Building Construction Amendments
- Number
- H.B. 54 (2020GS)
- Sponsor
- Rep. Snider, C.
- Final action
- Governor Signed 3/24/2020
- Outcome
- Became law — signed by Gov. Gary R. Herbert
Summary
This bill amends the State Construction and Fire Codes Act and enacts provisions regarding the use of mass timber products.
What it does
- This bill:
- amends the definition of the State Construction Code to include standards for the use of mass timber products;
- enacts building standards for the use of mass timber products for residential and commercial building construction; and
- makes technical and conforming changes.
Every vote on this bill
1/27/2020House/ passed 3rd reading
Senate Secretary
74 0 1YEA1/31/2020Senate Comm - Favorable Recommendation
Senate Business and Labor Committee
6 0 2not eligible / no record2/12/2020Senate/ passed 2nd reading
Senate 3rd Reading Calendar
27 0 2not eligible / no record2/13/2020Senate/ circled
Senate 3rd Reading Calendar
Voice votenot eligible / no record2/13/2020Senate/ uncircled
Senate 3rd Reading Calendar
Voice votenot eligible / no record2/13/2020Senate/ passed 3rd reading
Senate President
26 0 3not eligible / no recordBill text
enrolled version · official source
BUILDING CONSTRUCTION AMENDMENTS GENERAL SESSION STATE OF UTAH Chief Sponsor: Casey Snider Senate Sponsor: Curtis S. Bramble LONG TITLE General Description: This bill amends the State Construction and Fire Codes Act and enacts provisions regarding the use of mass timber products. Highlighted Provisions: This bill: ▸ amends the definition of the State Construction Code to include standards for the use of mass timber products; ▸ enacts building standards for the use of mass timber products for residential and commercial building construction; and ▸ makes technical and conforming changes. Money Appropriated in this Bill: None Other Special Clauses: None Utah Code Sections Affected: AMENDS: 15A-1-102 , as enacted by Laws of Utah 2011, Chapter 14 15A-2-101 , as enacted by Laws of Utah 2011, Chapter 14 15A-2-102 , as last amended by Laws of Utah 2016, Chapter 249 ENACTS: 15A-2a-101 , Utah Code Annotated 1953 15A-2a-102 , Utah Code Annotated 1953 15A-2a-201 , Utah Code Annotated 1953 15A-2a-202 , Utah Code Annotated 1953 15A-2a-203 , Utah Code Annotated 1953 15A-2a-204 , Utah Code Annotated 1953 15A-2a-301 , Utah Code Annotated 1953 15A-2a-302 , Utah Code Annotated 1953 15A-2a-401 , Utah Code Annotated 1953 Be it enacted by the Legislature of the state of Utah: Section 1. Section 15A-1-102 is amended to read: 15A-1-102. Definitions. As used in this title: (1) "Board" means the Utah Fire Prevention Board created in Section 53-7-203 . (2) "Division" means the Division of Occupational and Professional Licensing created in Section 58-1-103 , except as provided in: (a) Part 4, State Fire Code Administration Act; and (b) Chapter 5, State Fire Code Act. (3) "State Construction Code" means the State Construction Code adopted by: (a) Chapter 2, Adoption of State Construction Code; (b) Chapter 2a, Tall Wood Buildings of Mass Timber Construction Incorporated as Part of State Construction Code; [ (b) ] (c) Chapter 3, Statewide Amendments Incorporated as Part of State Construction Code; [ and ] [ (c) ] (d) Chapter 4, Local Amendments Incorporated as Part of State Construction Code[ . ] ; and (e) Chapter 6, Additional Construction Requirements. (4) "State Fire Code" means the State Fire Code adopted by Chapter 5, State Fire Code Act. (5) "Utah Code" means the Utah Code Annotated (1953), as amended. Section 2. Section 15A-2-101 is amended to read: 15A-2-101. Title -- Adoption of code. (1) This chapter is known as the "Adoption of State Construction Code." (2) In accordance with Chapter 1, Part 2, State Construction Code Administration Act, the Legislature repeals the State Construction Code in effect on July 1, 2010, and adopts the following as the State Construction Code: (a) this chapter; (b) Chapter 2a, Tall Wood Buildings of Mass Timber Construction Incorporated as Part of State Construction Code; [ (b) ] (c) Chapter 3, Statewide Amendments Incorporated as Part of State Construction Code; [ and ] [ (c) ] (d) Chapter 4, Local Amendments Incorporated as Part of State Construction Code[ . ] ; and (e) Chapter 6, Additional Construction Requirements. Section 3. Section 15A-2-102 is amended to read: 15A-2-102. Definitions. As used in this chapter [ and ] , Chapter 2a, Tall Wood Buildings of Mass Timber Construction Incorporated as Part of State Construction Code, Chapter 3, Statewide Amendments Incorporated as Part of State Construction Code, and Chapter 4, Local Amendments Incorporated as Part of State Construction Code: (1) "HUD Code" means the Federal Manufactured Housing Construction and Safety Standards Act, as issued by the Department of Housing and Urban Development and published in 24 C.F.R. Parts 3280 and 3282 (as revised April 1, 1990). (2) "IBC" means the edition of the International Building Code adopted under Section 15A-2-103 . (3) "IEBC" means the edition of the International Existing Building Code adopted under Section 15A-2-103 . (4) "IECC" means the edition of the International Energy Conservation Code adopted under Section 15A-2-103 . (5) "IFGC" means the edition of the International Fuel Gas Code adopted under Section 15A-2-103 . (6) "IMC" means the edition of the International Mechanical Code adopted under Section 15A-2-103 . (7) "IPC" means the edition of the International Plumbing Code adopted under Section 15A-2-103 . (8) "IRC" means the edition of the International Residential Code adopted under Section 15A-2-103 . (9) "NEC" means the edition of the National Electrical Code adopted under Section 15A-2-103 . (10) "UWUI" means the edition of the Utah Wildland Urban Interface Code adopted under Section 15A-2-103 . Section 4. Section 15A-2a-101 is enacted to read: CHAPTER 2a. TALL WOOD BUILDINGS OF MASS TIMBER CONSTRUCTION INCORPORATED AS PART OF STATE CONSTRUCTION CODE Part 1. General Provisions 15A-2a-101. Title. (1) This chapter is known as "Tall Wood Buildings of Mass Timber Construction