Alarm Systems."
(2)
NFPA 72, 
Chapter 10
, Section 10.5.3, Inspection, Testing, and Service Personnel, 
Subsection 10.5.3.1, Inspection Personnel, is deleted and rewritten as follows:
"Service personnel shall be qualified and experienced in the inspection, testing, and 
maintenance of fire alarm systems. Qualified personnel shall meet the certification 
requirements stated in rule made by the Utah Fire Prevention Board in accordance with 
Title 
63G, Chapter 3, Utah Administrative Rulemaking Act
."
(3)
NFPA 72, 
Chapter 10
, Section 10.12, Fire Alarm Signal Deactivation, Subsection 
10.12.2, is amended to add the following sentence: 
"When approved by the AHJ, the audible notification appliances may be 
deactivated during the investigation mode to prevent unauthorized reentry into the 
building."
Section 10. Section 
15A-5-304
 is amended to read:
15A-5-304
. Amendments and additions to NFPA related to Automatic Fire 
Sprinkler Systems.
(1)
NFPA 13, Installation of Sprinkler Systems, 
2019
2022
 edition
,
.
 Chapter 16, Section 
16.11.2.1, Local Waterflow Alarms, is amended by adding new subsections as follows:
(a)
NFPA 13, 
Chapter 16
, Section 16.9.11, Floor Control Valve Assemblies, Subsection 
16.9.11.5, is deleted and rewritten as follows:
"16.9.11.5, System Subdivision - Floor/Zone Control Valves.
Individual floor/zone control valves shall be used at the riser at each floor for 
connections to piping serving floor areas in excess of 5,000 square feet."
(b)
NFPA 13, 
Chapter 8
, Section 16.11.2.1, Local Waterflow Alarms, is amended by adding a 
new subsection as follows:
"16.11.2.1.1 Single Tenant Occupancies.
When a fire alarm system is not required by IFC, Section 907.2, an approved 
audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of the building, 
in a normally occupied location, to alert the occupants of the fire sprinkler system activation.
"
(c)
NFPA 13, 
Chapter 8
, Section 16.11.2.1, Local Waterflow Alarms, is amended by adding a 
new subsection as follows:
"
16.11.2.1.2 Multi-Tenant Occupancies.
When a fire alarm system is not required by IFC, Section 907.2, an approved 
audible/visual waterflow alarm (horn/strobe) shall be provided in the interior of each tenant 
space, in a normally occupied location, to alert the occupants of the fire sprinkler system 
activation.
"
(d)
NFPA 13, 
Chapter 8
, Section 16.11.2.1, Local Waterflow Alarms, is amended by adding a 
new subsection as follows:
"
16.11.2.1.3 Exterior Waterflow Alarm.
An approved audible/visual waterflow alarm (horn/strobe) shall be provided on the 
exterior of the building in a location approved by the AHJ."
(2)
NFPA 13D, Installation of Sprinkler Systems in One- and Two-Family Dwellings and 
Manufactured Homes, 
2019
2022
 edition.
(a)
NFPA 13D, 
Chapter 7
, Section 7.6, Alarms, is amended by adding a new subsection as 
follows:
"7.6.1 Exterior Waterflow Alarm.
When an alarm initiating device is included, an approved audible/visual waterflow alarm 
(horn/strobe) shall be provided on the exterior of the building in a location approved by the 
AHJ."
(b)
NFPA 13D, 
Chapter 7
, Section 7.6, Alarms, is amended by adding a new subsection as 
follows:
"7.6.2 Interior Alarm.
When an alarm initiating device is included, an interior fire alarm notification appliance 
is also required to sound throughout the dwelling. An approved audible sprinkler flow alarm to 
alert the occupants of the dwelling in a normally occupied location when the flow switch is 
activated must be provided."
(3)
NFPA, Standard 13R, Installation of Sprinkler Systems in Residential Occupancies up 
to and Including Four Stories in Height, 
2019
2022
 edition.
(a)
NFPA 13R, 
Chapter 6
, Section 6.8, Valves, is amended by adding a new subsection as 
follows:
"6.8.11 Floor/Zone Control Valves.
Individual floor/zone control valves shall be used at the riser at each floor for 
connections to piping serving floor areas in excess of 5,000 square feet or arranged in a 
manner acceptable to the AHJ."
(b)
NFPA 13R, 
Chapter 6
, Section 16, Alarms, is amended by adding a new subsection as 
follows:
"6.16.1.1 Local Waterflow Alarms.
When a fire alarm system is not required by IFC, Section 907.2, an approved 
notification appliance indicating waterflow shall be provided in the interior of each residential 
unit/tenant space, in a normally occupied location, to alert the occupants of the fire sprinkler 
system activation."
(c)
NFPA 13R, 
Chapter 6
, Section 16, Alarms, is amended by adding a new subsection as 
follows:
"6.16.1.2 Exterior Waterflow Alarm.
An approved audible/visual waterflow alarm (horn/strobe) shall be provided on the 
exterior of the building in a location approved by the AHJ."
(4)
NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire 
Protection Systems, 2020 edition.
NFPA 25, Section 5.3.4.4.1, the first line is deleted and replaced with the following:
"For system antifreeze installed prior to July 1, 2023, listed antifreeze shall not be 
required, where all of the following conditions are met:"
(5)
(4)
NFPA 72, National Fire Alarm and Signaling Code, 
2019
2022
 edition.
NFPA 72, a new Section 18.1.1.1 is added as follows:
"The fire code official may modify the requirements of this chapter in areas of 
educational occupancies used exclusively for special education students."
Section 11. 
Repealer.
Amendments and additions to NFPA related to manufacture, 
transportation, storage, and retail sales of fireworks.
Section 12. 
Effective Date.
This bill takes effect on 
July 1, 2026
.
3-2-26 10:42 AM