Incorporated as Part of State Construction Code." (2) This chapter establishes building standards for the use of mass timber products in residential and commercial building construction and is applicable statewide. (3) Where this chapter replaces a section of the IBC that Chapter 3, Statewide Amendments Incorporated as Part of State Construction Code, or Chapter 4, Local Amendments Incorporated as Part of State Construction Code, amends, the amendment in Chapter 3 or 4 shall apply to the IBC replacement in this chapter. Section 5. Section 15A-2a-102 is enacted to read: 15A-2a-102. Definitions. As used in this chapter: (1) "Mass timber" means a structural element of Type IV construction primarily of solid, built-up, panelized or engineered wood products that meet minimum cross section dimensions of Type IV construction. (2) "Non-combustible protection" (for mass timber) means non-combustible material in accordance with IBC Section 703.5, designed to increase the fire-resistance rating and delay the combustion of mass timber. (3) "Wall, load-bearing" means any wall meeting either of the following classifications: (a) any metal or wood stud wall that supports more than 100 pounds per linear foot (1459 N/m) of vertical load in addition to its own weight; or (b) any masonry or concrete, or mass timber wall that supports more than 200 pounds per linear foot (2919 N/m) of vertical load in addition to its own weight. Section 6. Section 15A-2a-201 is enacted to read: Part 2. Statewide Amendments to International Building Code 15A-2a-201. Amendments to Chapter 4 of IBC. In IBC, Section 403.3.2, is deleted and replaced with the following: "403.3.3 Water supply to required fire pumps. In all buildings that are more than 420 feet (128m) in building height, and buildings of Type IV-A and IV-B construction that are more than 120 feet in building height, required fire pumps shall be supplied by connections to not fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. Exception: Two connections to the same main shall be permitted provided that the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through not fewer than one of the connections." Section 7. Section 15A-2a-202 is enacted to read: 15A-2a-202. Amendments to Chapter 5 of IBC. (1) In IBC, Table 504.3, is deleted and replaced with the following: "Table 504.3 ALLOWABLE BUILDING HEIGHT IN FEET ABOVE GRADE PLANE OCCUPANCY CLASSIFICATION TYPE OF CONSTRUCTION SEE FOOTNOTES TYPE I TYPE II TYPE III TYPE IV TYPE V A B A B A B A B C HT A B A, B, E, F, M, S, U NS b UL S UL H-1, H-2, H-3, H-5 NS c, d UL S H-4 NS c, d UL S UL I-1 Condition 1, I-3 NS d, e UL S UL I-1 Condition 2, I-2 NS d, e, f UL S UL I-4 NS d, g UL S UL R h NS d UL S13D S13R S UL F or SI: 1 foot = 304.8 mm UL = Unlimited; NS = Buildings not equipped throughout with an automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3. a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter. b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies. c. New Group H occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.5. d. The NS value is only for use in evaluation of existing building area in accordance with the IEBC. e. New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies, Condition 1, see Exception 1 of Section 903.2.6. f. New and existing Group I-2 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the International Fire Code. g. New Group I-4 occupancies see Exceptions 2 and 3 of Section 903.2.6. h. New Group R occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.8." (2) In IBC, Table 504.4, "Allowable Number of Stories Above Grade Plane a, b " delete Type IV and replace it with the following, in relation to the occupancy classification and footnotes as indicated: OCCUPANCY CLASSIFICATION TYPE OF CONSTRUCTION SEE FOOTNOTES TYPE IV A B C HT A-1 NS S A-2 NS S A-3 NS S A-4 NS S A-5 NS UL S UL UL UL UL B NS S E NS S F-1 NS S F-2 NS S H-1 NS c, d NP NP NP S H-2 NS c, d S H-3 NS c, d S H-4 NS c, d S H-5 NS c, d S I-1 Condition 1 NS d, e S I-1 Condition 2 NS d, e S I-2 NS d, f NP NP NP S I-3 NS d, e S I-4 NS d, g S M NS S R-1 h NS d S13R S R-2 h NS d S13R S R-3 h NS d S13D S13R S R-4 h NS d S13D S13R S S-1 NS S S-2 NS S U NS S UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3. a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter. b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies. c. New Group H occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.5. d. The NS value is only for use in evaluation of existing building height in accordance with the IEBC. e. New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies, Condition 1, see Exception 1 of Section 903.2.6. f. New and existing Group I-2 occupancies are required to be protected by an automatic sprinkler system in accordance with Sections 903.2.6 and 1103.5 of the International Fire Code. g. For new Group I-4 occupancies, see Exceptions 2 and 3 of Section 903.2.6. h. New Group R occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.8." (3) In IBC, Table 506.2, "Allowable Area Factor (A t = NS, S1, S13R, S13D or SM, as applicable) in Square Feet a, b " delete Type IV and replace it with the following, in relation to the occupancy classification and footnotes as indicated: "OCCUPANCY CLASSIFICATION SEE FOOTNOTES TYPE OF CONSTRUCTION TYPE IV A B C HT A-1 NS 45,00 30,000 18,750 15,000 S1 180,0 120,000 75,000 60,000 SM 135,0 90,000 56,250 45,000 A-2 NS 45,00 30,000 18,750 15,000 S1 180,0 120,000 75,000 60,000 SM 135,0 90,000 56,250 45,000 A-3 NS 45,00 30,000 18,750 15,000 S1 180,0 120,000 75,000 60,000 SM 135,0 90,000 56,250 45,000 A-4 NS 45,00 30,000 18,750 15,000 S1 180,0 120,000 75,000 60,000 SM 135,0 90,000 56,250 45,000 A-5 NS UL UL UL UL S1 SM B NS 108,0 72,000 45,000 36,000 S1 432,0 288,000 180,000 144,000 SM 324,0 216,000 135,000 108,000 E NS 76,50 51,000 31,875 25,500 S1 306,0 204,000 127,500 102,000 SM 229,5 153,000 95,625 76,500 F-1 NS 100,5 67,000 41,875 33,500 S1 402,0 268,000 167,500 134,000 SM 301,5 201,000 125,625 100,500 F-2 NS 151,5 101,000 63,125 50,500 S1 606,0 404,000 252,500 202,000 SM 454,5 303,000 189,375 151,500 H-1 NS c 10,50 10,500 10,500 10,500 S1 H-2 NS c 10,50 10,500 10,500 10,500 S1 SM H-3 NS c 25,50 25,500 25,500 25,500 S1 SM H-4 NS c, d 72,00 54,000 40,500 36,000 S1 288,0 216,000 162,000 144,000 SM 216,0 162,000 121,500 108,000 H-5 NS c, d 72,00 54,000 40,500 36,000 S1 288,0 216,000 162,000 144,000 SM 216,0 162,000 121,500 108,000 I-1 NS d, e 54,00 36,000 18,000 18,000 S1 216,0 144,000 72,000 72,000 SM 162,0 108,000 54,000 54,000 I-2 NS d, f 36,00 24,000 12,000 12,000 S1 144,0 96,000 48,000 48,000 SM 108,0 72,000 36,000 36,000 I-3 NS d, e 36,00 24,000 12,000 12,000 S1 144,0 96,000 48,000 48,000 SM 108,0 72,000 36,000 36,000 I-4 NS d, g 76,50 51,000 25,500 25,500 S1 306,0 204,000 102,000 102,000 SM 229,0 153,000 76,500 76,500 M NS 61,50 41,000 25,625 20,500 S1 246,0 164,000 102,500 82,000 SM 184,5 123,000 76,875 61,500 R-1 h NS d 61,50 41,000 25,625 20,500 S13R S1 246,0 164,000 102,500 82,000 SM 184,5 123,000 76,875 61,500 R-2 h NS d 61,50 41,000 25,625 20,500 S13R S1 246,0 164,000 102,500 82,000 SM 184,5 123,000 76,875 61,500 R-3 h NS d UL UL UL UL S13D S13R S1 SM R-4 h NS d 61,50 41,000 25,625 20,500 S13D S13R S1 246,0 164,000 102,500 82,000 SM 184,5 123,000 76,875 61,500 S-1 NS 76,50 51,000 31,875 25,500 S1 306,0 204,000 127,500 102,000 SM 229,5 153,000 95,625 76,500 S-2 NS 115,5 77,000 48,125 38,500 S1 462,0 308,000 192,500 154,000 SM 346,5 308,000 144,375 115,500 U NS i 54,00 36,000 22,500 18,000 S1 216,0 144,000 90,000 72,000 SM 162,0 108,000 67,500 54,000 For SI: 1 square foot = 0.0929 m . UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S1 = Buildings a maximum of one story above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; SM = Buildings two or more stories above grade plane equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2; S13D = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.3. a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter. b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies. c. New Group H occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.5. d. The NS value is only for use in evaluation of existing building area in accordance with the IEBC. e. New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies, Condition 1, see Exception 1 of Section 903.2.6. f. New and existing Group I-2 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the International Fire Code. g. For New Group I-4 occupancies see Exceptions 2 and 3 of Section 903.2.6. h. New Group R occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.8. i. The maximum allowable area for a single-story nonsprinklered Group U greenhouse is permitted to be 9,000 square feet, or the allowable area shall be permitted to comply with Table C102.1 of Appendix C." (4) In IBC, Section 508.4.4 is deleted and replaced with the following: "508.4.4 Separation. Individual occupancies shall be separated from adjacent occupancies in accordance with Table 508.4." (5) In IBC, Section 508.4.4.1 is deleted and replaced with the following: "508.4.4.1 Construction. Required separations shall be fire barriers constructed in accordance with Section or horizontal assemblies constructed in accordance with Section 711, or both, so as to completely separate adjacent occupancies. Mass timber elements serving as fire barriers or horizontal assemblies to separate occupancies in Type IV-B or IV-C construction shall be separated from the interior of the building with an approved thermal barrier consisting of a minimum of 1/2 inch (12.7 mm) gypsum board or a material that is tested in accordance with and meets the acceptance criteria of both the Temperature Transmission Fire Test and the Integrity Fire Test of NFPA 275." (6) In IBC, Section 509, a new section is added as follows: "509.4.1.1 Type IV-B and IV-C construction. Where Table 509 specifies a fire-resistance-rated separation, mass timber elements serving as fire barriers or a horizontal assembly in Type IV-B or IV-C construction shall be separated from the interior of the incidental use with an approved thermal barrier consisting of a minimum of 1/2 inch (12.7 mm) gypsum board or a material that is tested in accordance with and meets the acceptance criteria of both the Temperature Transmission Fire Test and the Integrity Fire Test of NFPA 275." Section 8. Section 15A-2a-203 is enacted to read: 15A-2a-203. Amendments to Chapter 6 of IBC. (1) In IBC, Table 601 is deleted and replaced with the following: "TABLE 601 FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS) BUILDING ELEMENT TYPE I TYPE II TYPE III TYPE IV TYPE V A B A B A B A B C HT A B Primary structural frame f (see Section 202) a, b a, b 1b 1b 3a 2a 2a HT 1b Bearing walls Exterior e, f Interior a a 1/HT Nonbearing walls and partitions Exterior See Table 602 Nonbearing walls and partitions Interior d See Section 2304.1 1.2 Floor construction and associated secondary members (see Section 202) HT Roof construction and associated secondary members (see Section 202) 1/ b b, c b, c c b, c 1/2 HT b, c F or SI: 1 foot = 304.8 mm. a. Roof supports: Fire-resistance ratings of primary structural frame and bearing walls are permitted to be reduced by 1 hour where supporting a roof only. b. Except in Group F-1, H, M and S-1 occupancies, fire protection of structural members in roof construction shall not be required, including protection of primary structural frame members, roof framing and decking where every part of the roof construction is 20 feet or more above any floor immediately below. Fire-retardant-treated wood members shall be allowed to be used for such unprotected members. c. In all occupancies, heavy timber complying with Section 2304.11 shall be allowed where a 1-hour or less fire-resistance rating is required. d. Not less than the fire-resistance rating required by other sections of this code. e. Not less than the fire-resistance rating based on fire separation distance (see Table 602). f. Not less than the fire-resistance rating as referenced in Section 704.10." (2) In IBC, Table 602 is deleted and replaced with the following: "TABLE 602 FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE a, d, g Fire Separation Distance = X (feet) TYPE OF CONSTRUCTI ON OCCUPANC Y GROUP He OCCUPANCY GROUP F-1, M, S-1f OCCUPANCY GROUP A, B, F-2, I, R i , S-2, U h < 5b All ≤ X < 10 IA, IVA Others ≤ X < 30 IA, IB, IVA, IVB IIB, VB Others c c X ≥ 30 All F or SI: 1 foot = 304.8 mm. a. Load-bearing exterior walls shall also comply with the fire-resistance rating requirements of Table 601. b. See Section 706.1.1 for party walls. c. Open parking garages complying with Section 406 shall not be required to have a fire-resistance rating. d. The fire-resistance rating of an exterior wall is determined based upon the fire separation distance of the exterior wall and the story in which the wall is located. e. For special requirements for Group H occupancies, see Section 415.6. f. For special requirements for Group S aircraft hangars, see Section 412.3.1. g. Where Table 705.8 permits nonbearing exterior walls with unlimited area of unprotected openings, the required fire-resistance rating for the exterior walls is 0 hours. h. For a building containing only a Group U occupancy private garage or carport, the exterior wall shall not be required to have a fire-resistance rating where the fire separation distance is 5 feet (1523 mm) or greater. i. For a Group R-3 building of Type II-B or Type V-B construction, the exterior wall shall not be required to have a fire-resistance rating where the fire separation distance is 5 feet (1523 mm) or greater." (3) In IBC, Section 602.4 is deleted and replaced with the following: "602.4 Type IV. Type IV construction is that type of construction in which the building elements are mass timber or non-combustible materials and have fire-resistance ratings in accordance with Table 601. Mass timber elements shall meet the fire-resistance rating requirements of this section based on either the fire-resistance rating of the non-combustible protection, the mass timber, or a combination of both and shall be determined in accordance with Section 703.2 or 703.3. The minimum dimensions and permitted materials for building elements shall comply with the provisions of this section and Section 2304.11. Mass timber elements of Types IV-A, IV-B and IV-C construction shall be protected with non-combustible protection applied directly to the mass timber in accordance with Sections 602.4.1 through 602.4.3. The time assigned to the non-combustible protection shall be determined in accordance with Section 703.8 and comply with Section 722.7. Cross-laminated timber shall be labeled as conforming to PRG 320-18 as referenced in Section 2303.1.4. Exterior load-bearing walls and nonload-bearing walls shall be mass timber construction, or shall be of non-combustible construction. Exception: Exterior load-bearing walls and nonload-bearing walls of Type IV-HT Construction in accordance with Section 602.4.4. The interior building elements, including nonload-bearing walls and partitions, shall be of mass timber construction or of non-combustible construction. Exception: Interior building elements and nonload-bearing walls and partitions of Type IV-HT Construction in accordance with Section 602.4.4. Combustible concealed spaces are not permitted except as otherwise indicated in Sections 602.4.1 through 602.4.4. Combustible stud spaces within light frame walls of Type IV-HT construction shall not be considered concealed spaces, but shall comply with Section 718. In buildings of Type IV-A, B, and C, construction with an occupied floor located more than 75 feet above the lowest level of fire department access, up to and including 12 stories or feet above grade plane, mass timber interior exit and elevator hoistway enclosures shall be protected in accordance with Section 602.4.1.2. In buildings greater than 12 stories or 180 feet above grade plane, interior exit and elevator hoistway enclosures shall be constructed of non-combustible materials." (4) In IBC, Section 602.4.1 is deleted and replaced with the following: "602.4.1 Type IV-A. Building elements in Type IV-A construction shall be protected in accordance with Sections 602.4.1.1 through 602.4.1.6. The required fire-resistance rating of non-combustible elements and protected mass timber elements shall be determined in accordance with Section 703.2 or Section 703.3." (5) In IBC, Section 602, a new section is added as follows: "602.4.1.1 Exterior Protection. The outside face of exterior walls of mass timber construction shall be protected with non-combustible protection with a minimum assigned time of 40 minutes as determined in Section 722.7.1. All components of the exterior wall covering shall be on non-combustible material except water resistive barriers having a peak heat release rate of less than 150 kW/m , a total heat release of less than 20 MJ/m and an effective heat of combustion of less than 18 MJ/kg as determined in accordance with ASTM E1354 and having a flame spread index of 25 or less and a smoke-developed index of 450 or less as determined in accordance with ASTM E84 or UL723. The ASTM E1354 test shall be conducted on specimens at the thickness intended for use, in the horizontal orientation and at an incident radiant heat flux of 50 kW/m ." (6) In IBC, Section 602, a new section is added as follows: "602.4.1.2 Interior Protection. Interior faces of all mass timber elements, including the inside faces of exterior mass timber walls and mass timber roofs, shall be protected with materials complying with Section 703.5." (7) In IBC, Section 602, a new section is added as follows: "602.4.1.2.1 Protection Time. Non-combustible protection shall contribute a time equal to or greater than times assigned in Table 722.7.1(1), but not less than 80 minutes. The use of materials and their respective protection contributions listed in Table 722.7.1(2) shall be permitted to be used for compliance with Section 722.7.1." (8) In IBC, Section 602, a new section is added as follows: "602.4.1.3 Floors. The floor assembly shall contain a non-combustible material not less than one inch in thickness above the mass timber. Floor finishes in accordance with Section 804 shall be permitted on top of the non-combustible material. The underside of floor assemblies shall be protected in accordance with Section 602.4.1.2." (9) In IBC, Section 602, a new section is added as follows: "602.4.1.4 Roofs. The interior surfaces of roof assemblies shall be protected in accordance with Section 602.4.1.2. Roof coverings in accordance with Chapter 15 shall be permitted on the outside surface of the roof assembly." (10) In IBC, Section 602, a new section is added as follows: "602.4.1.5 Concealed spaces. Concealed spaces shall not contain combustibles other than electrical, mechanical, fire protection, or plumbing materials and equipment permitted in plenums in accordance with Section 602 of the IMC, and shall comply with all applicable provisions of Section 718. Combustible construction forming concealed spaces shall be protected in accordance with Section 602.4.1.2." (11) In IBC, Section 602, a new section is added as follows: "602.4.1.6 Shafts. Shafts shall be permitted in accordance with Sections 713 and 718. Both the shaft side and room side of mass timber elements shall be protected in accordance with Section 602.4.1.2." (12) In IBC, Section 602.4.2 is deleted and replaced with the following: "602.4.2 Type IV-B. Building elements in Type IV-B construction shall be protected in accordance with Sections 602.4.2.1 through 602.4.2.6. The required fire resistance rating of non-combustible elements or mass timber elements shall be determined in accordance with Section 703.2 or Section 703.3." (13) In IBC, Section 602, a new section is added as follows: "602.4.2.1 Exterior protection. The outside face of exterior walls of mass timber construction shall be protected with non-combustible protection with a minimum assigned time of 40 minutes as determined in Section 722.7.1. All components of the exterior wall covering shall be of non-combustible material except water resistive barriers having a peak heat release rate of less than 150 kW/m , a total heat release of less than 20 MJ/m and an effective heat of combustion of less than 18MJ/kg as determined in accordance with ASTM E1354, and having a flame spread index of or less and a smoke-developed index of 450 or less as determined in accordance with ASTM E84 or UL 723. The ASTM E1354 test shall be conducted on specimens at the thickness intended for use, in the horizontal orientation and at an incident radiant heat flux of kW/m ." (14) In IBC, Section 602, a new section is added as follows: "602.4.2.2 Interior protection. Interior faces of all mass timber elements, including the inside face of exterior mass timber walls and mass timber roofs, shall be protected, as required by this section, with materials complying with Section 703.5." (15) In IBC, Section 602, a new section is added as follows: "602.4.2.2.1 Protection time. Non-combustible protection shall contribute a time equal to or greater than times assigned in Table 722.7.1(1), but not less than 80 minutes. The use of materials and their respective protection contributions listed in Table 722.7.1(2) shall be permitted to be used for compliance with Section 722.7.1." (16) In IBC, Section 602, a new section is added as follows: "602.4.2.2.2 Protected area. All interior faces of all mass timber elements shall be protected in accordance with Section 602.4.2.2.1, including the inside face of exterior mass timber walls and mass timber roofs. Exceptions: Unprotected portions of mass timber ceilings and walls complying with Section 602.4.2.2.4 and the following: 1. Unprotected portions of mass timber: (a) ceilings, including attached beams, shall be permitted and shall be limited to an area equal to 20% of the floor area in any dwelling unit or fire area; (b) walls, including attached columns, shall be permitted and shall be limited to an area equal to 40% of the floor area in any dwelling unit or fire area; or (c) walls and ceilings, including attached columns and beams, in any dwelling unit or fire area shall be permitted in accordance with Section 602.4.2.2.3. 2. Mass timber columns and beams which are not an integral portion of walls or ceilings, respectively, shall be permitted to be unprotected without restriction of either aggregate area or separation from one another." (17) In IBC, Section 602, a new section is added as follows: "602.4.2.2.3 Mixed unprotected areas. In each dwelling unit or fire area, where both portions of ceilings and portions of walls are unprotected, the total allowable unprotected area shall be determined in accordance with Equation 6-1. (Utc/Ua c) + (Utw/Ua w) 1 (Equation 6-1) where: Utc = Total unprotected mass timber ceiling areas Ua c = Allowable unprotected mass timber ceiling area conforming to Section 602.4.2.2.2, Exception 1 Utw = Total unprotected mass timber wall areas Ua w = Allowable unprotected mass timber wall area conforming to Section 602.4.2.2.2, Exception 2." (18) In IBC, Section 602, a new section is added as follows: "602.4.2.2.4 Separation distance between unprotected mass timber elements. In each dwelling unit or fire area, unprotected portions of mass timber walls and ceilings shall be not less than 15 feet from unprotected portions of other walls and ceilings, measured horizontally along the ceiling and from other unprotected portions of walls measured horizontally along the floor." (19) In IBC, Section 602, a new section is added as follows: "602.4.2.3 Floors. The floor assembly shall contain a non-combustible material not less than one inch in thickness above the mass timber. Floor finishes in accordance with Section 804 shall be permitted on top of the non-combustible material. The underside of floor assemblies shall be protected in accordance with Section 602.4.1.2." (20) In IBC, Section 602, a new section is added as follows: "602.4.2.4 Roofs. The interior surfaces of roof assemblies shall be protected in accordance with Section 602.4.2.2 except, in non-occupiable spaces, they shall be treated as a concealed space with no portion left unprotected. Roof coverings in accordance with Chapter 15 shall be permitted on the outside surface of the roof assembly." (21) In IBC, Section 602, a new section is added as follows: "602.4.2.5 Concealed spaces. Concealed spaces shall not contain combustibles other than electrical, mechanical, fire protection, or plumbing materials and equipment permitted in plenums in accordance with Section 602 of the IMC, and shall comply with all applicable provisions of Section 718. Combustible construction forming concealed spaces shall be protected in accordance with Section 602.4.1.2." (22) In IBC, Section 602, a new section is added as follows: "602.4.2.6 Shafts. Shafts shall be permitted in accordance with Section 713 and Section 718. Both the shaft side and room side of mass timber elements shall be protected in accordance with Section 602.4.1.2." (23) In IBC, Section 602.4.3 is deleted and replaced with the following: "602.4.3 Type IV-C. Building elements in Type IV-C construction shall be protected in accordance with Sections 602.4.3.1 through 602.4.3.6. The required fire-resistance rating of building elements shall be determined in accordance with Section 703.2 or Section 703.3." (24) In IBC, Section 602, a new section is added as follows: "602.4.3.1 Exterior Protection. The exterior side of walls of combustible construction shall be protected with non-combustible protection with a minimum assigned time of 40 minutes as determined in Section 722.7.1. All components of the exterior wall covering shall be of non-combustible material except water resistive barriers having a peak heat release rate of less than 150 kW/m , a total heat release of less than 20 MJ/m and an effective heat of combustion of less than 18MJ/kg as determined in accordance with ASTM E1354 and having a flame spread index of or less and a smoke-developed index of 450 or less as determined in accordance with ASTM E84 or UL723. The ASTM E1354 test shall be conducted on specimens at the thickness intended for use, in the horizontal orientation and at an incident radiant heat flux of 50 kW/m ." (25) In IBC, Section 602, a new section is added as follows: "602.4.3.2 Interior protection. Mass timber elements are permitted to be unprotected." (26) In IBC, Section 602, a new section is added as follows: "602.4.3.3 Floors. Floor finishes in accordance with Section 804 shall be permitted on top of the floor construction." (27) In IBC, Section 602, a new section is added as follows: "602.4.3.4 Roofs. Roof coverings in accordance with Chapter 15 shall be permitted on the outside surface of the roof assembly." (28) In IBC, Section 602, a new section is added as follows: "602.4.3.5 Concealed spaces. Concealed spaces shall not contain combustibles other than electrical, mechanical, fire protection, or plumbing materials and equipment permitted in plenums in accordance with Section 602 of the IMC, and shall comply with all applicable provisions of Section 718. Combustible construction forming concealed spaces shall be protected with non-combustible protection with a minimum assigned time of 40 minutes as determined in Section 722.7.1." (29) In IBC, Section 602, a new section is added as follows: "602.4.3.6 Shafts. Shafts shall be permitted in accordance with Section 713 and Section 718. Shafts and elevator hoistway and interior exit stairway enclosures shall be protected with non-combustible protection with a minimum assigned time of 40 minutes as determined in Section 722.7.1, on both the inside of the shaft and the outside of the shaft." (30) In IBC, Section 602, a new section is added as follows: "602.4.4 Type IV-HT. Type IV construction (Heavy Timber, HT) is that type of construction in which the exterior walls are of non-combustible materials and the interior building elements are of solid wood, laminated heavy timber or structural composite lumber (SCL), without concealed spaces. The minimum dimensions for permitted materials including solid timber, glued-laminated timber, structural composite lumber (SCL) and cross laminated timber (CLT) and details of Type IV construction shall comply with the provisions of this section and Section 2304.11. Exterior walls complying with Section 602.4.4.1 or 602.4.4.2 shall be permitted. Interior walls and partitions not less than one-hour fire-resistance rating or heavy timber conforming with Section 2304.11.2.2 shall be permitted." (31) In IBC, Section 602, a new section is added as follows: "602.4.4.1 Fire-retardant-treated wood in exterior walls. Fire-retardant-treated wood framing and sheathing complying with Section 2303.2 shall be permitted within exterior wall assemblies not less than 6 inches (152 mm) in thickness with a two-hour rating or less." (32) In IBC, Section 602, a new section is added as follows: "602.4.4.2 Cross-laminated timber in exterior walls. Cross-laminated timber complying with Section 2303.1.4 shall be permitted within exterior wall assemblies not less than 6 inches (152 mm) in thickness with a two-hour rating or less, provided the exterior surface of the cross-laminated timber is protected by one the following: 1. fire-retardant-treated wood sheathing complying with Section 2303.2 and not less than 15/32 inch (12 mm) thick; 2. gypsum board not less than 1/2 inch (12.7 mm) thick; or 3. a non-combustible material." (33) In IBC, Section 602, a new section is added as follows: "602.4.4.3 Exterior structural members. Where a horizontal separation of 20 feet (6096 mm) or more is provided, wood columns and arches conforming to heavy timber sizes complying with Section 2304.11 shall be permitted to be used externally." Section 9. Section 15A-2a-204 is enacted to read: 15A-2a-204. Amendments to Chapter 7 of IBC. (1) In IBC, Section 703, a new section is added as follows: "703.8 Determination of non-combustible protection time contribution. The time, in minutes, contributed to the fire-resistance rating by the non-combustible protection of mass timber building elements, components, or assemblies, shall be established through a comparison of assemblies tested using procedures set forth in ASTM E119 or UL263. The test assemblies shall be identical in construction, loading, and materials, other than the non-combustible protection. The two test assemblies shall be tested to the same criteria of structural failure. (a) Test Assembly 1 shall be without protection. (b) Test Assembly 2 shall include the representative non-combustible protection. The protection shall be fully defined in terms of configuration details, attachment details, joint sealing details, accessories and all other relevant details. The non-combustible protection time contribution shall be determined by subtracting the fire-resistance time, in minutes, of Test Assembly 1 from the fire-resistance time, in minutes, of Test Assembly 2." (2) In IBC, Section 703, a new section is added as follows: "703.9 Sealing of adjacent mass timber elements. In buildings of Type IV-A, IV-B, and IV-C construction, sealant or adhesive shall be provided to resist the passage of air in the following locations: 1. At abutting edges and intersections of mass timber building elements required to be fire-resistance-rated. 2. At abutting intersections of mass timber building elements and building elements of other materials where both are required to be fire-resistance-rated. Sealants shall meet the requirements of ASTM C920. Adhesives shall meet the requirements of ASTM D3498. Exception: Sealants or adhesives need not be provided where they are not a required component of a tested fire-resistance-rated assembly." (3) In IBC, Section 718.2.1 is deleted and replaced with the following: "718.2.1 Fireblocking materials. Fireblocking shall consist of the following materials: 1. Two-inch (51 mm) nominal lumber. 2. Two thicknesses of 1-inch (25 mm) nominal lumber with broken lap joints. 3. One thickness of 0.719-inch (18.3 mm) wood structural panels with joints backed by 0.719-inch (18.3 mm) wood structural panels. 4. One thickness of 0.75-inch (19.1 mm) particleboard with joints backed by 0.75-inch (19 mm) particleboard. 5. 1/2 inch (12.7 mm) gypsum board. 6. 1/4 inch (6.4 mm) cement-based millboard. 7. Batts or blankets of mineral wool, mineral fiber or other approved materials installed in such a manner as to be securely retained in place. 8. Cellulose insulation installed as tested for the specific application. 9. Mass timber complying with Section 2304.11." (4) In IBC, Section 722, a new section is added as follows: "722.7 Fire-Resistance rating of mass timber. The required fire resistance of mass timber elements in Section 602.4 shall be determined in accordance with Section 703.2 or Section 703.3. The fire-resistance rating of building elements shall be as required in Tables 601 and 602 and as specified elsewhere in this code. The fire-resistance rating of the mass timber elements shall consist of the fire-resistance of the unprotected element added to the protection time of the non-combustible protection." (5) In IBC, Section 722, a new section is added as follows: "722.7.1 Minimum required protection. Where required by Sections 602.4.1 through 602.4.3, non-combustible protection shall be provided for mass timber building elements in accordance with Table 722.7.1(1). The rating, in minutes, contributed by the non-combustible protection of mass timber building elements, components, or assemblies, shall be established in accordance with Section 703.8. The protection contributions indicated in Table 722.7.1(2) and Section 722.7.2 shall be deemed to comply with this requirement when installed and fastened in accordance with Section 722.7.2." (6) In IBC, Section 722, a new table is added as follows: "TABLE 722.7.1(1) PROTECTION REQUIRED FROM NON-COMBUSTIBLE COVERING MATERIAL Required Fire Resistance Rating of Building Element per Tables 601 and 602 (hours) Minimum Protection Required from Non-combustible or more 120" (7) In IBC, Section 722, a new table is added as follows: "TABLE 722.7.1(2) PROTECTION PROVIDED BY NON-COMBUSTIBLE COVERING MATERIAL Non-combustible Protection Protection (minutes) 1/2 inch Type X Gypsum /8 inch Type X Gypsum Board 40" (8) In IBC, Section 722, a new section is added as follows: "722.7.2 Installation of gypsum board non-combustible protection. Gypsum board complying with Table 722.7.1(2) shall be installed in accordance with this section." (9) In IBC, Section 722, a new section is added as follows: "722.7.2.1 Interior surfaces. Layers of Type X gypsum board serving as non-combustible protection for interior surfaces of wall and ceiling assemblies determined in accordance with Table 722.7.1(1) shall be installed in accordance with the following: 1. Each layer shall be attached with Type S drywall screws of sufficient length to penetrate the mass timber at least 1 inch when driven flush with the paper surface of the gypsum board. Exception: The third layer, where determined necessary by Section 722.7, shall be permitted to be attached with 1 inch #6 Type S drywall screws to furring channels in accordance with ASTM C645. 2. Screws for attaching the base layer shall be 12 inches on center in both directions. 3. Screws for each layer after the base layer shall be 12 inches on center in both directions and offset from the screws of the previous layers by 4 inches in both directions. 4. All panel edges of any layer shall be offset 18 inches from those of the previous layer. 5. All panel edges shall be attached with screws sized and offset as in items 1 through above and placed at least 1 inch but not more than 2 inches from the panel edge. 6. All panels installed at wall-to-ceiling intersections shall be installed such that ceiling panels are installed first and the wall panels are installed after the ceiling panel has been installed and is fitted tight to the ceiling panel. Where multiple layers are required, each layer shall repeat this process. 7. All panels installed at a wall-to-wall intersection shall be installed such that the panels covering an exterior wall or a wall with a greater fire resistance rating shall be installed first and the panels covering the other wall shall be fitted tight to the panel covering the first wall. Where multiple layers are required, each layer shall repeat this process. 8. Panel edges of the face layer shall be taped and finished with joint compound. Fastener heads shall be covered with joint compound. 9. Panel edges protecting mass timber elements adjacent to unprotected mass timber elements in accordance with Section 602.4.2.2 shall be covered with 1-1/4 inch metal corner bead and finished with joint compound." (10) In IBC, Section 722, a new section is added as follows: "722.7.2.2 Exterior surfaces. Layers of Type X gypsum board serving as non-combustible protection for the outside of the exterior heavy timber walls determined in accordance with Table 722.7.1(1) shall be fastened 12 inches on center each way and 6 inches on center at all joints or ends. All panel edges shall be attached with fasteners located at least 1 inch but not more than 2 inches from the panel edge. Fasteners shall comply with one of the following: 1. Galvanized nails of minimum 12 guage with a 7/16 inch head of sufficient length to penetrate the mass timber a minimum of 1 inch. 2. Screws which comply with ASTM C1002 (Type S, Type W, or Type G) of sufficient length to penetrate the mass timber a minimum of 1 inch." (11) In IBC, Section 1705, a new section is added as follows: "1705.19 Sealing of mass timber. Periodic special inspections of sealants or adhesives shall be conducted where sealant or adhesive required by Section 703.9 is applied to mass timber building elements as designated in the approved construction documents." (12) In IBC, Section 3102.3 is deleted and replaced with the following: "3102.3 Type of construction. Non-combustible membrane structures shall be classified as Type IIB construction. Non-combustible frame or cable-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IIB construction. Heavy timber frame-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IV-HT construction. Other membrane structures shall be classified as Type V construction. Exception: Plastic less than 30 feet (9144 mm) above any floor used in greenhouses, where occupancy by the general public is not authorized, and for aquaculture pond covers is not required to meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701." (13) In IBC, Section 3102.6.1.1 is deleted and replaced with the following: "3102.6.1.1 Membrane. A membrane meeting the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 shall be permitted to be used as the roof or as a skylight on buildings of Type IIB, III, IV-HT and V construction, provided that the membrane is not less than 20 feet (6096 mm) above any floor, balcony or gallery." Section 10. Section 15A-2a-301 is enacted to read: Part 3. Statewide Amendments to International Fire Code 15A-2a-301. Amendments to Chapter 7 of IFC. In IFC, Section 701.6 is deleted and replaced with the following: "701.6 Owner's responsibility. The owner shall maintain an inventory of all required fire-resistance-rated construction, construction installed to resist the passage of smoke and the construction included in Sections 703 through 707 and Sections 602.4.1 and 602.4.2 of the International Building Code. Such construction shall be visually inspected by the owner annually and properly repaired, restored or replaced where damaged, altered, breached or penetrated. Records of inspections and repairs shall be maintained. Where concealed, such elements shall not be required to be visually inspected by the owner unless the concealed space is accessible by the removal or movement of a panel, access door, ceiling tile or similar movable entry to the space." Section 11. Section 15A-2a-302 is enacted to read: 15A-2a-302. Amendments to Chapters 9 and 33 of IFC. (1) In IFC, Section 914.3.1.2 is deleted and replaced with the following: "914.3.1.2 Water supply to required fire pumps. In all buildings that are more than 420 feet (128m) in building height, and buildings of Type IV-A and IV-B construction that are more than 120 feet in building height, required fire pumps shall be supplied by connections to not fewer than two water mains located in different streets. Separate supply piping shall be provided between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. Exception: Two connections to the same main shall be permitted provided that the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through not fewer than one of the connections." (2) In IFC, Section 3308, a new section is added as follows: "3308.9 Fire safety requirements for buildings of Types IV-A, IV-B, and IV-C construction. Buildings of Types IV-A, IV-B, and IV-C construction designed to be greater than six stories above grade plane shall comply with the following requirements during construction unless otherwise approved by the fire code official: 1. Standpipes shall be provided in accordance with Section 3313. 2. A water supply for fire department operations, as approved by the fire code official and the fire chief. 3. Where building construction exceeds six stories above grade plane, at least one layer of non-combustible protection where required by Section 602.4 of the International Building Code shall be installed on all building elements more than 4 floor levels, including mezzanines, below active mass timber construction before erecting additional floor levels. Exception: Shafts and vertical exit enclosures shall not be considered a part of the active mass timber construction. 4. Where building construction exceeds six stories above grade plane required exterior wall coverings shall be installed on all floor levels more than 4 floor levels, including mezzanines, below active mass timber construction before erecting additional floor level. Exception: Shafts and vertical exit enclosures shall not be considered a part of the active mass timber construction." Section 12. Section 15A-2a-401 is enacted to read: Part 4. Reference Standards 15A-2a-401. Reference Standards. ASTM D3498-03(2011): Standard Specification for Adhesives for Field-Gluing Plywood to Lumber Framing for Floor Systems ASTM International Barr Harbor Drive, P.O. Box C700 West Conshohocken, PA 19428-2959